Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-02 Cont ID  
Sent By albarran Date 2016-05-02 Time 16:17 Rev Time 0.00
Received By albarran Date 2016-05-02 Time 15:44 Sent To FIRE
Notes
2016-05-02 16:19:42PREVIOUSLY MENTIONED COMMENTS HAVE BEEN SATISFACTORILY
 ADDRESSED BUT NEW PAGES HAVE TO BE RESTAMPED BY FIRE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-02-03 Cont ID  
Sent By albarran Date 2016-02-03 Time 17:04 Rev Time 0.00
Received By albarran Date 2016-02-03 Time 15:18 Sent To I
Notes
2016-02-03 17:08:592ND ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
 NFPA 72 2010
  
 CORRECTIONS REQUIRED:
 1. AS EXPRESSED IN MY PREVIOUS COMMENT #4, THE RISER
 DIAGRAM AND THE DEVICE COUNT ON THE FLOOR PLAN DO NOT
 MATCH. CORRECT PLANS ACCORDINGLY.
 2. MY COMMENT #6 HAS TO DO WITH THE SAME ISSUE AS
 PREVIOUSLY INDICATED. THE LOAD CALCS ON THE PLANS DO
 MATCH THE RISER DIAGRAM, BUT NOT THE FLOOR PLAN.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-30 Cont ID  
Sent By albarran Date 2015-12-30 Time 09:39 Rev Time 0.00
Received By albarran Date 2015-12-29 Time 16:26 Sent To I
Notes
2015-12-30 09:40:11THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE SCOPE OF WORK AS DEFINED ON THE PLANS DOES NOT
 MATCH THAT INDICATED ON THE REVISION FORM. ALL
 DOCUMENTS HAVE TO MATCH, CORRECT AS REQUIRED.
 2. THERE ARE A COUPLE OF NEW SYMBOLS APPEARING ON THE
 PLAN NOT INCLUDED IN THE LEGEND. CORRECT AS REQUIRED.
 3. THE REQUIRED MANUFACTURERS SPEC SHEETS FOR THE NEW
 DEVICES SHALL ACCOMPANY THE SUBMITTAL.
 4. THE RISER DIAGRAM AS PRESENTED DOES NOT MATCH THE
 DEVICE COUNT ON THE PLANS. WHICH IS CORRECT? REVISE
 PLANS ACCORDINGLY.
 5. DEVICE PLACEMENT ON NEW PLANS DIFFERS IN MORE WAYS
 THAN INDICATED ON THE SUBMITTED REVISION FORM. CORRECT
 THE PLANS FOR AN ACTUAL ?AS BUILT? DRAWING.
 6. THE DIFFERENCE IN THE DEVICE COUNTS WILL ALSO HAVE
 TO BE REFLECTED ON THE CALCS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-04 Cont ID  
Sent By pleduc Date 2016-05-04 Time   Rev Time 0.00
Received By pleduc Date 2016-05-04 Time 15:49 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-21 Cont ID  
Sent By pleduc Date 2015-12-21 Time   Rev Time 0.00
Received By pleduc Date 2015-12-21 Time 16:09 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-04 Cont ID  
Sent By pleduc Date 2016-05-04 Time   Rev Time 0.00
Received By pleduc Date 2016-05-02 Time 14:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-03 Cont ID  
Sent By albarran Date 2016-02-03 Time 17:10 Rev Time 0.00
Received By albarran Date 2016-02-02 Time 11:44 Sent To  
Notes
2016-02-03 17:12:092/3/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED AND MADE AWARE OF DEFICIENCIES. SENT FILE TO
 SMALL DENIED BIN "W". MA
2016-02-02 11:44:54ALBARRAN'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-30 Cont ID  
Sent By albarran Date 2015-12-30 Time 09:41 Rev Time 0.00
Received By albarran Date 2015-12-17 Time 10:40 Sent To  
Notes
2015-12-30 09:43:0812/30/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED BOTH, VIA PHONE AND EMAIL. SENT TO SMALL
 DENIED BIN "W". MA
2015-12-18 10:41:11REVISION ROUTED TO FIRE