| 2016-01-06 11:41:08 | 1) SUBMIT A NARRATIVE THAT CLEARLY DESRIBES THE CHANGES |
| | THAT WERE MADE TO THE PLUMBING SYSTEMS. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 2) THE PLANS SHOW GAS APPLIANCES. THE GAS SHALL BE |
| | UNDER A SEPARATE PERMIT. THIS SHALL BE NOTED ON THE |
| | PLANS.TWO COPIES OF A GAS RISER ALONG WITH TWO COPIES |
| | OF MANUFACTURER'S SPECIFICATIONS FOR EACH GAS APPLIANCE |
| | SHALL BE SUBMITTED ALONG WITH A PERMIT APPLICATION WHEN |
| | SUBMITTING FOR THE GAS PERMIT. |
| | 3) SHT. A1 -SAN. RISER - BATH #4 - A VENT IS REQUIRED |
| | BETWEEN THE SHOWER AND TUB. 2014 FBCR SEC.P3101.2. |
| | 4) SHT. A1 - SAN. RISER - VIP BATH - A VENT IS REQUIRED |
| | BETWEEN THE SHOWER AND THE WATER CLOSET. 2014 FBCR |
| | SEC.P3101.2. |
| | 5) SHT. A1 - SAN.RISER - BATH #3 - A VENT IS REQUIRED |
| | BETWEEN THE SHOWER AND THE WATER CLOSET. 2014 FBCR |
| | SEC.P3101.2. |
| | 6) SHT. A1 - SAN. RISER - THERE IS A FLAT, DRY VENT ON |
| | THE DRAIN AT THE FISH TANK ON THE 2ND FLOOR. THE VENT |
| | MUST BEE TAKEN OFF ABOVE THE CENTERLINE OF THE DRAIN TO |
| | WHICH IT CONNECTS. 2014 FBCR SEC. P3104.3. |
| | 7) SHT. A5 SHOWS A POWER WASHER IN A/C STOR AREA #2, |
| | SHOW THE WATER CONNECTION TO THIS UNIT ON THE WATER |
| | RISER. IF IT IS SUPPLIED BY A HOSE FROM THE HOSE BIBB |
| | NOTE THIS ON THE PLAN. |
| | 8) SHT. A6 - THE FLOR PLAN SHOWS A DRYER IN THE SECOND |
| | FLOOR LAUNDRY BUT NO WASHING MACHINE, BUT THE SANITARY |
| | AND WATER RISER SHOWS A WASHING MACHINE. CLARIFY. |
| | 9) SHT. A6 - TWO LAVATORIES ARE SHOWN ON THE FLOOR PLAN |
| | IN THE MASTER BATH BUT ONLY ONE IS SHOWN ON THE |
| | SANITARY RISER.CLARIFY. |
| | 10) ALL FLOOR DRAINS CONNECTED TO THE SANITARY SYSTEM |
| | SHALL BE EQUIPPED WITH TRAP PRIMERS. 2014 FBCR |
| | SEC.P3201.2. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |