Plan Review Details - Permit 16010112
Plan Review Stops For Permit 16010112
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-05 Cont ID  
Sent By vperez Date 2016-02-05 Time 08:40 Rev Time 0.00
Received By vperez Date 2016-02-05 Time 08:39 Sent To FIRE
Notes
2016-02-05 08:41:48SENT TO FIRE DEPARTMENT TO RESTAMP INITIAL SHEET
 RESUBMITTED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-14 Cont ID  
Sent By albarran Date 2016-01-14 Time 10:57 Rev Time 0.00
Received By albarran Date 2016-01-08 Time 10:07 Sent To I
Notes
2016-01-14 10:58:27THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE RISER AS SHOWN ON THE DRAWINGS DOES NOT MATCH
 THE DEVICE COUNT ON PLANS.
 2. NEWLY INSTALLED FIRE ALARM SYSTEMS SHALL BE
 MONITORED AS INDICATED BY THE SEQUENCE OF OPERATION,
 BUT THE SIGNAGE SHOWN ON THE PLANS CONFLICT WITH THIS
 REQUIREMENT. WALL PLACARDS HAVE BEEN CROSSED OUT ON THE
 PLANS. REVISE THE DRAWING ACCORDINGLY.
 3. PER NFPA REQUIREMENTS YOU SHALL PROVIDE 75 DB AT THE
 PILLOW AT EACH SLEEPING AREA. REVISE YOUR DRAWING AND
 DEVICE PLACEMENT FOR COMPLIANCE WITH SUCH.
 4. ONCE DEVICE COUNT GETS ADJUSTED TO MEET MINIMUM
 AUDIBILITY REQUIREMENTS, ADJUST THE RISER DIAGRAM,
 BATTERY AND VOLTAGE DROP CALCS AS REQUIRED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-08 Cont ID  
Sent By pleduc Date 2016-02-08 Time   Rev Time 0.00
Received By pleduc Date 2016-02-08 Time 11:36 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-07 Cont ID  
Sent By pleduc Date 2016-01-07 Time   Rev Time 0.00
Received By pleduc Date 2016-01-07 Time 14:08 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-08 Cont ID  
Sent By pleduc Date 2016-02-08 Time   Rev Time 0.00
Received By pleduc Date 2016-02-01 Time 11:10 Sent To  
Notes
2016-02-02 11:10:58ALBARRAN'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-14 Cont ID  
Sent By albarran Date 2016-01-14 Time 10:59 Rev Time 0.00
Received By albarran Date 2016-01-06 Time 12:45 Sent To  
Notes
2016-01-14 11:00:181/14/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL DENIED BIN "L".
 MA
2016-01-06 12:45:31ROUTED TO FIRE