Plan Review Details - Permit 15120711
Plan Review Stops For Permit 15120711
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-01-12 Cont ID  
Sent By rmcdouga Date 2016-01-12 Time 08:25 Rev Time 0.00
Received By rmcdouga Date 2016-01-12 Time 07:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-01-12 Cont ID  
Sent By rmcdouga Date 2016-01-12 Time 08:25 Rev Time 0.00
Received By rmcdouga Date 2016-01-12 Time 07:58 Sent To  
Notes
2016-01-12 08:24:56PROVIDE A 20 AMP BRANCH CIRCUIT FOR THE BATHROOM AND A
 GFCI PROTECTED WALL RECEPTACLE OUTLET AT THE LAVATORY
 PER 2014 FBCR E3703.4 & E3901.6.
 INSTALL SMOKE ALARMS AS REQUIRED BY FBCR 314.3.1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-12 Cont ID  
Sent By rmcdouga Date 2016-01-12 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2015-12-21 Time 09:54 Sent To  
Notes
2015-12-22 09:57:36R14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-01-12 Cont ID  
Sent By rmcdouga Date 2016-01-12 Time 08:25 Rev Time 0.00
Received By rmcdouga Date 2016-01-12 Time 08:25 Sent To  
Notes
2016-01-12 08:44:00BATHROOM AIR SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS. FBCR M1507.2

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-12-31 Cont ID  
Sent By tklarge Date 2015-12-31 Time 05:51 Rev Time 0.00
Received By tklarge Date 2015-12-31 Time 05:40 Sent To  
Notes
***NONE***