Plan Review Details - Permit 15120847
Plan Review Stops For Permit 15120847
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By jwitmer Date 2016-03-14 Time 08:21 Rev Time 0.00
Received By jwitmer Date 2016-03-14 Time 08:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-11 Cont ID  
Sent By jwitmer Date 2016-01-11 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2016-01-11 Time 09:22 Sent To  
Notes
2016-01-11 11:15:11BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120847
 ADD: 2087 PALM BEACH LAKES BLVD
 CONT: TWT RESTAURANT DESIGN
 TEL: 813-886-8555
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 11/ 2016
 ACTION: DENIED
  
 1) SHEET A0.1:
  
 1A) WIND DESIGN CRITERIA, INDICATES THE ULTIMATE WIND
 LOAD OF 160 MPH. PLEASE SEE THE 2014 FBC-B FIGURE 1609A
 FOR CATEGORY II BUILDINGS, WEST PALM BEACH IS LOACATED
 IN A 170 VULT WIND ZONE. PLEASE CORRECT.
  
 1B) THE OCCUPANT LOAD TABLE UNDER THE 53 SQ. FT./5= 11
 NOT 10. WHEN THERE IS A FRACTION OF AN OCCUPANT YOU
 ROUND UP TO THE NEXT FULL OCCUPANT. 2014 FBC-B TABLE
 1004.1.2.
  
 2) SHEET A1.1;
  
 2A) SHEET A0.1 INDICATES INSIDE AND OUTSIDE SEATING
 THERE WILL BE 125 OCCUPANTS. SHEET A1.1 ONLY SHOWS ONE
 ACCESSBILE SEATING LOCATION. PLEASE SHOW COMPLIANCE
 WITH 2014 FBC-ACC. CODE SECTION 226.1 WHICH REQUIRES AT
 LEAST 5% (OR 7 SEATS) OF THE SEATS SHALL COMPLY WITH
 902.
  
 2B) SHEET A0.1 ALSO WILL NEED TO SHOW WHERE THE 7 SEATS
 WILL BE DISPERSED THROUGHOUT AND SHOW COMPLIANCE WITH
 902.
  
 2C) PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE WITH THE
 2014 FBC-ACC. CODE; 902.3 DINING SURFACES HEIGHT.
  
 2D) PLEASE PROVIDE FOR THE SEATING NEAREST THE
 RESTROOMS THE COMMON PATH OF TRAVEL FROM THE FURTHEST
 SEAT TO THE NEAREST EGRESS DOOR. SHOW COMPLIANCE WITH
 SECTION 1028.10.1.2 OF THE 2014 FBC-B SEATING AT TABLES
 AISLE ACCESS LEGTH SHALL NOT EXCEED 30 FT. WHERE A
 PERSON HAS A CHOICE OF 2 OR MORE PATHS OF EGRESS TRAVEL
 TO SEPARATE EXITS.
  
 2E) THE DOOR THAT LEADS INTO THE MENS RESTROOM, THERE
 IS A RECTANGLE THAT IS SHOWN 3/4'S THE WAY OFF THE
 WALL, WHAT IS REPRESENTED BY THIS FIGURE, THIS DOOR IS
 SUPPOSE TO HAVE 24 INCHES CLEAR SPACE, FROM THE LATCH
 APPROACH PULL SIDE OF THE DOOR. SEE 2014
 FBC-ACCESSIBILITY CODE FIGURE 404.2.4.1(H).
  
 3) SHEET M2.2:
  
 3A) PLEASE NOTE UNDER THE SHELL PERMIT ONLY THE ROOF
 TOP CURBS WERE BEING PERMITED. IT WILL BE THE
 RESPONSIBILITY OF THE TENANT BUILDOUT DESIGN TEAM TO
 SUPPLY THE WIND DESIGN FOR EQUIPMENT THAT WILL BE
 ANCHORED ABOVE THE ROOF LINE. THIS SHEET SHOWS A NEW
 PENETRATION THROUGH THE ROOF ASSEMBLY THE INTAKE FAN
 KEF-1. PLEASE PROVIDE STRUCTURAL SHEETS SHOWING THE NEW
 PENETRATION OF THE ROOF DECK, THE FRAMING AROUND THE
 NEW HOLE AND THE REQUIRED FASTENERS FOR THE NEW ROOF
 TOP CURB, AS WELL AS ROOF FRAMING FOR THE NEW ROOF TOP
 A/C STANDS. 2014 FBC-B , 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 3B) 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES. ROOF TOP CURBS
 (G) PRE-ENGINEERED A/C STANSD.
  
 3C) PLEASE PROVIDE THE ATTACHMENT DETAILS FROM THE ROOF
 TOP CURB TO THE AIR HANDLERS AND FOM THE A/C STANDS TO
 THE ROOF TOP CONDENSING UNITS. 2014 FBC-B ,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 3D) PLEASE PROVIDE THE WIDTH OF THE ROOF TOP CONDENSING
 UNITS THAT WILL BE ATTACHED TO THE ROOF TOP STAND, TO
 SHOW COMPLIANCE WITH 2014 FBC-B TABLE 1522.3.
  
 3E) THIS SHEET DOES NOT INDICATE HOW ACCESS TO THE
 ROOFTOP EQUIPMENT WILL BE ACHIEVED? ? 1509.6.4
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-17 Cont ID  
Sent By albarran Date 2016-03-17 Time 17:57 Rev Time 0.00
Received By albarran Date 2016-03-17 Time 15:56 Sent To  
Notes
2016-03-17 17:57:53ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 CORRECTED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-02-04 Cont ID  
Sent By albarran Date 2016-02-04 Time 18:30 Rev Time 0.00
Received By albarran Date 2016-02-04 Time 16:37 Sent To  
Notes
2016-02-04 18:31:321ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
  
 (A) SHEET E1.0
 1. THE FLORIDA FIRE PREVENTION CODE IN FORCE FOR THIS
 PROJECT IS THE 2012 EDITION.
 (BELOW COMMENTS 2 & 3 ARE ADDITIONAL NOTES TO THE BOXES
 SECTION)
 2. REVISE THIS SECTION TO INCLUDE:
 4. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 5. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 (B) SHEET E2.0
 3. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS.
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
 (C) SHEET E3.0
 4. THOUGH YOU INDICATE A SIGN OUTLET ABOVE EVERY DOOR,
 THE PANEL SCHEDULE CALLS THEM EXIT SIGNS; NOT THE
 INTENT. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH
 COMMERCIAL BUILDING AND EACH COMMERCIAL OCCUPANCY
 ACCESSIBLE TO PEDESTRIANS SHALL BE PROVIDED WITH AT
 LEAST ONE 20 AMP DEDICATED OUTLET IN AN ACCESSIBLE
 LOCATION AT EACH ENTRANCE TO EACH TENANT SPACE FOR SIGN
 OR OUTLINE LIGHTING. SERVICE HALLWAYS OR CORRIDORS
 SHALL NOT BE CONSIDERED ACCESSIBLE TO PEDESTRIANS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-02 Cont ID  
Sent By albarran Date 2016-02-02 Time 18:45 Rev Time 0.00
Received By albarran Date 2016-02-02 Time 17:40 Sent To  
Notes
2016-02-02 18:46:291ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 SHEET E1.0
 1. THE FLORIDA FIRE PREVENTION CODE IN FORCE FOR THIS
 PROJECT IS THE 2014 EDITION.
 (BELOW COMMENTS 2 & 3 ARE ADDITIONAL NOTES TO THE BOXES
 SECTION)
 2. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 3. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
  
 4. MISSING ELECTRICAL SHEETS E2.0 & E3.0. PROVIDE THE
 MISSING SHEETS FOR ELECTRICAL REVIEW. PLEASE MAKE SURE
 THAT THE LIGHTING SHEET INCLUDES A FIXTURE SCHEDULE
 ALONG WITH THE REQUIRED ALLOWABLE LIGHTING DENSITY
 CHART INDICATING COMPLIANCE WITH THE FBC-EC405
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-04 Cont ID  
Sent By scaldero Date 2016-01-04 Time 16:10 Rev Time 0.00
Received By scaldero Date 2016-01-04 Time 15:56 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-03-17 Cont ID  
Sent By gjohnson Date 2016-03-17 Time 14:18 Rev Time 0.00
Received By gjohnson Date 2016-03-17 Time 14:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-01-13 Cont ID  
Sent By gjohnson Date 2016-01-13 Time 14:32 Rev Time 0.00
Received By gjohnson Date 2016-01-13 Time 14:32 Sent To  
Notes
2016-01-13 14:42:541ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-07 Cont ID  
Sent By cpuell Date 2016-04-07 Time 13:36 Rev Time 0.00
Received By cpuell Date 2016-03-31 Time 11:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-18 Cont ID  
Sent By lmarchan Date 2016-03-18 Time 07:41 Rev Time 0.00
Received By lmarchan Date 2016-03-03 Time 14:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-05 Cont ID  
Sent By cpuell Date 2016-02-05 Time 07:54 Rev Time 0.00
Received By cpuell Date 2015-12-30 Time 15:41 Sent To  
Notes
2016-02-02 18:51:182/2/16 COMPLETED ELECTRICAL REVIEW. LEM & SAK NOTIFIED
 VIA EMAIL. MA

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-04-05 Cont ID  
Sent By ccole Date 2016-04-05 Time 14:51 Rev Time 0.00
Received By ccole Date 2016-04-05 Time 14:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-14 Cont ID  
Sent By ccole Date 2016-03-14 Time 11:52 Rev Time 0.00
Received By ccole Date 2016-03-14 Time 11:52 Sent To  
Notes
2016-03-14 12:08:412ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120847
 3/14/16
  
 1) THE RESPONSE NARRATIVE FROM THE ENGINEER TO THE
 PREVIOUS MECHANICAL COMMENTS IS STATING THAT THE DUCT
 SMOKE DETECTORS ARE UNDER THE LANDLORD'S PERMIT. PLEASE
 NOTE THE UPLOADED PLANS AND DOCUMENTS SHOW COMPLETE AC
 SYSTEMS AND MUCH BE REVIEWED AND APPROVED AS SUCH.
 OTHERWISE, THE SYSTEMS' DETAILS AND SPECIFICATIONS WILL
 HAVE TO BE REMOVED FROM THE SCOPE OF THE PROJECT, BUT
 THEN HOW WOULD THIS TENANT BUILD-OUT PERMIT BE FINALED
 OUT FOR CO? PLEASE NOTE THAT THE REVISION #16030102
 THAT HAS BEEN SUBMITTED UNDER THE SHELL PERMIT
 #15090236 HAS BEEN DISAPPROVED BY THE STRUCTURAL PLANS
 EXAMINER. PLEASE REVIEW THE COMMENTS.
 2) ENERGY CALCULATIONS HAVE BEEN SUBMITTED FOR THE
 PROPOSED PROJECT, HOWEVER NO AC COOLING AND HEATING
 CALCULATIONS HAVE BEEN SUBMITTED- PLEASE SEE SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION AND SUBMIT THE
 CALCS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-04 Cont ID  
Sent By ccole Date 2016-01-04 Time 14:30 Rev Time 0.00
Received By ccole Date 2016-01-04 Time 14:30 Sent To  
Notes
2016-01-04 14:47:571ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120847
 01/04/16
  
 1) SHEETS A0.1 & M1.1: THE SQUARE FOOT AREA
 CALCULATIONS SHOWN ON THESE PLAN SHEETS DO NOT MATCH-
 PLEASE REVIEW AND CORRECT.
 2) IN ACCORDANCE WITH TABLE 403.3 FBC-14 MECHANICAL,
 KITCHENS SHALL HAVE A REQUIRED EXHAUST RATE OF .7 PER
 SF. CLARIFY HOW THIS DEMAND IS BEING MET IN THE
 PREP/DISHWASH ROOM- NO EXHAUST IS SHOWN ON THE PLAN.
 3) INDICATE HOW THE DS DETECTORS WILL BE SUPERVISED,
 AND CLARIFY IF THE RTU'S WILL BE LINKED TO TOGETHER FOR
 SIMULTANEOUS SHUT-DOWN IF ANY SINGLE DETECTOR SHOULD
 ACTIVATE.
 4) THE CITY OF WPB REQUIRES SEPARATE PERMITS AND PLANS
 FOR THE KITCHEN HOOD AND EXHAUST SYSTEM, AND THE
 WALK-IN COOLER/FREEZER. PLEASE PLACE NOTES ON THE PLANS
 ACCORDINGLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-04-07 Cont ID  
Sent By gjohnson Date 2016-04-07 Time 11:53 Rev Time 0.00
Received By gjohnson Date 2016-04-07 Time 11:53 Sent To  
Notes
2016-04-07 11:57:44PLUMBING PROVISO:
  
 PROVIDE APPROVED WATER ISOMETRIC RISER DIAGRAM BEFORE
 ROUGH PLUMBING INSPECTION.
 PER WPB AMEND. TO FBC SEC. 107.3.5.1.3(13)
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-03-17 Cont ID  
Sent By gjohnson Date 2016-03-17 Time 13:30 Rev Time 0.00
Received By gjohnson Date 2016-03-17 Time 13:30 Sent To  
Notes
2016-03-17 13:29:242ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
  
 1.SHT. P.1 GREASE INTERCEPTOR CALCULATIONS ARE FOR A
 STANDARD CONCRETE VAULT TANK BUT YOU REFERENCE A CODE
 SEC THAT APPLIES TO A HYDROMECHANICAL GREASE
 INTERCEPTOR PLEASE CLARIFY.
 2. PLEASE PROVIDE PERMIT NUMBER FOR GREASE INTERCEPTOR
 INSTALLED BY LANDLORD PER WPB AMEND TO FBC SEC 107.2.1
 3. SHT. P.2 ON RISER DIAGRAM YOU CALL OUT A 1250 GAL
 CONCRETE GREASE TRAP ON THE FLOOR PLAN YOU CALL OUT A
 SCHIER GB250 PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC
 107.2.1
 4. SHT P.2 FLOOR DRAIN IN COOK LINE IN FRONT OF STEAMER
 , FLOOR DRAIN IN APPETIZER AREA INFRONT OF CHIP WARMER
 , THESE FLOOR DRAINS ARE NOT VENTED SHALL COMPLY WITH
 FBC PL SEC 901.1.2
 5. PROVIDE WATER RISER DIAGRAM . PER WPB AMEND TO FBC
 SEC 107.3.5.1.3(13)
 6. SHT FS-3 THE PIPING CONNECTING FLOOR DRAINS DOES NOT
 MATCH P.2 PLEASE CLARIFY PER WPB AMEND TO FBC SEC
 107.2.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-13 Cont ID  
Sent By gjohnson Date 2016-01-13 Time 06:42 Rev Time 0.00
Received By gjohnson Date 2016-01-13 Time 06:42 Sent To  
Notes
2016-01-13 06:45:321ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHALL INCLUDE EMPLOYEES IN OCCUPANT LOAD PER FBC
 SEC1604.1
 2.SHT. P.1 GREASE INTERCEPTOR CALCULATIONS ARE FOR A
 STANDARD CONCRETE VAULT TANK BUT YOU REFERENCE A CODE
 SEC THAT APPLIES TO A HYDROMECHANICAL GREASE
 INTERCEPTOR PLEASE CLARIFY.
 3. PLEASE PROVIDE PERMIT NUMBER FOR GREASE INTERCEPTOR
 INSTALLED BY LANDLORD PER WPB AMEND TO FBC SEC 107.2.1
 4. SHT. P.2 ON RISER DIAGRAM YOU CALL OUT A 1250 GAL
 CONCRETE GREASE TRAP ON THE FLOOR PLAN YOU CALL OUT A
 SCHIER GB250 PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC
 107.2.1
 5. SHT P.2 FLOOR DRAIN IN COOK LINE AREA NEXT TO
 PREP/DISHWASHER , FLOOR DRAIN IN APPETIZER AREA ,FLOOR
 DRAIN AND HUB DRAINS IN CASHERS AREA, FLOOR DRAIN IN
 WALKWAY BETWEEN THE PREPP/DISHWASHER AND THE REST OF
 THE KIT AREA. THESE FOOR DRAIN ARE NOT VENTED SHALL
 COMPLY WITH FBC PL SEC 901.1.2
 6. PROVIDE WATER RISER DIAGRAM . PER WPB AMEND TO FBC
 SEC 107.3.5.1.3(13)
 7. SHT FS-3 THE PIPING CONNECTING FLOOR DRAINS DOES NOT
 MATCH P.2 PLEASE CLARIFY PER WPB AMEND TO FBC SEC
 107.2.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-04-07 Cont ID  
Sent By skennedy Date 2016-04-07 Time 16:05 Rev Time 0.00
Received By skennedy Date 2016-04-07 Time 16:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-04-06 Cont ID  
Sent By skennedy Date 2016-04-06 Time 17:48 Rev Time 0.00
Received By skennedy Date 2016-04-06 Time 17:17 Sent To  
Notes
2016-04-06 17:48:181ST REVIEW: FBC 2014 5TH ED.
  
 SIGNATURE REVIEW.
  
 THE BELOW PLAN SHEETS BY MICHAEL ARRIGO AR0017335 ARE
 NOT DIGITALLY SIGNED AS HIS OTHER SHEETS ARE. PLEASE
 UPON NOTIFICATION THAT THE REVIEW CYCLE IS COMPLETE,
 UPLOAD ONLY THOSE SHEETS INTO THE "SIGNATURE" FOLDER
 THROUGH THE PROJECTDOX SYSTEM.
  
 SHEETS G1.1, A2.1, A3.1, A3.2, FS-1, FS-2,
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-03-11 Cont ID  
Sent By jroach Date 2016-03-11 Time 12:04 Rev Time 0.00
Received By jroach Date 2016-03-11 Time 12:04 Sent To  
Notes
2016-03-11 12:04:20PROVISO
  
 THE NEON SIGNS SHOWN AS PROPOSED IN THE WINDOWS SHALL
 NOT BE PERMITTED AS THE MAXIMUM # OF PERMITTED SIGNS
 HAS ALREADY BEEN REACHED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT 561.822.1448 OR VIA EMAIL AT [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2016-01-22 Cont ID  
Sent By jroach Date 2016-01-22 Time 14:10 Rev Time 0.00
Received By jroach Date 2016-01-22 Time 14:10 Sent To  
Notes
2016-01-22 14:11:17PROVISO
  
 THE NEON SIGNS SHOWN AS PROPOSED IN THE WINDOWS SHALL
 NOT BE PERMITTED AS THE MAXIMUM # OF PERMITTED SIGNS
 HAS ALREADY BEEN REACHED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT 561.822.1448 OR VIA EMAIL AT [email protected]
2016-01-08 15:47:171/8/16