Plan Review Details - Permit 15120589
Plan Review Stops For Permit 15120589
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-20 Cont ID  
Sent By rmcdouga Date 2016-01-20 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2016-01-20 Time 06:49 Sent To  
Notes
2016-01-20 06:51:16FIRST REVIEW WAS UNINTENTIONALLY LOCKED.
  
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF A SURVEY THAT SHOWS THE
 LOCATION OF THE EXISTING STRUCTURES AND THE PROPOSED
 STRUCTURES. FBC 107.2.1
  
 2) SUBMIT TWO COPIES OF A SITE PLAN THAT SHOWS THE
 DISTANCE BETWEEN THE PROPOSED STRUCTURES AND THE
 PROPERTY LINES AND ADJACENT STRUCTURES ON THE SAME LOT.
 FBC R302.1 & FBC 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY. IN THE CASE OF DEMOLITION, THE SITE PLAN SHALL
 SHOW CONSTRUCTION TO BE DEMOLISHED AND THE LOCATION AND
 SIZE OF EXISTING STRUCTURES AND CONSTRUCTION THAT ARE
 TO REMAIN ON THE SITE OR PLOT.
  
 3) SUBMIT TWO SETS OF DRAFTMAN QUALITY PLANS THAT
 INCLUDE A FOUNDATION PLAN, FLOOR PLAN, ELEVATIONS, WALL
 AND ROOF FRAMING PLANS AND STRUCTURAL DETAILS. FBC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) FBC-R 301.1 BUILDINGS AND STRUCTURES, AND ALL PARTS
 THEREOF, SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL
 LOADS, INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS,
 FLOOD LOADS, AND WIND LOADS AS PRESCRIBED BY THIS CODE.
 THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL
 LOADS FROM THEIR POINT OF ORIGIN THROUGH THE
 LOAD-RESISTING ELEMENTS TO THE FOUNDATION.
  
 5) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 6) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
  
 7) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS AND
 COMPONENT AND CLADDING DESIGN PRESSURES PURSUANT TO
 FBC-R301.2.
  
 8) FBC 107.3.5.3 ? INDICATE THE MEANS OF TERMITE
 PROTECTION PROPOSED PURSUANT TO FBC-R318.
  
 9) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-20 Cont ID  
Sent By rmcdouga Date 2016-01-20 Time 10:20 Rev Time 0.00
Received By rmcdouga Date 2016-01-19 Time 18:59 Sent To  
Notes
2016-01-19 19:08:40PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ELECTRICAL FLOOR PLANS SHOWING
 THE LOCATIONS OF ALL LIGHTING, APPLIANCE (WATER HEATER,
 ETC.) AND RECEPTACLE OUTLETS. FBC 107.2.1
  
 2) FBC- 107.3.5.3 PROVIDE AN ELECTRIC SERVICE RISER
 WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL.
 PROVIDE COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND
 SHOW CIRCUITS ON FLOOR PLAN.
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-20 Cont ID  
Sent By rmcdouga Date 2016-01-20 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2015-12-17 Time 11:30 Sent To  
Notes
2015-12-18 11:30:26R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-01-20 Cont ID  
Sent By rmcdouga Date 2016-01-20 Time 16:25 Rev Time 0.00
Received By rmcdouga Date 2016-01-20 Time 16:25 Sent To  
Notes
2016-01-20 16:25:32BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-19 Cont ID  
Sent By rmcdouga Date 2016-01-19 Time 18:56 Rev Time 0.00
Received By rmcdouga Date 2016-01-19 Time 18:49 Sent To  
Notes
2016-01-19 18:56:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR
 R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE
 FORMS AS REQUIRED.
  
 2) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15.
  
 3) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW
 CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST,
 KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS,
 EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR,
 ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION,
 COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS,
 APPLIANCES, BOILERS, REFRIGERATION, BATHROOM
 VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION.
  
 4) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 5) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-22 Cont ID  
Sent By tklarge Date 2015-12-22 Time 04:12 Rev Time 0.00
Received By tklarge Date 2015-12-22 Time 03:27 Sent To  
Notes
2015-12-22 03:33:451) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR REVIEW
 PER THE WPB AMEND. TO FBC SEC. 107.3.5.3.
 2) SHOW THE SHOWER DIMENSIONS (LXW) ON THE PLAN.COMPLY
 WITH 2014 FBCR SECS. P2708, P2709.
 3) SHOW THE FIXTURE CLEARANCES/SPACING OF ALL FIXTURES
 PER 2014 FBCR SECS. P2705.1, R307.1.
 4) SHOW BOTH BUILDING DRAIN CONNECTIONS TO THE BUILDING
 SEWER ON THE PLAN AND SHOW THE SIZE OF THE SEWER. SHOW
 THE REQUIRED CLEANOUTS. 2014 FBCR SECS. P3005.2,
 P3005.2.7.
 5) SHOW THE LOCATION OF EACH WATER SERVICE & WATER
 METER ON THE PLAN AND THE LOCATION OF THE MAIN SHUTOFF
 VALVE FOR EACH STRUCTURE. 2014 FBCR SEC. P2903.9.1.
 6) HOT WATER SHALL BE SUPPLIED TO BOTH UNITS.SHOW
 LOCATION OF WATER HEATERS ON THE PLAN. 2014 FBCR SEC.
 P2801.1.
 7) SUBMIT A SITE PLAN/SURVEY SHOWING THE LOCATION OF
 BOTH STRUCTURES ON THE PLAN. WPB AMEND. TO FBC SEC.
 107.2.1.
 8) THE BACKING BOARD FOR THE WALLS IN THE SHOWERS SHALL
 COMPLY WITH 2014 FBCR SECS. R702.3.8.1, R702.4.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-01-13 Cont ID  
Sent By sgraham Date 2016-01-13 Time 15:20 Rev Time 0.00
Received By sgraham Date 2016-01-13 Time 15:20 Sent To  
Notes
2016-01-13 15:27:2912/13/16 ZONING FAILED
  
 1. SUBMIT TWO UP TO DATE SURVEYS OF THE PROPERTY
 2. SUBMIT PLANS SHOWING THE WORK
 3. ACCORDING TO OUR RECORDS THERE IS NO EFFICIENCY
 ROOMS ON THIS PROPERTY. THE ZONING IS SF11 WHICH DOES
 NOT PERMIT YOU TO HAVE THE EFFICIENCY ROOMS.
2015-12-28 16:11:3512/28/15