Plan Review Details - Permit 15120782
Plan Review Stops For Permit 15120782
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-12-30 Cont ID  
Sent By aclange Date 2015-12-30 Time 16:21 Rev Time 0.00
Received By aclange Date 2015-12-30 Time 16:11 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-25 Cont ID  
Sent By albarran Date 2016-01-25 Time 15:50 Rev Time 0.00
Received By albarran Date 2016-01-25 Time 14:04 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-13 Cont ID  
Sent By albarran Date 2016-01-13 Time 13:47 Rev Time 0.00
Received By albarran Date 2016-01-13 Time 11:57 Sent To I
Notes
2016-01-13 13:48:07THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. ACCORDING TO THE NOTES ON THE SUBMITTED PLANS, THE
 SERVICE IS TO BE RELOCATED. THE PERMIT APPLICATION
 SHALL BE REVISED TO INCLUDE THIS AS WELL.
 2. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM
 SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS
 SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR
 SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE
 SITE SPECIFIC.
 3. NEC 408.4 CIRCUIT DIRECTORY AND/OR IDENTIFICATION:
 THE CIRCUIT DIRECTORY AS SHOWN IS NOT CORRECT. THOUGH
 IT MAY MATCH THE LOADS INDICATED ON THE SUBMITTED SPEC
 SHEETS, THEY HAVE TO BE CORRECTED TO MATCH THE UNITS
 PROPOSED & INSTALLATION. ACCORDING TO THE SPEC SHEET
 AND THE PANEL SCHEDULES, YOUR GREATER LOADS ARE GOING
 TO THE CU RATHER THAN THE AH WHICH IS WHERE THE 9.6 KW
 HEATER IS TO BE PLACED.
 4. THE OCP SHALL BE AS SPECIFIED ON THE UNIT NAME PLATE
 AND CORRECTED SPEC SHEET.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-25 Cont ID  
Sent By albarran Date 2016-01-25 Time 15:53 Rev Time 0.00
Received By albarran Date 2016-01-21 Time 09:29 Sent To  
Notes
2016-01-25 16:06:221/25/16 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL READY BIN "D". MA
2016-01-22 09:29:12RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-13 Cont ID  
Sent By albarran Date 2016-01-13 Time 13:49 Rev Time 0.00
Received By albarran Date 2015-12-23 Time 17:43 Sent To  
Notes
2016-01-13 13:50:391/13/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL DENIED BIN "D".
 MA
2015-12-23 17:43:30BLDG MISC 1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-01-25 Cont ID  
Sent By ccole Date 2016-01-25 Time 12:18 Rev Time 0.00
Received By ccole Date 2016-01-25 Time 12:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-31 Cont ID  
Sent By ccole Date 2015-12-31 Time 07:21 Rev Time 0.00
Received By ccole Date 2015-12-31 Time 07:21 Sent To  
Notes
2015-12-31 07:32:361ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120782
 12/31/15
  
 1) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 ATTACHMENT OF THE CU BRACKET TO THE EXTERIOR WALL, AND
 ATTACHMENT OF THE CU TO THE BRACKET- SECTION 301.15
 FBC-14 MECHANICAL. THE ENGINEER OF RECORD SHALL PROVIDE
 THE WINDLOAD DESIGN CRITERIA, AND PROVIDE REVIEW AND
 APPROVSL SIGNATURES ON THE SUBMITTALS FOR THE WALL
 BRACKET AND TIE DOWN CLIPS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  