| 2016-01-15 15:07:29 | CHRISTOPHER S. THROOP, C.B.O. |
| | BLDG. PLANS EXAMINER ? PX3169 |
| | (561) 805-6718 |
| | [email protected] |
| | |
| | PROVIDE PRODUCT APPROVAL FOR WINDOW MULLIONS. |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW SUBMITTALS. |
| | |
| | CONACT PALM BEACH COUNTY FOR POSSIBLE IMPACT FEES. |
| | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND |
| | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED |
| | WITH A COPY OF RECEIPT AS APPLICABLE. |
| | |
| | PROVIDE RE-INFORCEMENT DETAIL FOR CMU WALLS. |
| | R606.12.2.2.3 REINFORCEMENT REQUIREMENTS FOR MASONRY |
| | ELEMENTS. |
| | |
| | MASONRY ELEMENTS LISTED IN SECTION R606.12.2.2.2 SHALL |
| | BE REINFORCED IN EITHER THE HORIZONTAL OR VERTICAL |
| | DIRECTION IN ACCORDANCE WITH THE FOLLOWING: |
| | |
| | 1. HORIZONTAL REINFORCEMENT. HORIZONTAL JOINT |
| | REINFORCEMENT SHALL CONSIST OF AT LEAST TWO |
| | LONGITUDINAL W1.7 WIRES SPACED NOT MORE THAN 16 INCHES |
| | (406 MM) FOR WALLS GREATER THAN 4 INCHES (102 MM) IN |
| | WIDTH AND AT LEAST ONE LONGITUDINAL W1.7 WIRE SPACED |
| | NOT MORE THAN 16 INCHES (406 MM) FOR WALLS NOT |
| | EXCEEDING 4 INCHES (102 MM) IN WIDTH; OR AT LEAST ONE |
| | NO. 4 BAR SPACED NOT MORE THAN 48 INCHES (1219 MM). |
| | WHERE TWO LONGITUDINAL WIRES OF JOINT REINFORCEMENT ARE |
| | USED, THE SPACE BETWEEN THESE WIRES SHALL BE THE WIDEST |
| | THAT THE MORTAR JOINT WILL ACCOMMODATE. HORIZONTAL |
| | REINFORCEMENT SHALL BE PROVIDED WITHIN 16 INCHES (406 |
| | MM) OF THE TOP AND BOTTOM OF THESE MASONRY ELEMENTS. |
| | |
| | 2. VERTICAL REINFORCEMENT. VERTICAL REINFORCEMENT SHALL |
| | CONSIST OF AT LEAST ONE NO. 4 BAR SPACED NOT MORE THAN |
| | 48 INCHES (1219 MM). VERTICAL REINFORCEMENT SHALL BE |
| | LOCATED WITHIN 16 INCHES (406 MM) OF THE ENDS OF |
| | MASONRY WALLS. |
| | |
| | APPLY FOR SEPERATE PERMIT FOR ACCESSORY BLDG. (OFFICE). |
| | ADJUST VALUES FOR EACH STRUCTURE. |