| 2016-01-11 09:14:15 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010116 |
| | ADD: 418 KANUGA DR. UNITS 4,5 & 6 |
| | CONT: CANA LLC |
| | TEL: 954-410-1784 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JAN. 11/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) THERE IS A DISCREPANCY IN THE ADDRESSING OF THE |
| | PERMIT APPLICATION VERSES THE PLANS. THE PERMIT |
| | APPLICATION INDICATES WORK BEING COMPLETED IN UNITS 4,5 |
| | & 6 WHEREAS THE PLANS INDICATE WORK TO BE COMPLETED IN |
| | UNITS 1,2,3 &4. PLEASE PROVIDE ADDITIONAL INFORMATION, |
| | 107.2.1.3. |
| | |
| | 2) SHEET S-2 SHOWS NEW 1/2 INCH DRYWALL BEING APPLIED |
| | TO THE TENANT SEPARATION WALL. PLEASE PROVIDE |
| | COMPLIANCE WITH: |
| | 2014 FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING |
| | DWELLING UNITSIN THE SAME BUILDING, WALLS SEPARATING |
| | SLEEPING UNITS IN THE SAME BUILDING AND WALLS |
| | SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER |
| | OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME BUILDING |
| | SHALL BE CONSTRUCTED AS FIRE PARTITIONSIIN ACCORDANCE |
| | WITH SECTION 708. |
| | |
| | 2014 FBC 708.3 FIRE RE-SISTANCE RATINGS REQUIRE 1 HR. |
| | SEE EXCEPTIONS. CORRIDOR WALL 1/2 HR. OR VB 1/2 HR. |
| | WHEN AUTOMATIC SPRINKLER IN ACCORDANCE WITH 903.3.1.1. |
| | |
| | 3) PLEASE PROVIDE EITHER A RATED WALL ASSEMBLY DETAIL |
| | FOR EITHER U.L. LISTING OR GYPSUM ASSOCIATION FOR THE |
| | TENANT FIRE PARTITION. 708.3 FIRE RESISTANCE RATING. |
| | |
| | 4) PLEASE PROVIDE A CUT SECTION THROUGH THE TENANT FIRE |
| | PARTION IN COMPLIANCE WITH: |
| | 2014 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND |
| | FROM THE TOP OF THE FOUNDATION OR FLOOR/CEILING |
| | ASSEMBLY BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF |
| | SHEATHING, SLAB OR DECK ABOVE OR TO THE |
| | FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING |
| | ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED THERETO. |
| | IN COMBUSTIBLE CONSTRUCTION WHERE THE FIRE PARTITIONS |
| | ARE NOT REQUIRED TO BE CONTINUOUS TO THE SHEATHING, |
| | DECK OR SLAB, THE SPACE BETWEEN THE CEILING AND THE |
| | SHEATHING, DECK OR SLAB ABOVE SHALL BE FIREBLOCKED OR |
| | DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS 718.2 AND |
| | 718.3 AT THE PARTITION LINE. THE SUPPORTING |
| | CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED |
| | FIRE-RESISTANCE RATING OF THE WALL SUPPORTED, EXCEPT |
| | FOR WALLS SEPARATING TENANT SPACES IN COVERED AND OPEN |
| | MALL BUILDINGS, WALLS SEPARATING DWELLING UNITS, WALLS |
| | SEPARATING SLEEPING UNITS AND CORRIDOR WALLS, IN |
| | BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION. |
| | |
| | 5) SHEET S-1 NOTE 18 INDICATES THE USE OF 5/8 INCH TYPE |
| | X DRYWALL TO BE ATTACHED TO THE CEILING FRAMING. PLEASE |
| | PROVIDE A RATED FLOOR ASSEMBLY DETAIL FROM EITHER U.L. |
| | LISTING OR GYPSUM ASSOCIATION FOR THE HORIZONTAL |
| | ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME |
| | BUILDING. |
| | |
| | 2014 FBC-B 420.3 HORIZONTAL SEPARATION. FLOOR |
| | ASSEMBLIES SEPARATING DWELLING UNITS IN THE SAME |
| | BUILDINGS, FLOOR ASSEMBLIES SEPARATING SLEEPING UNITS |
| | IN THE SAME BUILDING AND FLOOR ASSEMBLIES SEPARATING |
| | DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES |
| | CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE |
| | CONSTRUCTED AS HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH |
| | SECTION 711. |
| | |
| | 2014 FBC-B 711.3 FIRE-RESISTANCE RATING. THE |
| | FIRE-RESISTANCE RATING OF FLOOR AND ROOF ASSEMBLIES |
| | SHALL NOT BE LESS THAN THAT REQUIRED BY THE BUILDING |
| | TYPE OF CONSTRUCTION. HORIZONTAL ASSEMBLIES SEPARATING |
| | DWELLING UNITS IN THE SAME BUILDING AND HORIZONTAL |
| | ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME |
| | BUILDING SHALL BE A MINIMUM OF 1-HOUR |
| | FIRE-RESISTANCE-RATED CONSTRUCTION. |
| | |
| | EXCEPTION: DWELLING UNIT AND SLEEPING UNIT SEPARATIONS |
| | IN BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION |
| | SHALL HAVE FIRE-RESISTANCE RATINGS OF NOT LESS THAN 1/2 |
| | HOUR IN BUILDINGS EQUIPPED THROUGHOUT WITH AN AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1. |
| | |
| | 6) AREAS OF THE 1ST FLOOR WHERE THE CEILING IS BEING |
| | REMOVED AND COMPLIANCE WITH FLOOR INSULATION CAN BE |
| | ACHIEVED WITH THE FOLLOWING CODE SECTIONS: |
| | |
| | 6A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 6B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 6C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2014 720.2 |
| | CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE |
| | CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF |
| | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 7) SHEET S-2 DOES NOT SHOW WHERE ATTIC ACCESS WILL BE |
| | ACHIEVED FBC-B 1209.2 ATTIC SPACES. AN OPENING NOT LESS |
| | THAN 20 INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE |
| | PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF |
| | OVER 30 INCHES (762 MM). CLEAR HEADROOM OF NOT LESS |
| | THAN 30 INCHES (762 MM) SHALL BE PROVIDED IN THE ATTIC |
| | SPACE AT OR ABOVE THE ACCESS OPENING. |
| | |
| | 8) SHEET S-3 THE PROPOSED ROOF PLAN DOES NOT SHOW HOW |
| | COMPLIANCE WITH THE 2014 FBC-B: |
| | 1203.2 ATTIC SPACES. ENCLOSED ATTICS AND ENCLOSED |
| | RAFTER SPACES FORMED WHERE CEILINGS ARE APPLIED |
| | DIRECTLY TO THE UNDERSIDE OF ROOF FRAMING MEMBERS SHALL |
| | HAVE CROSS VENTILATION FOR EACH SEPARATE SPACE BY |
| | VENTILATION OPENINGS PROTECTED AGAINST THE ENTRANCE OF |
| | RAIN AND SNOW. BLOCKING AND BRIDGING SHALL BE ARRANGED |
| | SO AS NOT TO INTERFERE WITH THE MOVEMENT OF AIR. AN |
| | AIRSPACE OF NOT LESS THAN 1 INCH (25 MM) SHALL BE |
| | PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING. |
| | THE NET FREE VENTILATING AREA SHALL NOT BE LESS THAN |
| | 1/150TH OF THE AREA OF THE SPACE VENTILATED. |
| | |
| | 9) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (B) WINDOWS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | |
| | 10) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 11) SHEET S-3 THE WINDOW DETAIL IS MISSING COMPLIANCE |
| | WITH: 2014 FBC-B TABLE 2308.9.5 HEADER SPANS. 22FT. 10 |
| | INCHES. 2-2X4'S ON THE VERTICAL W/ 1 JACK STUD FOR |
| | CARRYING A ROOF AND CEILING LOAD. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |