Plan Review Details - Permit 15120650
Plan Review Stops For Permit 15120650
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-04 Cont ID  
Sent By albarran Date 2016-02-04 Time 11:17 Rev Time 0.00
Received By albarran Date 2016-02-04 Time 10:01 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-14 Cont ID  
Sent By albarran Date 2016-01-14 Time 11:46 Rev Time 0.00
Received By albarran Date 2016-01-14 Time 11:37 Sent To I
Notes
2016-01-14 11:46:10THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE RISER AS SHOWN ON THE DRAWINGS DOES NOT MATCH
 THE DEVICE COUNT ON PLANS.
 2. NEWLY INSTALLED FIRE ALARM SYSTEMS SHALL BE
 MONITORED AS INDICATED BY THE SEQUENCE OF OPERATION,
 BUT THE SIGNAGE SHOWN ON THE PLANS CONFLICT WITH THIS
 REQUIREMENT. WALL PLACARDS HAVE BEEN CROSSED OUT ON THE
 PLANS. REVISE THE DRAWING ACCORDINGLY.
 3. PER NFPA REQUIREMENTS YOU SHALL PROVIDE 75 DB AT THE
 PILLOW AT EACH SLEEPING AREA. REVISE YOUR DRAWING AND
 DEVICE PLACEMENT FOR COMPLIANCE WITH SUCH.
 4. ONCE DEVICE COUNT GETS ADJUSTED TO MEET MINIMUM
 AUDIBILITY REQUIREMENTS, ADJUST THE RISER DIAGRAM,
 BATTERY AND VOLTAGE DROP CALCS AS REQUIRED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-21 Cont ID  
Sent By pleduc Date 2015-12-21 Time   Rev Time 0.00
Received By pleduc Date 2015-12-21 Time 16:17 Sent To E
Notes
2015-12-21 16:33:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET FA - 03 - THERE IS AN INCORRECT REFERNCE TO
 THE FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
 2. ALL AUDIBLE LEVELS SHALL COMPLY WITH NFPA 101
 CHAPTER 31, EXISTING APARTMENT OCCUPANCIES, CHAPTER 9
 BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT; 9.6
 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS, AND
 NFPA 72.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-04 Cont ID  
Sent By albarran Date 2016-02-04 Time 11:18 Rev Time 0.00
Received By albarran Date 2016-02-01 Time 11:11 Sent To  
Notes
2016-02-04 11:19:352/4/16 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT FILE TO SMALL READY BIN "L". MA
2016-02-02 11:12:13ALBARRAN'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-14 Cont ID  
Sent By albarran Date 2016-01-14 Time 11:46 Rev Time 0.00
Received By albarran Date 2015-12-18 Time 14:27 Sent To  
Notes
2016-01-14 11:48:361/14/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL DENIED BIN "L".
 MA
2015-12-18 14:27:53ROUTED TO FIRE