 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW. YOU MAY CHOOSE TO SEND ME RESPONSES TO THESE
 COMMENTS VIA E-MAIL.
  
 PROVIDE FLOOR PLAN.
 DOOR SCHEDULE IDENTIFIES THE SUBJECT DOOR AS WOOD &/OR
 FIBERGLASS. THE NOA PROVIDED IS FOR A STEEL DOOR.
 CLARIFY WHAT A WINDOW JUMB IS?
 PROVIDE DETAIL FOR VERTICAL RE-INFORCING AT NEW
 OPENING.
 PROVIDE DETAIL FOR METAL FRAMING TO EXISTING LINTEL.
 1010.9 HANDRAILS.
 RAMPS WITH A RISE GREATER THAN 6 INCHES (152 MM) SHALL
 HAVE HANDRAILS ON BOTH SIDES. HANDRAILS SHALL COMPLY
 WITH SECTION 1012.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-22 Cont ID  
Sent By skennedy Date 2016-03-22 Time 14:32 Rev Time 0.00
Received By skennedy Date 2016-03-22 Time 14:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By mvaldes Date 2016-02-08 Time 09:39 Rev Time 0.00
Received By mvaldes Date 2016-02-08 Time 09:39 Sent To  
Notes
2016-02-08 09:40:58JOB PERMIT NUMBER: 15120858
 JOB ADDRESS: 3071 CONTINENTAL DR
 WEST PALM BEACH 33407
 DATE: FEB 8 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. 1 PLEASE ADD TO NOTES NEC 700.12 (F) (4) - EMERGENCY
 LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF SAME LOCAL
 AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY THE AREA,
 EM LIGHTS MAY BE ON OWN CIRCUIT.
 2. FBC 1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED.
 THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE,
 SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE
 SERVED BY THE MEANS OF EGRESS ARE OCCUPIED. ( THIS IS A
 RECOMMENDATION FOR THE PURPOSES OF LIFE SAFETY NO
 EXTERIOR SECURITY LIGHTING SHOWN WOULD BE A GOOD IDEA
 TO ADD FOR THE OUTSIDE OF THE BUILDING. ESPECIALLY TO
 ILLUMINATE ADA RAMP. )
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-08 Cont ID  
Sent By pleduc Date 2016-02-05 Time   Rev Time 0.00
Received By pleduc Date 2016-02-05 Time 11:05 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-12-30 Cont ID  
Sent By pleduc Date 2015-12-30 Time   Rev Time 0.00
Received By pleduc Date 2015-12-30 Time 16:45 Sent To B
Notes
2015-12-30 16:52:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. THERE IS NO INDICATION OF THE OCCUPANCY OR THE
 OCCUPANCY LOAD THIS EXIT DOOR SERVES.
  
 2. THERE IS NO INDICATION OF THE INTERIOR FLOOR PLAN
 THAT THIS DOOR SERVES.
  
 3. THERE IS NO INDICATION OF THE LOCKING/LATCHING
 DEVICE ON THIS DOOR.
  
 4. THERE IS NO INDICATION OF THE EXIT HARDWARE ATTACHED
 TO THIS DOOR.
  
 5. THERE IS NO INDICATION OF AN EXIT SIGN OR EMERGENCY
 LIGHT ON THE INSIDE OF THIS DOOR.
  
 6. THIS INSTALLATION SHALL COMPLY WITH THE 5TH EDITION
 OF THE FLORIDA FIRE PREVENTION CODE INCLUDING, BUT NOT
 LIMITED TO, NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-08 Cont ID  
Sent By cpuell Date 2016-02-08 Time 10:01 Rev Time 0.00
Received By cpuell Date 2016-01-27 Time 13:47 Sent To  
Notes
2016-01-28 13:47:14RESUB ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-07 Cont ID  
Sent By cthroop Date 2016-01-07 Time 10:16 Rev Time 0.00
Received By cthroop Date 2016-01-07 Time 10:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-02-01 Cont ID  
Sent By sgraham Date 2016-02-01 Time 13:26 Rev Time 0.00
Received By sgraham Date 2016-02-01 Time 13:26 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-01-05 Cont ID  
Sent By sgraham Date 2016-01-05 Time 09:34 Rev Time 0.00
Received By sgraham Date 2016-01-05 Time 09:34 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved