Plan Review Details - Permit 15120611
Plan Review Stops For Permit 15120611
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-16 Cont ID  
Sent By jwitmer Date 2016-03-16 Time 11:52 Rev Time 0.00
Received By jwitmer Date 2016-03-16 Time 09:40 Sent To  
Notes
2016-03-16 11:52:33BUILDING PLAN REVIEW
 W. P.B. PERMIT: 25120611
 ADD: 700 S. ROSEMARY AVE. SUITE # 212
 CONT: ADCON ADVANCED CONSTRUCTION
 TEL: 561-856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. MARCH 16/2016
 ACTION: BUILDING PROVISO
  
 1) PROVISO/ DEFERRED SUBMITTAL :2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS &
 ATTACHMENTS TO RTU AND OR ROOF TOP FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-25 Cont ID  
Sent By jwitmer Date 2016-02-25 Time 06:45 Rev Time 0.00
Received By jwitmer Date 2016-02-25 Time 05:47 Sent To  
Notes
2016-02-25 05:59:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 25120611
 ADD: 700 S. ROSEMARY AVE. SUITE # 212
 CONT: ADCON ADVANCED CONSTRUCTION
 TEL: 561-856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: THURS. FEB. 25/2016
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) 2ND REQUEST. PLEASE PROVIDE A DEMO SHEET OR PROVIDE
 A EXISTING LAY OUT AND WHAT IS NEW FOR COMPARISON. THE
 INTERIOR DEMO PERMIT (15110848) WAS DESIGNED UNDERTHE
 SAME ARCHITECT. PLEASE NOTE THERE ARE ELEMENTS REMOVED
 UNDERTHE DEMO PERMIT THAT WILL CONSTITUTE NEW WORK AND
 HAVE TO COMPLY WITH: 2014 EXISTING BUILDING CODE LEVEL
 II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 ONE AREA IN QUESTION IS THE REMOVAL OF STAIR LABELED
 D-8. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) COMPLIED. PLEASE PROVIDE CALCULATIONS FOR PLATFORM
 CONSTRUCTION INCOMPLIANCE WITH 2014 FBC-B 410.4 WHERE
 THE PLATFORMS ARE NOT MORE THAN 30 INCHES (762 MM)
 ABOVE THE MAIN FLOOR, AND NOT MORE THAN ONE-THIRD OF
 THE ROOM FLOOR AREA AND NOT MORE THAN 3,000 SQUARE FEET
 (279 M2) IN AREA.
  
 5) 2ND REQUEST. THE AREA OF RAISED PLATFORM INTHE UPPER
 PORTION OF THE PLANS INDICATES A RAISED PLATFORM WITH
 AN OCCUPANT LOAD GREATER THAN 50AND WITH ONLY 1
 ACCESSIBLE MEANS OF EGRESS(RAMP). WITH THE REMOVAL OF
 STAIR TO THE LEFT PORTION OF THE RAISED PLATFROM (STAIR
 D-8 ON DEMO PERMIT) THE 2ND ACCESSIBLE MEANS OF EGRESS
 CAN NOW BE BUILT WITH THE 2ND RAMP ANS
 REQUIREDHANDRAILS. SHEET A6 SHOWS (2) RAISED PLATFORM
 DINING AREAS UPPER PORTION OF THE PLANS BY THE MAIN
 ENTRY THE OTHER TO THE LOWER PORTION OF THE MAIN ENTRY.
 IN BOTH DINING AREAS THE OCCUPANT LOAD IS GREATER THAN
 50 AND WILL NEED TO SHOW COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION). THE LOWER PORTION IS NOT
 BEING TOUCHED, UNDER THE EXISITNG BUILDING CODE LEVEL
 II ALTERATIONS THIS IS NOT ADDRESSED. PLEASE NOTE THAT
 BEING SAID, IT DOES NOT RELIEVE THE OWNER FROM A
 BARRIER FREE DESIGN UNDER THE ADA AND LIABLE TO LAW
 SUIT.
  
 ***2003 IBC-B 1007.1 *** WHERE MORE THAN ONE MEANS OF
 EGRESS IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM
 ANY ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE
 SPACE SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF
 EGRESS.
  
  
 6) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE:
 6A) 2ND REQUEST. 221.2.1.1 GENERAL SEATING. WHEELCHAIR
 SPACES COMPLYING WITH 802.1 SHALL BE PROVIDED IN
 ACCORDANCE WITH 2014 ACC.CODE SECTION 226.1 5% OF THE
 OVERALL SEATING. SEATING COUNT 357 SEATS/.05= 23
 ACC.SEATS.
  
  
 6B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES. THE PLANS SHOW 3 OF
 THE ACCESSIBLE SEATS AT A SERVER POINT OF SALE STATION
 AND NOT IN THE DINING ROOM. THE PLANS DO NOT SHOW ANY
 ACCESSIBLE SEATING IN THE OUTDOOR SEATING AREA.THE
 PRIVATE DINING ROOM OR INTHE BOOTH AREAS AS WELL AS THE
 HIGH TOP SEATING ADJACENT TO THE BAR.
  
 6C) SEMI-COMPLIED. THE PLANS WILL NEED TO SHOW THE
 ADDITIONAL ACCESSIBLE SEATING REQUIRED. 902.2 CLEAR
 FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305 POSITIONED FOR A FORWARD APPROACH SHALL BE
 PROVIDED. KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED.
  
 6D) 2ND REQUEST. NOT SHOWN 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 6E) COMPLIED.
  
 7) COMPLIED. EXISITNG.
  
 8) PROVISO/ DEFERRED SUBMITTAL :2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 THE MECHANICAL SHEETS SHOW A ROOF TOP UNIT, OARTU-1. IS
 THIS A EXISITNG UNIT OR NEW? IF NEW PLEASE PROVIDE THE
 ENGINEERING FOR THE NEW ROOF TOP OPENING, NEW ROOF TOP
 CURB AND TIE DOWN OF THE CURB AS WELL AS THE TIE DOWN
 OF THE ROOF TOP UNIT TO THE CURB. 1609.6.4.4.1
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 (G) PRE-ENGINEERED A/C STANDS
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-07 Cont ID  
Sent By jwitmer Date 2016-01-07 Time 08:33 Rev Time  
Received By jwitmer Date 2016-01-07 Time 06:30 Sent To  
Notes
2016-01-07 08:18:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 25120611
 ADD: 700 S. ROSEMARY AVE. SUITE # 212
 CONT: ADCON ADVANCED CONSTRUCTION
 TEL: 561-856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: THURS. JAN. 07/2016
 ACTION: DENIED
  
 1) COVERSHEET DOES NOT SHOW A INDEX OF PLANS NOR WITHIN
 THE SET OF PLANS IS THERE A EGRESS SHEET SHOWING THE
 EGRESS THROUGH OUT THE TENANT SPACE, EXIT DIRECTIONALS,
 EXIT LIGHTS NOR EMERGENCY LIGHTS OR EMERGENCY BATTERY
 BACK UP LIGHTS.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5.1.1. MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS.
 (7.) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY
  
 2) THE COVERSHEET LIST THIS AS A BUILDING TYPE II
 BUILDING. THIS BUILDING WAS BUILT UNDER THE 1997 SBCCI
 CODE AS A TYPE II BUILDING. UNDER THE 2014 FBC-B THIS
 EQUATES TO A TYPE IB BUILDING TYPE, PLEASE UPDATE
 PLANS.
  
 3) PLEASE PROVIDE A DEMO SHEET OR PROVIDE A EXISTING
 LAY OUT AND WHAT IS NEW FOR COMPARISON. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) PLEASE PROVIDE CALCULATIONS FOR PLATFORM
 CONSTRUCTION INCOMPLIANCE WITH 2014 FBC-B 410.4 WHERE
 THE PLATFORMS ARE NOT MORE THAN 30 INCHES (762 MM)
 ABOVE THE MAIN FLOOR, AND NOT MORE THAN ONE-THIRD OF
 THE ROOM FLOOR AREA AND NOT MORE THAN 3,000 SQUARE FEET
 (279 M2) IN AREA.
  
 5) SHEET A6 SHOWS (2) RAISED PLATFORM DINING AREAS ONE
 LEFT OF THE MAIN ENTRY THE OTHER TO THE RIGHT OF THE
 MAIN ENTRY. IN BOTH DINING AREAS THE OCCUPANT LOAD IS
 GREATER THAN 50 AND WILL NEED TO SHOW COMPLIANCE WITH
 THE 2014 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 6) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY
 CODE:
 6A) 221.2.1.1 GENERAL SEATING. WHEELCHAIR SPACES
 COMPLYING WITH 802.1 SHALL BE PROVIDED IN ACCORDANCE
 WITH TABLE 221.2.1.1.
  
 6B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 6C) 902.2 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6D) 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6E) SHEET A-17 DETAILS D & H BOTH SHOW ACCESSIBLE
 HANDRAILS FOR STAIRS BUT NO FOR RAMPS, RAMP HANDRAILS
 REQUIRE COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE
 505.10.1 RAMPS TOP AND BOTTOM EXTENTIONS AT RAMPS.
  
 7A) SHEET A-17 SHOWS WHAT IS CALLED A EQUIPMENT
 PLATFORM, PLEASE SGOW COMPLIANCE WITH 505.3.1 AREA
 LIMITATION. THE AGGREGATE AREA OF ALL EQUIPMENT
 PLATFORMS WITHIN A ROOM SHALL BE NOT GREATER THAN
 TWO-THIRDS OF THE AREA OF THE ROOM IN WHICH THEY ARE
 LOCATED. THIS APPEARS TO BE A STORY.
  
 7B) SHOW COMPLIANCE WITH 505.3.2 AUTOMATIC SPRINKLER
 SYSTEM. WHERE LOCATED IN A BUILDING THAT IS REQUIRED TO
 BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM,
 EQUIPMENT PLATFORMS SHALL BE FULLY PROTECTED BY
 SPRINKLERS ABOVE AND BELOW THE PLATFORM, WHERE REQUIRED
 BY THE STANDARDS REFERENCED IN SECTION 903.3.
  
 8) THE MECHANICAL SHEETS SHOW A ROOF TOP UNIT, OARTU-1.
 IS THIS A EXISITNG UNIT OR NEW? IF NEW PLEASE PROVIDE
 THE ENGINEERING FOR THE NEW ROOF TOP OPENING, NEW ROOF
 TOP CURB AND TIE DOWN OF THE CURB AS WELL AS THE TIE
 DOWN OF THE ROOF TOP UNIT TO THE CURB. 1609.6.4.4.1
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 (G) PRE-ENGINEERED A/C STANDS
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-22 Cont ID  
Sent By albarran Date 2016-03-22 Time 19:09 Rev Time 0.00
Received By albarran Date 2016-03-22 Time 18:39 Sent To FIRE
Notes
2016-03-22 19:10:05REVISED SHEET SUBMITTED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-03 Cont ID  
Sent By albarran Date 2016-03-03 Time 11:08 Rev Time 0.00
Received By albarran Date 2016-03-02 Time 18:41 Sent To I
Notes
2016-03-03 11:13:34TRYING TO FOLLOW THE NARRATIVE I REALIZED THAT I HAD AN
 OLD AND UNREVISED SHEET E3.1. WHILE LOOKING FOR THE
 SHOW WINDOW OUTLETS ON THE OLDER SHEET I WENT TO THE
 ARCHITECTURAL DRAWINGS AND NOTICED THAT WHAT APPEARS TO
 BE AN OPEN AREA ON THE ELECTRICAL SHEET IS A CLOSED
 ROOM ON THE SHEET A3 REQUIRING LIGHTING AND LIGHTING
 CONTROL. I SPOKE W/GORDON SCOTT THE PROJECT MANAGER TO
 CONFIRM MY FINDINGS. HE WILL RESUBMIT CORRECTED SHEETS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-21 Cont ID  
Sent By albarran Date 2016-01-21 Time 18:58 Rev Time 0.00
Received By albarran Date 2016-01-21 Time 13:40 Sent To I
Notes
2016-01-21 18:59:41THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE APPLICABLE EDITION OF THE NEC IS THE 2011, AS
 REFERENCED IN THE 5TH EDITION OF THE FBC-2014. CORRECT
 SHEET A1.
 2. THERE ARE MANY MISSING EXIT LIGHTS TO NAME EACH.
 PLEASE SEE YELLOW HIGHLIGHTS ON THE REVIEWED DRAWINGS
 ON SHEET E2.1
 3. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 4. THE MANDATORY LIGHTING CONTROLS OF FBC-EC405 ARE
 MISSING IN THE AREAS OF THE PROPOSED STORAGE AND
 PROPOSED BEER COOLER. SEE LIGHTING SHEET HIGHLIGHTED IN
 GREEN.
 5. SHEET E3.1A REFLECTS NEW STAIRS 2R & 3R. IF THESE
 HAVE MORE THAN 6 RISERS, NEC AND REQUIRES ILLUMINATION
 AND SWITCHING.
 6. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY.
 7. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 8. NEC 210.8(B) GROUND FAULT CIRCUIT-INTERRUPTER
 PROTECTION OTHER THAN DWELLING UNITS. ALL KITCHEN
 RECEPTACLES SHALL BE GFCI PROTECTED.
 9. THOUGH THE FIRE ALARM REQUIRES A SEPARATE PERMIT AND
 SUBMITTAL, MAKE NOTE CHANGE TO DUCT DETECTOR TO
 INITIATE A GENERAL ALARM.
 10. ACCORDING TO NFPA 72 SECTION 10.15, SMOKE DETECTOR
 PROTECTION IS REQUIRED IN AREAS IDENTIFIED BY AN ASTRIX
 * 10 ON THE FIRE ALARM FLOOR PLANS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-03-29 Cont ID  
Sent By pleduc Date 2016-03-29 Time   Rev Time 0.00
Received By pleduc Date 2016-03-28 Time 16:37 Sent To G
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-02 Cont ID  
Sent By pleduc Date 2016-03-02 Time   Rev Time 0.00
Received By pleduc Date 2016-02-29 Time 16:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-12-22 Cont ID  
Sent By pleduc Date 2015-12-23 Time   Rev Time 0.00
Received By pleduc Date 2015-12-22 Time 12:33 Sent To  
Notes
2015-12-22 13:28:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET A - 1 - THE OCCUPANY LOAD CALCULATIONS FOR THE
 STORAGE AND COOLER AREA APPEAR TO BE INCORRECT THOUGH
 IT DOES NOT ADVERSELY AFFECT THE OVER ALL LOAD, IT MUST
 BE CORRECTED.
  
 2. SHEET A - 3 - DOOR D 1-7 APPEARS TO SWING IN BOTH
 DIRECTIONS. PROVIDE CLEAR INDICATION THAT IT SWINGS IN
 THE PATH OF EXIT EGRESS AND THERE IS NO LATCH.
  
 3. SHEET E - 2.1 - EXIT SIGNAGE IS REQUIRED FOR EXIT
 DOORS D1-5 AND D 1-7. CONFIRM EXIT SIGNS AT THE STORAGE
 ROOM DOOR AND THE REAR CORRIDOR DOOR.
  
 4. SHEET E 2-1 AND A - 4 - EMERGENCY LIGHTING REQUIRED
 THROUGHOUT THE OCCUPANCY ONLY 5 ARE NOTED IN THE
 KITCHEN AREA. PROVIDE INDICATION THAT THE EXIT SIGNS
 PROVIDE THE REQUIRED EMERGENCY LIGHTING OR PROVIDE
 ADDITIONAL EMERGENCY LIGHTING TO MEET THE REQUIRED
 CANDELA PER NFPA 101 THROUGHOUT THE OCCUPANCY.

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2016-03-23 Cont ID  
Sent By tklarge Date 2016-03-23 Time 13:23 Rev Time 0.00
Received By tklarge Date 2016-03-23 Time 13:23 Sent To  
Notes
2016-03-23 13:24:25MANUFACTURER'S SPECIFICATIONS SHALL BE ONSITE FOR
 INSPECTION.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2016-03-16 Cont ID  
Sent By gjohnson Date 2016-03-16 Time 17:35 Rev Time 0.00
Received By gjohnson Date 2016-03-16 Time 17:35 Sent To  
Notes
2016-03-16 17:35:21GAS COMMENTS:
 3RD REQUEST
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
  
  
  
 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 3RD REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-02-28 Cont ID  
Sent By tklarge Date 2016-02-28 Time 06:59 Rev Time 0.00
Received By tklarge Date 2016-02-28 Time 06:59 Sent To  
Notes
2016-02-28 07:00:47COMPLY WITH GAS COMMENTS FROM PREVIOUS GAS REVIEW.
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-01-04 Cont ID  
Sent By gjohnson Date 2016-01-04 Time 11:52 Rev Time 0.00
Received By gjohnson Date 2016-01-04 Time 11:52 Sent To  
Notes
2016-01-04 12:07:461ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. SHEET P0.2 KITCHEN SCHEDULE E108, E99, E96 SHOW GAS
 CONNECTION THOSE APPLIANCES DO NOT NEED GAS BUT WARE
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-29 Cont ID  
Sent By pleduc Date 2016-03-29 Time   Rev Time 0.00
Received By skennedy Date 2016-03-11 Time 10:20 Sent To  
Notes
2016-03-14 10:20:43C28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-03 Cont ID  
Sent By albarran Date 2016-03-03 Time 11:19 Rev Time 0.00
Received By albarran Date 2016-02-19 Time 09:56 Sent To  
Notes
2016-03-03 11:27:013/3/16 FAILED THE LAST OF ALL MP REVIEWS. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO LARGE DENIED BIN "A".
 MA
2016-02-22 09:56:58C20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-21 Cont ID  
Sent By albarran Date 2016-01-21 Time 19:01 Rev Time 0.00
Received By albarran Date 2015-12-17 Time 11:09 Sent To  
Notes
2016-01-21 19:02:591/21/16 FAILED THE LAST OF ALL TRADE REVIEWS
 (ELECTRICAL). CONTRACTOR NOTIFIED VIA EMAIL. SENT FILE
 TO LARGE DENIED DRAWER "A". MA
2015-12-18 11:10:59C20

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-03-30 Cont ID  
Sent By skennedy Date 2016-03-30 Time 16:56 Rev Time 0.00
Received By skennedy Date 2016-03-30 Time 16:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-03-21 Cont ID  
Sent By ccole Date 2016-03-21 Time 10:48 Rev Time 0.00
Received By ccole Date 2016-03-21 Time 08:47 Sent To  
Notes
2016-03-21 10:51:333RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120611
 3/21/16
  
 1) IT APPEARS THE PLAN SHEET M6.2 IS MISSING FROM THE
 PLAN SETS, AND ALSO THE AC LOAD CALCULATIONS ARE NOT IN
 THE PERMIT FILE. PLEASE RE-SUBMIT THE REQUIRED PLANS
 AND DOCUMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-02-29 Cont ID  
Sent By ccole Date 2016-02-29 Time 11:01 Rev Time 0.00
Received By ccole Date 2016-02-26 Time 11:06 Sent To  
Notes
2016-03-01 11:04:153RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120611
 2/29/16
  
 1) SUBMIT PLANS SHEET M2.2 AS INDICATED IN THE RESPONSE
 NARRATIVE FROM KAMM ENGINEERING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-28 Cont ID  
Sent By ccole Date 2015-12-28 Time 14:20 Rev Time 0.00
Received By ccole Date 2015-12-28 Time 14:20 Sent To  
Notes
2015-12-28 14:35:091ST REVIEW 2014 MECHANICAL
 PERMIT #15120611
 12/28/15
  
 1) SHEET M2.1: OUTDOOR AIR IS BEING SUPPLIED ONLY TO
 THE CENTRAL DINING AREA VIA OARTU-1, HOWEVER NO O/A IS
 BEING SUPPLIED TO THE KITCHEN, THE PRIVATE DINING AREA,
 THE UPPER DINING AREAS, AND THE BACK BAR AREA THROUGH
 AHU'S 1, 2, & 3. PLEASE REFER TO TABLE 403.3 FBC-14
 MECHANICAL AND REVISE THE PLANS TO SHOW COMPLIANCE.
 2) M2.1: DUCT SMOKE DETECTORS ARE REQUIRED TO BE
 INSTALLED IN THE RETURN AIR SYSTEMS OF AHU'S 1, 2, & 3-
 SEE SECTION 606.2.1.
 3) PROVIDE A CHILLED WATER PIPING LAYOUT PLAN WITH PIPE
 AND PIPE INSULATION DETAILS.
 4) PROVIDE A HVAC ROOF PLAN SHOWING THE LOCATIONS OF
 THE OARTU-1, THE AC AND REFRIGERATION CONDENSERS, AND
 THE KITCHEN HOOD EXHAUST AND SUPPLY FANS. PLEASE
 INCLUDE CLEARANCES DISTANCES AS OUTLINED IN SECTIONS
 401.4 AND 501.3.1 FBC-14 MECHANICAL.
 5) PROVIDE ENGINEERED TIE DOWN DETAILS FOR THE OARTU-1
 AND THE AC CONDENSERS.
 6) PLACE A NOTE ON THE PLANS INDICATING THE KITCHEN
 HOODS, AND WALK-IN COOLER WILL BE DONE UNDER SEPARATE
 PERMITS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-03-16 Cont ID  
Sent By gjohnson Date 2016-03-16 Time 17:40 Rev Time 0.00
Received By gjohnson Date 2016-03-16 Time 17:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-02-28 Cont ID  
Sent By tklarge Date 2016-02-28 Time 06:59 Rev Time 0.00
Received By tklarge Date 2016-02-28 Time 05:32 Sent To  
Notes
2016-02-28 06:29:111) SHT. A-8 - THE EQUIPMENT SCHEDULE SHOWS GAS TO
 EQUIPMENT NUMBERS E96, E99, E106 & E117. THIS HAS BEEN
 CORRECTED ON THE EQUIPMENT SCHEDULE IN THE PLUMBING
 DRAWINGS AND ALSO NEEDS TO BE CORRECTED ON THIS SHEET.
 2) SHOW THE CAPACITY OF THE EXISTING GREASE INTERCEPTOR
 AND SUBMIT GREASE WASTE CALCULATIONS TO ENSURE THE
 EXISTING GREASE TRAP HAS THE CAPACITY TO PERFORM AS
 DESIGNED.FBC SEC. 107.2.1.
 3) THE TWO FLOOR SINKS & FLOOR DRAIN LOCATED IN THE
 ROOM WITH THE WATER HEATEER AND THE EXISTING MOP SINK
 ARE NOT VENTED. COMPLY WITH 2014 FPC SEC. 910 OR 914.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-04 Cont ID  
Sent By gjohnson Date 2016-01-04 Time 11:38 Rev Time 0.00
Received By gjohnson Date 2016-01-04 Time 11:38 Sent To  
Notes
2016-01-04 11:52:131ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHEET P5.1 GREASE RISER FOR BACK BAR AREA, EACH
 FIXTURE BRANCH SHALL CONNECT SEPARATELY TO HORIZONTALL
 BRANCH SHALL COMPLY WITH FBC P SEC 914
 2. SHEET P5.1 GREASE RISER FOR KITCHEN AREA, EACH
 FIXTURE BRANCH MUST CONNECT TO A VENTED HORIZONTA
 BRANCH IT CAN NOT CONNECT TO BUILD DRAIN WITH OUT BEING
 VENTED. SHALL COMPLY WITH FBC PL SEC 910.1 OR 914
 3. SHOW BACKFLOW DEVICE ON RISER DIGRAM FOR FIXTURES
 THAT REQUIRE A SEPARATE BACKFLOW PER WPB AMEND. TO FBC
 SEC107.2.1

Review Stop Z ZONING
Rev No 3 Status P Date 2016-03-15 Cont ID  
Sent By eschneid Date 2016-03-15 Time 14:52 Rev Time 0.50
Received By eschneid Date 2016-03-15 Time 14:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-02-29 Cont ID  
Sent By eschneid Date 2016-02-29 Time 10:42 Rev Time 0.25
Received By eschneid Date 2016-02-29 Time 10:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-01-06 Cont ID  
Sent By eschneid Date 2016-01-06 Time 13:21 Rev Time 0.50
Received By eschneid Date 2016-01-06 Time 13:21 Sent To  
Notes
***NONE***