Plan Review Details - Permit 16010042
Plan Review Stops For Permit 16010042
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-01-13 Cont ID  
Sent By cthroop Date 2016-01-13 Time 15:44 Rev Time 0.00
Received By cthroop Date 2016-01-13 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-07 Cont ID  
Sent By cthroop Date 2016-01-07 Time 09:52 Rev Time 0.00
Received By cthroop Date 2016-01-07 Time 09:52 Sent To E
Notes
2016-01-07 10:07:40CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 REFERENCE CURRENT CODES ON PLANS. 2014 FBC 5TH EDITION
 PROVIDE FLOOR PLAN WITH DEMENSIONS, CANNOT VERIFY
 PROPOSED FLOOR SPAN.
 PROVIDE DETAIL FOR FLOOR JOIST BEARING AT CMU WALL,
 (DETAIL 1, PG S-1).
 PROVIDE ATTACHMENT DETAIL FOR LEDGER BOARDS.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2016-01-13 Cont ID  
Sent By mvaldes Date 2016-01-13 Time 10:34 Rev Time 0.00
Received By mvaldes Date 2016-01-13 Time 10:34 Sent To  
Notes
2016-01-13 10:36:35FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 -DRAWING SHOW NO ELECTRIC WILL BE SUBMITTED SEPERATELY.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-13 Cont ID  
Sent By cthroop Date 2016-01-13 Time 15:44 Rev Time 0.00
Received By cthroop Date 2016-01-04 Time 10:07 Sent To  
Notes
2016-01-05 10:07:44BLDG -$5000

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-01-13 Cont ID  
Sent By cthroop Date 2016-01-13 Time 15:44 Rev Time 0.00
Received By cthroop Date 2016-01-13 Time 15:44 Sent To  
Notes
***NONE***