Plan Review Details - Permit 15120871
| Plan Review Stops For Permit 15120871 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2016-01-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-12-31 |
Time |
06:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-12-31 |
Time |
06:07 |
Sent To |
|
|
| Notes |
| 2015-12-31 06:33:14 | 1) SUBMIT 2 COPIES OF A COMPLETE GAS PIPING DIAGRAM FOR | | | REVIEW. THERE WAS NO GAS PIPING DIAGRAM ASSOCIATWD WITH | | | THE POOL PERMIT. | | | | | | 2). SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL | | | GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. | | | G2413. | | | | | | 3.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE | | | CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE. | | | WPB AMENDMENTS TO FBC SEC.107.2.1. | | | | | | 4). BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD | | | ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS | | | SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 | | | (37) OR 2014 FBC-RES. SEC. G2413. | | | | | | 5). SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN | | | THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS | | | SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. | | | | | | 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. | | | SEC. G2413.2. . | | | | | | 7) THE GAS INSTALLATION SHALL BE INSTALLED BY | | | CERTIFIED GAS OR PLUMBING CONTR. | | | | | | ***NOTE*** AN ELECTRIC PERMIT MAY ALSO BE REQUIRED. | | | GAS BY SEPARATE PERMIT. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-12-31 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-12-31 |
Time |
06:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-12-30 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2015-12-30 13:58:28 | PLUMB -$5000 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-01-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-01-05 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-01-05 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
|