Plan Review Details - Permit 15120707
Plan Review Stops For Permit 15120707
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-01-14 Cont ID  
Sent By mvaldes Date 2016-01-14 Time 09:46 Rev Time 0.00
Received By mvaldes Date 2016-01-14 Time 09:46 Sent To  
Notes
2016-01-14 10:09:201ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 PROVISO : FACP B IN MECHANICAL ROOM DOESN'T HAVE A
 SMOKE DETECTOR PLEASE INSTALL PRIOIR TO INSPECTION.
 NFPA 72 2010 EDTION 10.15* PROTECTION OF FIRE ALARM
 SYSTEM. IN AREAS THAT ARE NOT
 CONTINUOUSLY OCCUPIED, AUTOMATIC SMOKE DETECTION SHALL
 BE
 PROVIDED AT THE LOCATION OF EACH FIRE ALARM CONTROL
 UNIT(S),
 NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDERS, AND
 SUPERVISING
 STATION TRANSMITTING EQUIPMENT TO PROVIDE NOTIFICATION
 OF
 FIRE AT THAT LOCATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-29 Cont ID  
Sent By lmarchan Date 2016-01-19 Time 10:39 Rev Time 0.00
Received By scaldero Date 2015-12-29 Time 11:50 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-19 Cont ID  
Sent By lmarchan Date 2016-01-19 Time 10:38 Rev Time 0.00
Received By lmarchan Date 2015-12-21 Time 10:43 Sent To FIRE
Notes
***NONE***