Plan Review Details - Permit 15120638
Plan Review Stops For Permit 15120638
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-02-03 Cont ID  
Sent By Mgonzale Date 2016-02-03 Time   Rev Time 1.00
Received By mgonzale Date 2016-02-03 Time   Sent To I
Notes
2016-02-03 10:27:20PASSED WITH PROVISOS:
  
 PLAN MUST ADHERE TO ENGINEERING SERVICES PLAN APPROVAL
 E15080030 DATED 1/12/2016 / AS SUBMITTED TO PALM BEACH
 COUNTY HEALTH DEPARTMENT.
 PALM BEACH COUNTY HEALTH DEPARTMENT PERMIT APPROVAL
 MUST BE ALSO POSTED ON-SITE AT ALL TIMES.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-19 Cont ID  
Sent By wjolin Date 2016-01-19 Time 12:11 Rev Time 0.00
Received By wjolin Date 2016-01-19 Time 11:18 Sent To  
Notes
2016-01-19 12:09:435001 NORTH MILITARY TRAIL
 PERMIT #15120638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 SUBMIT A COPY OF THE CONTRACT JUSTIFYING THE PERMIT
 VALUATION.THE TOTAL PERMIT JOB VALUE NEEDS TO INCLUDE
 BOTH MATERIALS AND LABOR. SUBMIT EQUIPMENT CUTSHEETS
 FOR BACKFLOW PREVENTERS, JOINT RESTRAINT SYSTEMS, PIPE
 AND FITTINGS.
  
 JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
  
 CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION
 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY
 TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE
 SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE
 CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM
 PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN
 THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER
 SECOND.
  
 FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, THE
 INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE
 COMPLETING AND SIGNING THE CONTRACTOR?S MATERIAL AND
 TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
  
 HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION
 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT 200 PSI OR 50 PSI IN EXCESS
 OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER,
 AND SHALL MAINTAIN THAT PRESSURE +/-5 PSI FOR 2 HOURS.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-09 Cont ID  
Sent By cpuell Date 2016-02-07 Time 08:15 Rev Time 0.00
Received By cpuell Date 2016-01-04 Time 09:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-21 Cont ID  
Sent By lmarchan Date 2015-12-21 Time 08:12 Rev Time 0.00
Received By lmarchan Date 2015-12-18 Time 14:17 Sent To  
Notes
2015-12-21 08:12:16DISREGARD IN STOP, PROJECT IS DIGITAL
2015-12-18 14:17:50ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hmoser Date 2016-01-07 Time 13:15 Sent To  
Notes
2016-01-11 14:28:46PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS
 ON BELL RESTRAINTS AT FIRST INSPECTION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-02-11 Cont ID  
Sent By skennedy Date 2016-02-11 Time 08:05 Rev Time 0.00
Received By skennedy Date 2016-02-11 Time 08:05 Sent To  
Notes
***NONE***