| 2016-01-14 10:58:27 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. THE RISER AS SHOWN ON THE DRAWINGS DOES NOT MATCH |
| | THE DEVICE COUNT ON PLANS. |
| | 2. NEWLY INSTALLED FIRE ALARM SYSTEMS SHALL BE |
| | MONITORED AS INDICATED BY THE SEQUENCE OF OPERATION, |
| | BUT THE SIGNAGE SHOWN ON THE PLANS CONFLICT WITH THIS |
| | REQUIREMENT. WALL PLACARDS HAVE BEEN CROSSED OUT ON THE |
| | PLANS. REVISE THE DRAWING ACCORDINGLY. |
| | 3. PER NFPA REQUIREMENTS YOU SHALL PROVIDE 75 DB AT THE |
| | PILLOW AT EACH SLEEPING AREA. REVISE YOUR DRAWING AND |
| | DEVICE PLACEMENT FOR COMPLIANCE WITH SUCH. |
| | 4. ONCE DEVICE COUNT GETS ADJUSTED TO MEET MINIMUM |
| | AUDIBILITY REQUIREMENTS, ADJUST THE RISER DIAGRAM, |
| | BATTERY AND VOLTAGE DROP CALCS AS REQUIRED. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |