Plan Review Details - Permit 15120536
Plan Review Stops For Permit 15120536
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-06-07 Cont ID  
Sent By jwitmer Date 2016-06-07 Time 11:09 Rev Time 0.00
Received By jwitmer Date 2016-06-07 Time 08:54 Sent To  
Notes
2016-06-07 11:09:11BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120536
 ADD: 2745 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: 561-568-8931
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: TUES. JUNE 07/ 2016
 ACTION: BUILDING PROVISO
  
 1) PROVISO: SHEET 035-A.1.1.1A & 038-A1.1.1.1D BOTH
 SHOW THE USE OF PLATFORM LIFTS. A REVISION IS REQUIRED,
 DELETING THE PLATFORM LIFT IN COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE 206.7 NOT ALLOWED IN NEW
 CONSTRUCTION.
  
 2) PROVISO: 090-A4-4 DETAILS 1 & 2 FLOOR STRUCTURAL
 MEMBERS ARE 34 INCH DOUBLE T CONCRETE JOIST. THIS WOULD
 PROVIDE AN 8FT.-8 IN. CLEAR SPACE BENEATH THE JOIST,
 DEPENDING ON THE LAYOUT OF THE RAINWATER HORIZONTAL
 RUNS AND FIRE SPRINKLER LAYOUT WHICH HAS NOT YET BEEN
 PROVIDED.2014 FBC-B 406.4.1.
  
 3) PROVISO: 2014 FBC-B SECTION [F] 406.6.3 AUTOMATIC
 SPRINKLER SYSTEM. AN ENCLOSED PARKING GARAGE SHALL BE
 EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.2.10.
  
 4) PROVISO: DEFERRED SUBMITTAL . DOOR TYPE (N) SHOW
 THEY ARE A HORIZONTAL BI-PARTING DOOR. SHEET 113-A8-0
 INDICATES A DOOR TYPE (N) BUT DOES NOT INDICATE TO
 WHICH CODE SECTION THE DOORS ARE COMPLY 1008.1.4.2
 POWER OPERATED DOORS OR 1008.1.4.3 HORIZONTAL SLIDING
 DOORS OR HOW MUCH FORCE IS TO BE APPLIED TO SET THE
 DOOR IN MOTION. DOORS SHALL BE OPENABLE BY A SIMPLE
 METHOD FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR
 EFFORT, HOW WILL THIS BE ACCOMPLISHED.
  
 5) PROVISO/ DEFERRRED SUBMITTAL. SHEET 100-A6-2
 SKYLIGHT GLAZING IS GOING TO COMPLY WITH THE 2014 FBC-B
 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS.
 2405.5 UNIT SKYLIGHTS AND TUBULAR DAYLIGHTING DEVICES.
  
 6) PROVISO: DEFERRED SUBMITTALS. PLEASE SUBMIT PRODUCT
 APPROVALS TO COMPLY WITH: 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING, AND
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 7) PROVISO: DEFERRED SUBMITTALS. 2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-04-15 Cont ID  
Sent By jwitmer Date 2016-04-15 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2016-04-14 Time   Sent To  
Notes
2016-04-15 09:35:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120536
 ADD: 2745 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: 561-568-8931
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. APRIL 14/ 2016
 ACTION: DENIED
  
 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 7/1/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $500,000. PER CITY OF WEST
 PALM BEACH ORDINANCE NO. 4504-14, AND CITY OF WEST PALM
 BEACH CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC
 PLACES, SECTION 78-123(A) AND SECTION 78-126(A), THE
 ART ASSESSMENT IS 1% OF THE TOTAL PROJECT CONSTRUCTION
 COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) COMPLIED. 109.3.6.1 WRITTEN THRESHOLD INSPECTION
 PLAN.
  
 2B) 2ND REQUEST, THE THRESHOLD INSPECTION FORMS ARE TO
 BE SIGNED BY ALL PARTIES BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED
 OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE. CONTACT KEN
 CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT
 MAY BE ISSUED.
  
 2C) COMPLIED. 663 FLORIDA STATUTE.
  
 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
  
 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTICE ONLY: FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
  
 2G) INFORMATIONAL. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2H) INFORMATIONAL. 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) 2ND REVIEW. SHEET 001-INDEX INDICATES SHEET 033-A0.1
 IS MISSING, AND IS NOT PART OF THIS SUBMITTAL. A
 THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) 2ND REQUEST. THE SUBMITTED DOCUMENT IS SIGNED AND
 SEALED AS A PAPER DOCUMENT, THERE IS NO ELECTRONIC
 SIGNATURE TO THIS DOCUMENT. THE ENGINEER HAS 2 OPTIONS,
 EITHER COMPLY WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS OR SUBMIT 1 ORIGINAL PAPER
 DOCUMENT SIGNED AND SEALED.
  
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) SHEET 027-LS-1E:
  
 5A) COMPLIED.
  
 5B) 2ND REQUEST. SUBMITTED A MANUFACTURERS BROCHURE
 FROM GARAVENTA LIFT. THE BROCHURE WAS PRINTED IN
 CANADA, THE LIFT MAYBE MADE IN CANADA AND NOT HAVE A
 ASME A18.1 LISTING. THE SERVICE VESTIBULE SHOWS THE USE
 OF A PLATFORM LIFT, PLEASE PROVIDE THE MANUFACTURERS
 SHOP DRAWINGS AND OR SPEC SHEET THAT SHOWS THE LIFT
 COMPLIES WITH ASME A18.1 (FBC-ACCESSIBILITY CODE
 410.1).
  
 5C) COMPLIED. RECEIVING ROOM 163, EXIT DISCHARGE TO A
 PUBLIC WAY.
  
 5D) COMPLIED. NO MEZZANINE IN THE PARTS STORAGE LEVEL.
  
 5E) COMPLIED.
 6-8) COMPLIED.
  
 9) 2ND REQUEST. SHEET 145-S1.1A IN THE BOTTOM RIGHT
 SHOWS A KEY FOUNDATION PLAN FOR THE FOUNDATION. THE KEY
 PLAN DOES NOT IDENTIFY THE FOUNDATION BEHIND THE
 BUILDING LABELED 1. PLEASE PROVIDE WHERE THIS PLAN CAN
 BE LOCATED.
  
 10-11) COMPLIED.
  
 12) 2ND REQUEST. PLEASE SHOW THE STRETCHER REQUIREMENTS
 WITHIN THE CAB. THE CONCRETE WALL OPENING AND THE CAB
 OPENING DOES NOT LINE UP, MAKING THE TURN INTO THE CAB
 APPEAR VERY TIGHT FOR CODE COMPLIANCE.
 SHEET 037-A1-1-1C NOR THE SHEET 109-A7-1 SHOW THE CAB
 OF ELEVATOR # 1 ACCOMMODATES THE AMBULANCE STRETCHER
 REQUIREMENTS OF FBC-B 3002.4.
  
 13) COMPLIED.
  
 14A) COMPLIED. GENERATOR IS BEING ADDED TO THE PROJECT.
  
 14B) COMPLIED.
  
 14C) PROVISO: 090-A4-4 DETAILS 1 & 2 FLOOR STRUCTURAL
 MEMBERS ARE 34 INCH DOUBLE T CONCRETE JOIST. THIS WOULD
 PROVIDE AN 8FT.-8 IN. CLEAR SPACE BENEATH THE JOIST,
 DEPENDING ON THE LAYOUT OF THE RAINWATER HORIZONTAL
 RUNS AND FIRE SPRINKLER LAYOUT WHICH HAS NOT YET BEEN
 PROVIDED.2014 FBC-B 406.4.1.
  
 15)COMPLIED
  
 16-17) PROVISO: SHEET 026-LS-0-. FULLY SPRINKLERED
 BUILDING. DEFERRED SUBMITTAL.
  
 18) COMPLIED.
  
 19) 2ND REQUEST. THERE IS NO REVISED SHEET. . THIS
 COMMENT IS COMMON FOR ALL FLOORS. SHEET 055-A1-2-B THE
 FLOOR INDICATES THE ELEVATION OF THE LEVEL FLOOR AT
 38.0 FEET. THE PLANS DO SHOW WHAT APPEARS TO BE FLOOR
 DRAINS BUT THE DIFFERENCE IN ELEVATION IS NOT MARKED ON
 THE PLANS NOR IS THERE ANY NOTES ON THE PLANS
 INDICATING THE DIFFERENCE IN ELEVATION. PLEASE PROVIDE
 COMPLIANCE WITH THE 2014 FBC-B 406.4.5 FLOOR SURFACE.
 THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR
 OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE
 MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN
 VEHICLE ENTRY DOORWAY.
  
 20) SEE COMMENTS FROM THE MECHANICAL REVIEWER 2ND
 REVIEW. PORTIONS OF THE 1ST FLOOR AND 2ND FLOOR ARE
 CONSIDERED AN ENCLOSED PARKING GARAGE, PLEASE IDENTIFY
 WHERE IN EITHER THE ARCHITECTURAL SHEETS OR THE
 MECHANICAL SHEETS COMPLIANCE WITH 2014 FBC-B 406.6.2
 VENTILATION. A MECHANICAL VENTILATION SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL.
  
 21) PROVISO: 2014 FBC-B SECTION [F] 406.6.3 AUTOMATIC
 SPRINKLER SYSTEM. AN ENCLOSED PARKING GARAGE SHALL BE
 EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.2.10.
  
 22) SEE COMMENTS FROM THE MECHANICAL REVIEWER. PLEASE
 PROVIDE WHERE COMPLIANCE WITH FBC-B SECTION 406.8.2
 VENTILATION. REPAIR GARAGES SHALL BE MECHANICALLY
 VENTILATED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL. THE VENTILATION SYSTEM SHALL BE
 CONTROLLED AT THE ENTRANCE TO THE GARAGE.
  
 23) PROVISO: 2014 FBC-B SECTION 406.8.6 AUTOMATIC
 SPRINKLER SYSTEM. A REPAIR GARAGE SHALL BE EQUIPPED
 WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.2.9.1.
  
 24) COMMENT IS NEW FROM THE ORIGINAL COMMENT!!!!! SHEET
 038-A1-1-1D. NEXT TO STAIR 128 THE PLANS INDICATE THE
 USE OF A PLATFORM LIFT. THIS IS NEW CONSTRUCTION PLEASE
 LOOK AT THE SCOPING REQUIREMENT FOR THE LIMITED USE OF
 PLATFORM LISTS ON AN ACCESSIBLE ROUTE IN NEW
 CONSTRUCTION UNDER 2014 FBC-B 206.7.
  
 25) SHEETS 035-A1.1.1A THROUGH 040-A1.1.1F, AND SHEET
 113-A8.0 DOOR SCHEDULE:
  
 25A) PROVISO: DEFERRED SUBMITTAL . DOOR TYPE (N) SHOW
 THEY ARE A HORIZONTAL BI-PARTING DOOR. SHEET 113-A8-0
 INDICATES A DOOR TYPE (N) BUT DOES NOT INDICATE TO
 WHICH CODE SECTION THE DOORS ARE COMPLY 1008.1.4.2
 POWER OPERATED DOORS OR 1008.1.4.3 HORIZONTAL SLIDING
 DOORS OR HOW MUCH FORCE IS TO BE APPLIED TO SET THE
 DOOR IN MOTION. DOORS SHALL BE OPENABLE BY A SIMPLE
 METHOD FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR
 EFFORT, HOW WILL THIS BE ACCOMPLISHED.
  
 25B) COMPLIED
  
 26) PROVISO/ DEFERRRED SUBMITTAL. SHEET 100-A6-2 PLEASE
 PROVIDE HOW THE SKYLIGHT GLAZING IS GOING TO COMPLY
 WITH THE 2014 FBC-B 2405.2 ALLOWABLE GLAZING MATERIALS
 AND LIMITATIONS.
 2405.5 UNIT SKYLIGHTS AND TUBULAR DAYLIGHTING DEVICES.
 UNIT SKYLIGHTS AND TUBULAR DEVICES SHALL BE TESTED AND
 LABELED AS COMPLYING WITH AAMA/WDMA/CSA 101/I.S./A440.
 THE LABEL SHALL STATE THE NAME OF THE MANUFACTURER, THE
 APPROVED LABELING AGENCY, THE PRODUCT DESIGNATION AND
 THE PERFORMANCE GRADE RATING AS SPECIFIED IN
 AAMA/WDMA/CSA 101/I.S.2/ A440. IF THE PRODUCT
 MANUFACTURER HAS CHOSEN TO HAVE THE PERFORMANCE GRADE
 OF THE SKYLIGHT RATED SEPARATELY FOR POSITIVE AND
 NEGATIVE DESIGN PRESSURE, THEN THE LABEL SHALL STATE
 BOTH PERFORMANCE GRADE RATINGS AS SPECIFIED IN
 AAMA/WDMA/ CSA 101/I.S.2/A440 AND THE SKYLIGHT SHALL
 COMPLY WITH SECTION 2405.5.2. IF THE SKYLIGHT IS NOT
 RATED SEPARATELY FOR POSITIVE AND NEGATIVE PRESSURE,
 THEN THE PERFORMANCE GRADE RATING SHOWN ON THE LABEL
 SHALL BE THE PERFORMANCE GRADE RATING DETERMINED IN
 ACCORDANCE WITH AAMA/WDMA/CSA 101/ I.S.2/A440 FOR BOTH
 POSITIVE AND NEGATIVE DESIGN PRESSURE AND THE SKYLIGHT
 SHALL CONFORM TO SECTION 2405.5.1.
  
 27) 2ND REQUEST. SHEET 140-S0.1 . 0143_1.S0.4 &
 143.1_S).4A.
 PLEASE PROVIDE WHERE THE MEAN ROOF HEIGHT FOR THE
 BUILDING IS GIVEN? 2014 FBC-B TABLE 1609.7(2) I CAN
 UNDERSTAND THERE WILL BE ONE SET OF CALCULATIONS UNDER
 COMPONENTS AND CLADDING FOR THE ENCLOSED PORTION OF THE
 BUILDING, BUT WOULDN?T IT BE TAKEN AT THE TOP OF THE
 PARKING GARAGE? THIS IS ONE BUILDING, ONE MEAN ROOF
 HEIGHT. THE ISSUE IS THE DIFFERENT COEFFICIENTS USED
 FOR AN OPEN BUILDING AND ENCLOSED BUILDING. SO WOULDN?T
 THERE BE 2 SCENARIOS A PORTION OF THE BUILDING AS OPEN
 AND A PORTION OF THE BUILDING ENCLOSED?
  
 THE 2ND ISSUE WITH THE UPPER PORTION OF THE CHARTS, FOR
 EXAMPLE THE UPPER LEFT CHARTS THE GROSS ALLOWABLE WIND
 LOADS MAIN ROOF ROOFING MATERIALS IS LISTED WITH
 COMPONENTS AND CLADDING. THE NEXT CHART DOWN THE CHART
 INDICATES NET ALLOWABLE WIND LOADS MAIN ROOF JOIST AND
 STILL LISTED AS COMPONENTS AND CLADDING. JOIST ARE NOT
 COMPONENTS AND CLADDING BUT PART OF THE MWFRS (MAIN
 WIND FORCE RESISTING SYSTEM). THIS OCCURS 4 TIMES ON
 THIS PAGE WHERE IT APPEARS TO BE A DIFFERENCE IN THE
 CORRECT TERMINOLOGY AND ASSOCIATED PRESSURES. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED AND APPEARS TO BE A
 TYPO IN REGARDS TO TERMINOLOGY.
  
 COMMENT 1ST ROUND COMMENTS. SHEET 140-S0.1 STRUCTURAL
 SPECIFICATION NOTES MISC. NOTE # 6 IS THE WIND DESIGN
 CRITERIA, PLEASE ALSO PROVIDE AT WHAT MEAN ROOF HEIGHT
 IS THE PRESSURES FOUND ON SHEET 143-S0.4 TAKEN? UNTIL
 THE MEAN ROOF HEIGHT IS GIVEN THE PRESSURES CANNOT BE
 VERIFIED. 2014 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS
 FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR
 THE BUILDING. MEAN ROOF HEIGHT. THE AVERAGE OF THE ROOF
 EAVE HEIGHT AND THE HEIGHT TO THE HIGHEST POINT ON THE
 ROOF SURFACE, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR
 ROOF ANGLE OF LESS THAN OR EQUAL TO 10 DEGREES (0.18
 RAD).
  
  
 28) 2ND REQUEST. PLEASE PROVIDE THE PRESSURES FOUND ON
 SHEET 143-S0.4 IN VASD SINCE ALL OF THE PRODUCT
 APPROVALS ARE IN VASD. THE INSPECTORS ON SITE WILL BE
 LOOKING FOR THE PRESSURES ON THE S0,4 SHEET TO BE
 INLINE WITH THE PRODUCT APPROVALS. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 29A) PROVISO: DEFERRED SUBMITTALS.
 PLEASE SUBMIT PRODUCT APPROVALS TO COMPLY WITH: 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING, AND
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 29B) PROVISO: DEFERRED SUBMITTALS.
 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 29C) PROVISO: DEFERRED SUBMITTALS. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 30) COMPLIED.
  
 31) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 32) PLANS MISSING THE ELECTRONIC SIGNATURES ON THE
 CIVEL SHEETS AND SITE PLANS, ALSO REVIEWED
 ARCHITECTURAL AND STRUCTURAL.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 33) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-19 Cont ID  
Sent By jwitmer Date 2016-01-19 Time 10:38 Rev Time 0.00
Received By jwitmer Date 2016-01-14 Time 07:15 Sent To  
Notes
2016-01-19 10:38:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120536
 ADD: 2745 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: 561-568-8931
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: FRI. JAN. 15/ 2016
 ACTION: DENIED
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 2G) INFORMATIONAL. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2H) INFORMATIONAL. 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) SHEET 011-INDEX INDICATES SHEETS 028-LS-1W,
 029-LS-2E, 030-LS-2W, 033-A0.1 & 034-A1.1.1 ARE
 MISSING, WERE NOT PART OF THIS SUBMITTAL. A THOROUGH
 REVIEW CANNOT BE MADE AT THIS TIME, AS A RESULT OF THE
 ADDITIONAL INFORMATION REQUESTED ADDITIONAL COMMENTS
 MAY APPEAR THAT WERE NOT PART OF THIS REVIEW.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) PLEASE PROVIDE A SOILS REPORT IN COMPLIANCE WITH:
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) SHEET 027-LS-1E:
 5A) THE PLAN DOES SHOW EXIT DIRECTIONAL AND EXIT
 LIGHTS, BUT THE PLAN DOES NOT PROVIDE A EGRESS PATH,
 INCLUDING MEZZANINE OCCUPANT LOADS, ALLOWABLE OCCUPANT
 LOAD FOR STAIRS PER FBC-B 1005.3.1 AND AS TO WHICH
 DOORS THEY WILL EXIT AND THE ALLOWABLE OCCUPANT LOAD
 PER SET OF DOORS PER FBC-B 1005.3.2.
  
 5B) THE SERVICE VESTIBULE SHOWS THE USE OF A PLATFORM
 LIFT, PLEASE PROVIDE THE MANUFACTURERS SHOP DRAWINGS
 AND OR SPEC SHEET THAT SHOWS THE LIFT COMPLIES WITH
 ASME A18.1 (FBC-ACCESSIBILITY CODE 410.1).
  
 5C) THERE IS AN AREA OF CONCERN, THE DRIVEWAY 170
 APPEARS TO BE A DUAL USE LOADING ZONE FOR THE PARTS
 RECEIVING ROOM 163. THE ISSUE IS BOTH ROOMS THE PARTS
 RECEIVING DOOR AND ROOM 166 DETAIL ROOM BOTH SHOW THE
 EXTERIOR DOOR IS THE EXIT DISCHARGE THAT LEADS INTO A
 COURTYARD AREA THAT IS NOT PROTECTED AS REQUIRED BY
 SECTION 1027.4, 1027.4.1 & 1027.4.2 THAT WILL ALLOW THE
 OCCUPANT TO TRAVEL TO THE PUBLIC WAY. OCCUPANT LOADS
 FOR THESE DOORS HAS NOT BEEN DECLARED SO THE REQUIRED
 WIDTH OF THE EGRESS PATH CANNOT CURRENTLY BE
 DETERMINED.
 5D) THE MEZZANINE LEVEL IS NOT SHOWN ON THE 1ST FLOOR
 LIFE SAFETY PLAN, ALTHOUGH IT IS NOT ANOTHER STORY SEE
 054-A1-2-1A. IT APPEARS THERE ARE 2 MEZZANINES, ONE
 OVER THE BUSINESS OCCUPANCY THE OTHER IN THE PARTS
 STORAGE AREA. THE MEZZANINE LEVEL OVER THE BUSINESS
 OCCUPANCY DOES HAVE WHAT APPEARS TO BE A ELEVATOR TO
 GET A WHEEL CHAIRED CLIENT OR WORKER TO THE UPPER
 PORTION OF THE MEZZANINE BUT THERE ARE STAIRS DOWN TO
 THE CONFERENCE ROOM. NO ACCESSIBILITY TO THE CONFERENCE
 ROOM.
 2014 FBC-B 201.1.1VERTICAL ACCESSIBILITY. 201.1.1
 VERTICAL ACCESSIBILITY. SECTIONS 553.501-553.513, F.S.,
 AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN DO NOT
 RELIEVE THE OWNER OF ANY BUILDING, STRUCTURE OR
 FACILITY GOVERNED BY THOSE SECTIONS FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE AND
 BELOW THE OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER
 THE STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN
 SUCH BUILDING, STRUCTURE OR FACILITY.
  
 203.9 EMPLOYEE WORK AREAS.
 SPACES AND ELEMENTS WITHIN EMPLOYEE WORK AREAS SHALL
 ONLY BE REQUIRED TO COMPLY WITH 206.2.8, 207.1, AND
 215.3 AND SHALL BE DESIGNED AND CONSTRUCTED SO THAT
 INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER, AND
 EXIT THE EMPLOYEE WORK AREA.
  
 5E) SHEET 054-A1-2-1A. THE QUESTION ARISES IS THE
 ELEVATOR ON EMERGENCY POWER? HOW WILL WHEELCHAIR BOUND
 PERSON GET BACK DOWN FROM THE MEZZANINE IN CASE OF LOSS
 OF POWER? . 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
  
 6) SHEET 036-A1-1-1B PARTS STORAGE IS THERE A MEZZANINE
 LEVEL IN THE PARTS STORAGE OR A OPEN GRID SECOND FLOOR?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 7A) SHEET 036-A1-1-1B INDICATES A TIRE CAROUSEL, PLEASE
 PROVIDE MANUFACTURES SPECIFICATIONS AND CUT SHEETS ON
 THIS EQUIPMENT. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 7B) PLEASE PROVIDE THE CUBIC FEET THE TIRE CAROUSEL
 ENCLOSES, MAY NEED TO COMPLY WITH 903.2.9.2 BULK
 STORAGE OF TIRES.
  
 8) SHEET 036-A1-1-1B SERVICE BAY INDICATES THE USE OF
 CAR LIFTS WILL THESE LIFTS BE USING A HYDRAULIC TYPE
 LIFT? IS SO PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B
 SECTION B 3011.1 ELECTROLYSIS PROTECTION FOR
 UNDERGROUND HYDRAULIC ELEVATOR CYLINDERS. ALL NEWLY
 INSTALLED UNDERGROUND HYDRAULIC PRESSURE CYLINDERS
 SHALL BE ENCASED IN OUTER PLASTIC CONTAINMENT TO
 MINIMIZE ELECTROLYTIC CORROSION BETWEEN THE METAL
 CYLINDER AND GROUND CATHODE.
  
 9) SHEET 145-S1.1A IN THE BOTTOM RIGHT SHOWS A KEY
 FOUNDATION PLAN FOR THE FOUNDATION. THE KEY PLAN DOES
 NOT IDENTIFY THE FOUNDATION BEHIND THE BUILDING LABELED
 1. PLEASE PROVIDE WHERE THIS PLAN CAN BE LOCATED.
  
 10) SHEET 037-A1-1-1C INDICATES AN ELEVATOR DETAIL
 FOUND ON 109-A7-1 INDICATING THE ELEVATOR TO THE 6TH
 FLOOR/ ROOF TOP OF THE GARAGE AND SHEET 111-A7-3 BOTH
 APPEAR TO BE A HYDRAULIC TYPE ELEVATOR .
 PLEASE PROVIDE CODE COMPLIANCE WITH 2014 FBC-B 3011.1
 ELECTROLYSIS PROTECTION FOR UNDERGROUND HYDRAULIC
 ELEVATOR CYLINDERS. ALL NEWLY INSTALLED UNDERGROUND
 HYDRAULIC PRESSURE CYLINDERS SHALL BE ENCASED IN OUTER
 PLASTIC CONTAINMENT TO MINIMIZE ELECTROLYTIC CORROSION
 BETWEEN THE METAL CYLINDER AND GROUND CATHODE.
  
 11) SHEET 036-A1-1-1B THE CAR LIFTS DO NOT INDICATE IF
 THE CAR LIFTS ARE A HYDRAULIC TYPE OF ELEVATOR
 REQUIRING COMPLIANCE WITH 2014 FBC-B 3011.1
 ELECTROLYSIS PROTECTION FOR UNDERGROUND HYDRAULIC
 ELEVATOR CYLINDERS.
  
 12) SHEET 037-A1-1-1C NOR THE SHEET 109-A7-1 SHOW THE
 CAB OF ELEVATOR # 1 ACCOMMODATES THE AMBULANCE
 STRETCHER REQUIREMENTS OF FBC-B 3002.4.
  
 13) SHEET 109-A7-1 WILL ALSO NEED TO PROVIDE COMPLIANCE
 WITH FBC-B 3004.2 & 3004.3 VENTING.
  
 14A) SHEET 109-A7-1 SHOWS ELEVATOR # 1 AS THE VERTICAL
 ACCESSIBILITY FOR THE PARKING GARAGE FLOORS.
 IS THE ELEVATOR # 1 TIED TO EMERGENCY POWER TO BE
 CONSIDERED RELIABLE MEANS OF EGRESS IF THE POWER FAILS.
 MISSING THE LIFE SAFETY SHEET FOR THE 2ND FLOOR BUT FOR
 THE 3RD THROUGH THE 6TH FLOOR THE OCCUPANT LOAD IS 259
 PER FLOOR. 2014 FBC-B SECTION 1021.2 REQUIRES AT LEAST
 2 EXITS FROM EACH STORY OR OCCUPIED ROOF.
 THE 2014 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE MEANS
 OF EGRESS SHALL COMPLY WITH THE 2003 IBC SECTION 1007.
 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF EGRESS IS
 REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO ACCESSIBLE MEANS OF EGRESS. PLEASE
 PROVIDE WHAT WILL BE CONSIDERED THE SECOND MEANS OF
 ACCESSIBLE EGRESS FOR THE PARKING GARAGE LEVELS
 2THROUGH 6.
  
 14B) THE PARKING GARAGE. THE PLANS DO NOT INDICATE THE
 USE OF THE PARKING GARAGE OTHER THAN THE STORAGE OF
 CARS. THE PLANS WILL NEED TO CLARIFY IF THE PARKING
 GARAGE IS STRICTLY FOR INVENTORY OF CARS, OR IF BOTH
 INVENTORY OF CARS AND CUSTOMER PARKING? THE QUESTION
 ARISES DOES THE REQUIREMENT FOR ACCESSIBLE PARKING
 SPACES FOR THE PUBLIC WITH ACCESS AISLES COME INTO PLAY
 AS WELL AS HEIGHT REQUIREMENTS FOR VAN PARKING.
 2014 FBC-ACCESSIBILITY CODE 208.3.1, & 502.1 THROUGH
 502.7 EVEN THOUGH THE PARKING GARAGE MAYBE STRICTLY
 USED JUST FOR THE INVENTORY OF AUTOMOBILES.
 PLEASE REVIEW SECTION FBC-ACCESSIBILITY CODE 208.1
 REQUIREMENTS FOR VAN PARKING STRUCTURES. EXCEPTION:
 PARKING SPACES USED EXCLUSIVELY FOR BUSES, TRUCKS,
 OTHER DELIVERY VEHICLES, LAW ENFORCEMENT VEHICLES, OR
 VEHICULAR IMPOUND SHALL NOT BE REQUIRED TO COMPLY WITH
 208 PROVIDED THAT LOTS ACCESSED BY THE PUBLIC ARE
 PROVIDED WITH A PASSENGER LOADING ZONE COMPLYING WITH
 503.
  
 14C) SHEET 090-A4-4 DETAILS 1 & 2 BOTH PROVIDE
 ELEVATIONS FOR THE FINISH FLOOR ON VARIOUS FLOOR LEVELS
 AND DETAIL # 1 INDICATES THE FLOOR STRUCTURAL MEMBERS
 ARE 34 INCH DOUBLE T CONCRETE JOIST. THIS WOULD PROVIDE
 AN 8FT.-8 IN. CLEAR SPACE BENEATH THE JOIST, DEPENDING
 ON THE LAYOUT OF THE RAINWATER HORIZONTAL RUNS AND FIRE
 SPRINKLER LAYOUT WHICH HAS NOT YET BEEN PROVIDED.2014
 FBC-B 406.4.1.
  
 15A) SHEET 079-A3-0 HEADING PARKING GARAGE CALCULATIONS
 PLEASE ADD AN ADDITIONAL COLUMN PER 2014
 FBC-B SECTION 406.2. THE AREA OF SUCH OPENINGS IN
 EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20
 PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER.
  
 15B) IN THE 2014 FBC-B SECTION 406.5.2 THE CODE ALSO
 REQUIRES THE INTERIOR WALLS SHALL BE NOT LESS THAN 20
 PERCENT OPEN WITH UNIFORMLY DISTRIBUTED OPENINGS.
 PLEASE ADD ANOTHER COLUMN TO THE HEADING PARKING GARAGE
 CALCULATIONS SHOWING CODE COMPLIANCE.
 16A) SHEET 026-LS-0-1 UNDER THE HEADING OF APPLICABLE
 CODES INDICATES THIS BUILDING IS TO BE A 1B TYPE OF
 CONSTRUCTION. FULLY SPRINKLERED BUILDING. THE INDEX
 SHEET 001 DOES NOT INDICATE ANY FIRE SPRINKLER PLANS TO
 BE INCORPORATED WITHIN THE SET OF DRAWINGS. THE PLANS
 SHEET 026-LS-0.1 INDICATES AREA INCREASES WERE TAKEN
 FOR FIRE SPRINKLERING OF THE WHOLE BUILDING.
  
 16B) SHEETS 108-A7-0 STAIR 3 (ASSUMED STAIR 2 IS ALIKE
 BUT OPPOSITE) SHOWS FLOOR PLAN VIEW AS WELL AS A CUT
 SECTION THROUGH THE STAIR TOWER BUT THERE IS NO MENTION
 OR DETAILS OF HOW THE OPEN PARKING GARAGE IS GOING TO
 BE FIRE SPRINKLERED AS WELL AS THE 6TH FLOOR OR ROOF
 LEVEL. THIS LEVEL IS OCCUPIED (USABLE) SPACE AND
 CONSIDERED A STORY? THE PLANS DO NOT PROVIDE A STAND
 PIPE IN ANY OF THE STAIR TOWERS, 1,2 OR 3. SEE 2014
 FBC-B 406.5.8.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (5.) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
  
 17) SHEET 109-A7-1 ALSO IS LACKING THE REQUIRED
 STANDPIPE WITHIN THE STAIRWELL AND HOW THE UPPER LEVEL
 THE 6TH FLOOR/ ROOF TOP PARKING LEVEL WILL ACHIEVE CODE
 COMPLIANCE.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (5.) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
  
 18A) PLEASE SHOW WHERE THE PLANS CAN SHOW COMPLIANCE
 WITH THE 2014 FBC-B SECTION 406.4.3 VEHICLE BARRIERS.
 VEHICLE BARRIERS NOT LESS THAN 2 FEET 9 INCHES (835 MM)
 IN HEIGHT SHALL BE PLACED AT THE ENDS OF DRIVE LANES,
 AND AT THE END OF PARKING SPACES WHERE THE VERTICAL
 DISTANCE TO THE GROUND OR SURFACE DIRECTLY BELOW IS
 GREATER THAN 1 FOOT (305 MM). VEHICLE BARRIERS SHALL
 COMPLY WITH THE LOADING REQUIREMENTS OF SECTION
 1607.8.3.
  
 18B) PLEASE SHOW WHERE THE PLANS CAN SHOW COMPLIANCE
 WITH THE 2014 FBC-B SECTION 406.4.2 GUARDS.
 GUARDS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 1013. GUARDS SERVING AS VEHICLE BARRIERS SHALL COMPLY
 WITH SECTIONS 406.4.3 AND 1013.
  
 19) THIS COMMENT IS COMMON FOR ALL FLOORS. SHEET
 055-A1-2-B THE FLOOR INDICATES THE ELEVATION OF THE
 LEVEL FLOOR AT 38.0 FEET. THE PLANS DO SHOW WHAT
 APPEARS TO BE FLOOR DRAINS BUT THE DIFFERENCE IN
 ELEVATION IS NOT MARKED ON THE PLANS NOR IS THERE ANY
 NOTES ON THE PLANS INDICATING THE DIFFERENCE IN
 ELEVATION. PLEASE PROVIDE COMPLIANCE WITH THE 2014
 FBC-B 406.4.5 FLOOR SURFACE.
 THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR
 OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE
 MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN
 VEHICLE ENTRY DOORWAY.
  
 20) PORTIONS OF THE 1ST FLOOR AND 2ND FLOOR ARE
 CONSIDERED AN ENCLOSED PARKING GARAGE, PLEASE IDENTIFY
 WHERE IN EITHER THE ARCHITECTURAL SHEETS OR THE
 MECHANICAL SHEETS COMPLIANCE WITH 2014 FBC-B 406.6.2
 VENTILATION. A MECHANICAL VENTILATION SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL.
  
 21) PLEASE PROVIDE WHERE IN THE SUBMITTED PLANS
 COMPLIANCE WITH FBC-B SECTION [F] 406.6.3 AUTOMATIC
 SPRINKLER SYSTEM. AN ENCLOSED PARKING GARAGE SHALL BE
 EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.2.10.
  
 22) PLEASE PROVIDE WHERE COMPLIANCE WITH FBC-B SECTION
 406.8.2 VENTILATION. REPAIR GARAGES SHALL BE
 MECHANICALLY VENTILATED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL. THE VENTILATION SYSTEM SHALL
 BE CONTROLLED AT THE ENTRANCE TO THE GARAGE.
  
 23) PLEASE PROVIDE WHERE COMPLIANCE WITH FBC-B SECTION
 406.8.6 AUTOMATIC SPRINKLER SYSTEM.
 A REPAIR GARAGE SHALL BE EQUIPPED WITH AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.2.9.1.
  
 24) SHEET 038-A1-1-1D. NEXT TO STAIR 128 THE PLANS
 INDICATE THE USE OF A PLATFORM LIFT, PLEASE PROVIDE
 COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE 410.1
 THROUGH 410.6.
  
 25) SHEETS 035-A1.1.1A THROUGH 040-A1.1.1F, AND SHEET
 113-A8.0 DOOR SCHEDULE:
  
 25A) DOOR TYPE (N) SHOW THEY ARE A HORIZONTAL
 BI-PARTING DOOR. SHEET 113-A8-0 INDICATES A DOOR TYPE
 (N) BUT DOES NOT INDICATE TO WHICH CODE SECTION THE
 DOORS ARE COMPLY 1008.1.4.2 POWER OPERATED DOORS OR
 1008.1.4.3 HORIZONTAL SLIDING DOORS OR HOW MUCH FORCE
 IS TO BE APPLIED TO SET THE DOOR IN MOTION. DOORS SHALL
 BE OPENABLE BY A SIMPLE METHOD FROM BOTH SIDES WITHOUT
 SPECIAL KNOWLEDGE OR EFFORT, HOW WILL THIS BE
 ACCOMPLISHED.
  
 25B) SHEET 039-A1-1-1E DOOR 121 IS IDENTIFIED ON THE
 PLAN AS A SLIDING GLASS DOOR. SHEET 113-A8-0 INDICATES
 THIS DOOR TYPE AS DOOR TYPE ( E ), WHICH IS A SWING
 TYPE OF DOOR. 107.2.1.3 IT APPEARS TO BE A TYPO,
 ADDITIONAL INFORMATION IS REQUIRED.
  
 26) SHEET 100-A6-2 PLEASE PROVIDE HOW THE SKYLIGHT
 GLAZING IS GOING TO COMPLY WITH THE 2014 FBC-B 2405.2
 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS.
 2405.5 UNIT SKYLIGHTS AND TUBULAR DAYLIGHTING DEVICES.
 UNIT SKYLIGHTS AND TUBULAR DEVICES SHALL BE TESTED AND
 LABELED AS COMPLYING WITH AAMA/WDMA/CSA 101/I.S./A440.
 THE LABEL SHALL STATE THE NAME OF THE MANUFACTURER, THE
 APPROVED LABELING AGENCY, THE PRODUCT DESIGNATION AND
 THE PERFORMANCE GRADE RATING AS SPECIFIED IN
 AAMA/WDMA/CSA 101/I.S.2/ A440. IF THE PRODUCT
 MANUFACTURER HAS CHOSEN TO HAVE THE PERFORMANCE GRADE
 OF THE SKYLIGHT RATED SEPARATELY FOR POSITIVE AND
 NEGATIVE DESIGN PRESSURE, THEN THE LABEL SHALL STATE
 BOTH PERFORMANCE GRADE RATINGS AS SPECIFIED IN
 AAMA/WDMA/ CSA 101/I.S.2/A440 AND THE SKYLIGHT SHALL
 COMPLY WITH SECTION 2405.5.2. IF THE SKYLIGHT IS NOT
 RATED SEPARATELY FOR POSITIVE AND NEGATIVE PRESSURE,
 THEN THE PERFORMANCE GRADE RATING SHOWN ON THE LABEL
 SHALL BE THE PERFORMANCE GRADE RATING DETERMINED IN
 ACCORDANCE WITH AAMA/WDMA/CSA 101/ I.S.2/A440 FOR BOTH
 POSITIVE AND NEGATIVE DESIGN PRESSURE AND THE SKYLIGHT
 SHALL CONFORM TO SECTION 2405.5.1.
  
 27) SHEET 140-S0.1 STRUCTURAL SPECIFICATION NOTES MISC.
 NOTE # 6 IS THE WIND DESIGN CRITERIA, PLEASE ALSO
 PROVIDE AT WHAT MEAN ROOF HEIGHT IS THE PRESSURES FOUND
 ON SHEET 143-S0.4 TAKEN? UNTIL THE MEAN ROOF HEIGHT IS
 GIVEN THE PRESSURES CANNOT BE VERIFIED. 2014 FBC-B
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. MEAN ROOF HEIGHT. THE AVERAGE OF THE ROOF
 EAVE HEIGHT AND THE HEIGHT TO THE HIGHEST POINT ON THE
 ROOF SURFACE, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR
 ROOF ANGLE OF LESS THAN OR EQUAL TO 10 DEGREES (0.18
 RAD).
  
  
 28) PLEASE PROVIDE THE PRESSURES FOUND ON SHEET
 143-S0.4 IN VASD SINCE ALL OF THE PRODUCT APPROVALS ARE
 IN VASD. THE INSPECTORS ON SITE WILL BE LOOKING FOR THE
 PRESSURES ON THE S0,4 SHEET TO BE INLINE WITH THE
 PRODUCT APPROVALS. 1609.3.1 WIND SPEED CONVERSION VULT
 TO VASD.
  
 29A) PLEASE SUBMIT PRODUCT APPROVALS TO COMPLY WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING, AND
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 29B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 29C) THE CONTRACTOR OR DESIGNER OF RECORD MAY ELECT TO
 : 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 30A) PLEASE PROVIDE COMPLIANCE WITH:2014 FBC-B 1013.6
 MECHANICAL EQUIPMENT. GUARDS SHALL BE PROVIDED WHERE
 APPLIANCES, EQUIPMENT, FANS, ROOF HATCH OPENINGS OR
 OTHER COMPONENTS THAT REQUIRE SERVICE ARE LOCATED
 WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF
 A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED
 MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR
 GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN
 DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN 30
 INCHES (762 MM) BEYOND EACH END OF SUCH APPLIANCE,
 EQUIPMENT, FAN OR COMPONENT.
  
 30B) 2014 FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE
 PROVIDED WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN
 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A
 WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED
 MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR
 GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN
 DIAMETER.
  
 30C) 2014 FBC-B 1509.6 MECHANICAL EQUIPMENT SCREENS.
 MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF
 THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN
 ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE
 BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER
 THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS
 SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
 31) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 32) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-20 Cont ID  
Sent By vperez Date 2016-05-20 Time 12:14 Rev Time 0.00
Received By vperez Date 2016-05-20 Time 12:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-31 Cont ID  
Sent By vperez Date 2016-03-31 Time 07:53 Rev Time 0.00
Received By vperez Date 2016-03-31 Time 07:53 Sent To  
Notes
2016-03-31 08:00:002ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS:
  
 THE BELOW COMMENTS AS PREVIUOSLY STATED WILL REQUIRE
 AHJ APPROVAL, PLEASE MAKE ARRANGEMENTS TO CONTACT
 ROBERT BROWN (BO) OR DOUG HARVEY (ABO)
 ALL OTHER COMMENTS ADDRESSED EXCEPT THE BELOW INITIAL
 REVIEW COMMENTS
  
  
 13. SHEET 3.1- PLEASE NOTE THAT ALL MAIN DISCONNECTS
 MUST BE GROUPED AT THE SAME LOCATION PER NEC 230.72A.
 ALSO NEC 230.2 REQUIRES THAT BUILDINGS BE SUPPLIED BY
 ONLY ONE SERVICE UNLESS PERMITTED BY NEC 230.2A THROUGH
 230.2D. THE ARRANGEMENTS OF THE ELECTRICAL SERVICE
 SHOWN PER PHASING INTENT MUST BE APPROVED BY SPECIAL
 PERMISSION OF THE AHJ. PROVIDE REQUEST IN WRITING WHICH
 IS SUBJECT TO APPROVAL.
 14. SHEET 3.2- RISER DIAGRAM AT THIS TIME WILL NEED TO
 BE REVISITED PENDING APPROVAL AS NOTED IN COMMENT #13.
 SEE ABOVE.
 15. SHEETS 4.1 THROUGH 4.4- PANEL SCHEDULES AT THIS
 TIME WILL NEED TO BE REVISITED PENDING APPROVAL AS
 NOTED IN COMMENT #13. SEE ABOVE.
 16. SHEET 5.3- ELECTRICAL ROOMS MUST COMPLY WITH NEC
 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF
 THE WORKING SPACE. SHOW TWO MEANS OF EXIT FOR ROOM 170.
 ALSO NEC 110.26C3 REQUIRES PERSONNEL DOORS TO BE
 EQUIPPED WITH PANIC HARDWARE AND OPEN IN THE DIRECTION
 OF EGRESS. A NOTE WILL SUFFICE.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By vperez Date 2016-02-08 Time 14:28 Rev Time 0.00
Received By vperez Date 2016-02-05 Time 11:34 Sent To  
Notes
2016-02-08 14:30:53INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. SHEET E0.1- PLEASE UPDATE GENERAL NOTE TO INDICATE
 AND REFLECT THE CURRENT FBC 2014 5TH EDITION AS THE
 CODE IN EFFECT AT THE TIME OF THIS REVIEW.
 2. SHEET ES1.1- PLEASE ADD A GENERAL NOTE TO SHEET TO
 INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE
 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND
 THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE
 LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL
 SUFFICE
 3. SHEET ES1.1- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR ALL SITE LIGHTING AND ASSOCIATED EQUIPMENT,
 GENERATOR, ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT
 LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND
 DATA, SIGNAGE, WIRELESS SYSTEMS, CAR CHARGING STATIONS,
 ETC. A NOTE WILL SUFFICE.
 4. SHEET E1.0- PLEASE LABEL RECEPTACLE ON CIRCUIT L32
 TO BE GFCI PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF
 SINK ALL TO BE GFCI.
 5. SHEET E1.0- NOTE INDICATING THE CLASSIFICATION OF
 AREAS AS NOTED IN NEC 511.3 IS TOO VAGUE AS TO THE
 AREA, PER ENGINEER OF RECORD (EOR) THAT ARE TO BE
 CLASSIFIED. PLEASE CLARIFY THE DESIGN INTENT AND LABEL
 THE FLOOR PLANS ACCORDINGLY.
 6. SHEET E1.1- THE RECEPTACLE OUTLETS IN THE BREAK ROOM
 THAT ARE WITHIN 6FT OF THE SINK MUST BE LABELED GFCI
 NEC 210.8B5
 7. SHEET E1.1- THE RECEPTACLES OUTLETS SERVING THE
 SERVICE BAY REPAIR AREAS MUST ALL BE GFCI PROTECTED PER
 NEC 511.12, ROOM 169.
 8. SHEET E1.2- THE RECEPTACLE OUTLETS IN THE BREAK ROOM
 THAT ARE WITHIN 6FT OF THE SINK MUST BE LABELED GFCI
 NEC 210.8B5
 9. SHEET 1.3- LABEL CIRCUIT L7-26 TO DRINKING FOUNTAIN
 GFCI PROTECTED PER NEC 422.52
 10. SHEET 1.3- THE RECEPTACLES OUTLETS SERVING THE
 SERVICE BAY REPAIR AREAS MUST ALL BE GFCI PROTECTED PER
 NEC 511.12
 11. SHEET 1.4- THE RECEPTACLES OUTLETS SERVING THE
 SERVICE BAY REPAIR AREAS MUST ALL BE GFCI PROTECTED PER
 NEC 511.12
 12. SHEET 1.4- THE FIRE PUMP NOTES INDICATE ?DRAWINGS
 TO BE PROVIDED BY OTHERS? A COMPLETE REVIEW COULD NOT
 BE PERFORMED AT THIS TIME.
 13. SHEET 3.1- PLEASE NOTE THAT ALL MAIN DISCONNECTS
 MUST BE GROUPED AT THE SAME LOCATION PER NEC 230.72A.
 ALSO NEC 230.2 REQUIRES THAT BUILDINGS BE SUPPLIED BY
 ONLY ONE SERVICE UNLESS PERMITTED BY NEC 230.2A THROUGH
 230.2D. THE ARRANGEMENTS OF THE ELECTRICAL SERVICE
 SHOWN PER PHASING INTENT MUST BE APPROVED BY SPECIAL
 PERMISSION OF THE AHJ. PROVIDE REQUEST IN WRITING WHICH
 IS SUBJECT TO APPROVAL.
 14. SHEET 3.2- RISER DIAGRAM AT THIS TIME WILL NEED TO
 BE REVISITED PENDING APPROVAL AS NOTED IN COMMENT #13.
 SEE ABOVE.
 15. SHEETS 4.1 THROUGH 4.4- PANEL SCHEDULES AT THIS
 TIME WILL NEED TO BE REVISITED PENDING APPROVAL AS
 NOTED IN COMMENT #13. SEE ABOVE.
 16. SHEET 5.3- ELECTRICAL ROOMS MUST COMPLY WITH NEC
 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF
 THE WORKING SPACE. SHOW TWO MEANS OF EXIT FOR ROOM 170.
 ALSO NEC 110.26C3 REQUIRES PERSONNEL DOORS TO BE
 EQUIPPED WITH PANIC HARDWARE AND OPEN IN THE DIRECTION
 OF EGRESS. A NOTE WILL SUFFICE.
 17. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-12-30 Cont ID  
Sent By cranford Date 2015-12-30 Time 10:54 Rev Time 0.00
Received By cranford Date 2015-12-30 Time 10:18 Sent To  
Notes
2015-12-30 10:54:55SEE ENGINEERING REVIEW UNDER E15120026
  
 ALSO UNDER ADDRESS 2901 OKEECHOBEE BLVD

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-06 Cont ID  
Sent By scaldero Date 2016-04-06 Time 16:15 Rev Time 0.00
Received By scaldero Date 2016-04-06 Time 15:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-01-12 Cont ID  
Sent By scaldero Date 2016-01-12 Time 17:19 Rev Time 0.00
Received By scaldero Date 2016-01-12 Time 16:48 Sent To  
Notes
2016-01-12 17:19:03PERMIT # 15120536
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) INDEX LISTS SHEETS THAT ARE MISSING FROM THIS PLAN:
 LS-1W, LS-E, LS-2W, A.01, AND A1.1.1.
  
 2) SHEET AUTOTURN: THE "S" TURN ON THE SOUTH SIDE
 ENTRANCE SHOWS ENCROACHMENT ON THE CURBS. RECOMMEND
 REDUCING SIZE OF THE ISLANDS/BUFFERS AND SOFTENING THE
 TURN. ADDITIONALLY, THERE IS CONCERN THAT IF THE ACCESS
 GATES, AT THIS SAME ENTRANCE, ARE FULLY OPEN (BOTH
 SIDES) THE WEST SIDE GATE MAY IMPEDE EMERGENCY VEHICLE
 ACCESS.
  
 3) SHEET AUTOTURN: EXITING FROM THE PARKING GARAGE
 ALONG THE NORTH SIDE BRINGS SIMILAR CONCERNS. PLEASE
 INDICATE WHAT THE RECTANGLE TO THE EAST OF THAT ACCESS
 POINT REFERS TO. IS IT A STEP-UP TO THE DOORS? AN
 ISLAND TO PROTECT PEDESTRIANS? ETC?
  
 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 5) LIFE SAFETY SHEETS PROVIDED ARE LACKING REQUIRED
 DETAILS. PROVIDE A LIFE SAFETY PLAN SHOWING ALL
 OCCUPANCY TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL ETC.
  
 6) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 7) FIRE LANES ARE NOT INDICATED ON THE LIFE SAFETY
 SHEETS OR SITE PLAN SHEETS. PER SECTION 18.2.3.5.3
 (NFPA 1), FIRE LANES SHALL BE MARKED WITH FREESTANDING
 SIGNS READING, ?FIRE LANE - NO PARKING BY ORDER OF THE
 FIRE DEPARTMENT.? SIGNS SHALL BE 12? X 18? WITH A WHITE
 BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF
 SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS
 SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED
 A MAXIMUM OF 60 FEET APART.
  
 8)SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 9) PER SECTION 7.2.2.5.4 - STAIRWAY IDENTIFICATION: NEW
 ENCLOSED STAIRS SERVING THREE OR MORE STORIES AND
 EXISTING ENCLOSED STAIRS SERVING FIVE OR MORE STORIES
 SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS ?NO ROOF ACCESS? AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER ?B?
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 10) PROVIDE ADDITIONAL DETAILS/CLARIFICATION REGARDING
 THE TIRE CAROUSEL AND METHOD OF TIRE STORAGE.
  
 GENERAL COMMENTS:
  
 1) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 2) STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 3) PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 4) PROVIDE A KNOX KEY SWITCH TO ALLOW GATE ACCESS TO
 EMERGENCY RESPONDERS. KEY SWITCH CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-06-09 Cont ID  
Sent By ccole Date 2016-06-09 Time 14:34 Rev Time 0.00
Received By ccole Date 2016-05-18 Time 08:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-28 Cont ID  
Sent By lmarchan Date 2016-04-28 Time 08:01 Rev Time 0.00
Received By lmarchan Date 2016-03-25 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-08 Cont ID  
Sent By vperez Date 2016-02-08 Time 14:31 Rev Time 0.00
Received By vperez Date 2016-02-08 Time 14:31 Sent To  
Notes
2016-02-08 14:32:05EMAIL SENT TO CAROLINE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-18 Cont ID  
Sent By lmarchan Date 2015-12-18 Time 10:37 Rev Time 0.00
Received By lmarchan Date 2015-12-17 Time 14:32 Sent To  
Notes
2015-12-18 10:37:29APPLICANT NEEDS TO FIX PAGES THAT ARE BLANK.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-06-07 Cont ID  
Sent By jwitmer Date 2016-06-07 Time 08:55 Rev Time 0.00
Received By jwitmer Date 2016-06-07 Time 08:55 Sent To  
Notes
2016-06-07 08:55:34FOUNDATION PERMIT: 16020586
 P. B. C. IMPACT FEES ASSESSMENT
 03/21/ 2016
 RECEIPT NO: 20160321-263
 MU-2016-004100-0000
 AMOUNT: $229,375.63
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-04-15 Cont ID  
Sent By   Date 2016-04-15 Time   Rev Time 0.00
Received By   Date 2016-04-15 Time   Sent To  
Notes
2016-04-15 09:33:11 
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-01-19 Cont ID  
Sent By jwitmer Date 2016-01-19 Time 10:39 Rev Time 0.00
Received By jwitmer Date 2016-01-19 Time 10:39 Sent To  
Notes
2016-01-19 10:39:27IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-06-09 Cont ID  
Sent By ccole Date 2016-06-09 Time 14:34 Rev Time 0.00
Received By ccole Date 2016-05-26 Time 17:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-29 Cont ID  
Sent By ccole Date 2016-03-29 Time 16:52 Rev Time 0.00
Received By ccole Date 2016-03-29 Time 16:52 Sent To  
Notes
2016-03-29 16:52:412ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120536
 3/29/16
  
 1) 1ST REVIEW COMMENTS #1 & 2 STILL EXIST. PLEASE
 PROVIDE THE REVISED ENERGY CALCULATIONS AND INCLUDE
 COMPLIANCE DATA IN THE CALCULATIONS FOR THE NEW MS-6 &
 7 SYSTEMS.
 2) 1ST REVIEW COMMENT #4 STILL EXISTS. PLEASE NOTE THAT
 SYSTEMS THAT HAVE COOLING CAPACITIES GREATER THAN
 65,000 BTUH MUST MEET THE MINIMUM EER NOT SEER- SEE
 TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION.
 3) THE NARRATIVE RESPONSE FROM THE EOR TO COMMENTS #5 &
 6 INDICATE NATURAL AIR INFILTRATION IS TO BE USED TO
 PROVIDE THE REQUIRED O/A AIR FOR THE SYSTEMS, HOWEVER
 THESE SYSTEMS ARE ALSO PROVIDING THE MAKE-UP AIR FOR
 THE EXHAUST SYSTEMS- REFER TO SECTION 501.4 FBC-14
 MECHANICAL WHICH STATES THAT THE CALCULATED BUILDING
 AIR INFILTRATION RATE SHALL NOT BE USED AS A COMPONENT
 OF A MAKE-UP AIR SYSTEM.
 4) SHEET M0.3: A) THE MODEL NUMBER AND SENSIBLE BTU
 CAPACITY LISTED FOR AHU-4/CU-4 DO NOT APPEAR TO BE
 CORRECT. B) AHU-11/CU-11 SYSTEM SHOULD HAVE AN EER PER
 TABLE C404.2.3(1).
 5) M1.0: THE SERVICE RECEPTION GARAGE REQUIRES AN
 EXHAUST SYSTEM PER SECTION 404.1 FBC-14 MECHANICAL. CO2
 AND NO2 SENSORS ARE SHOWN ON THE PLANS, HOWEVER NO
 EXHAUST SYSTEM IS SHOWN, AND THERE IS NO EXHAUST FAN
 DESIGNATED FOR THAT AREA IN THE EQUIPMENT SCHEDULE.
 6) M1.1: LABEL THE O/A INTAKE LOUVER FOR AHU-4 & 5.
 7) COMMENT #14 FROM THE 1ST REVIEW HAS NOT BEEN
 COMPLETELY ADDRESSED. PLEASE PROVIDE THE REQUESTED
 EXHAUST CALCULATION ON THE PLAN, INDICATE THE TYPE AND
 SIZE (DIMENSIONS) OF THE MAKE-UP AIR INTAKE, AND
 PROVIDE A SUBMITTAL REVIEWED AND APPROVED BY THE EOR.
 8) COMMENT #15 STILL EXISTS: NEITHER THE MECHANICAL OR
 FIRE ALARM PLANS ARE INDICATING A SEQUENCE OF OPERATION
 FOR THE DUCT SMOKE DETECTORS. PLEASE REVIEW THE
 PREVIOUS COMMENT AND SHOW COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-30 Cont ID  
Sent By ccole Date 2015-12-30 Time 12:12 Rev Time 0.00
Received By ccole Date 2015-12-29 Time 12:12 Sent To  
Notes
2015-12-30 14:32:431ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120536
 12/30/15
  
 1) THE ENERGY CALCULATION FORM 506-2014 MUST BE
 CERTIFIED WITH SIGNATURES OF THE LICENSED DESIGN
 PROFESSIONALS OF THE PROPOSED PROJECT- SECTION C103.1.1
 FBC-14 ENERGY CONSERVATION.
 2) THE ASHRAE 90.1 MANDATORY COMPLIANCE CHECKLIST MUST
 BE COMPLETED AND ATTACHED TO FORM 506-2014.
 3) ENERGY COMPLIANCE DATA FOR THE FOLLOWING SYSTEMS
 SHOWN ON THE PLANS WAS NOT LISTED IN FORM 506-2014:
 RTU'S 6, 7, 8, 9, & 10; AHU'S 6, 7, 8, 9, & 10; AND
 MINI-SPLIT SYSTEMS MS- 1, 2, 4, & 5.
 4) RTU-3 IS LISTED AS 13 SEER IN THE AC SCHEDULE BUT
 LISTED AS 12 EER IN FORM 506-2014- PLEASE SEE TABLE
 C403.2.3(1) FBC-14 ENERGY CONSERVATION.
 5) THE AC LOAD CALCS INDICATE 4575 CFM'S OF OUTSIDE
 VENTILATION AIR FOR AHU- 1&2, HOWEVER THOSE SYSTEMS ARE
 NOT INCLUDED IN THE OUTDOOR AIR CALCULATIONS AND
 SCHEDULE ON SHEET M0.2, AND THERE IS NO O/A DUCT SHOWN
 ON THE PLANS FOR THOSE UNITS.
 6) THE AC LOAD CALCS INDICATE 522 CFM'S OF OUTSIDE
 VENTILATION AIR FOR AHU-11, HOWEVER THE SYSTEM IS NOT
 INCLUDED IN THE O/A CALCS OR SCHEDULE ON M0.2, AND
 THERE IS NO O/A DUCT SHOWN ON THE PLAN FOR THE SYSTEM.
 7) PLEASE REMOVE RTU-5 FROM THE O/A SCHEDULE: IT IS NOT
 IN THE EQUIPMENT SCHEDULE OR THE CALCS.
 8) HOW IS O/A BEING PROVIDED TO AHU'S 3, 4, 5, & 9. THE
 PLAN DOES NOT INDICATE A MEANS OF SUPPLY.
 9) M0.2: THE O/A CALCULATION FOR THE PORSCHE SHOWROOM
 (RTU-1) IS INCORRECT. THE MINIMAL O/A REQUIRED IS 822
 CFM'S. PLEASE REVIEW THE AC LOAD CALCS FOR THE SYSTEM.
 10) M1.0: PLEASE REVIEW SECTION 3006.2 FBC-14 BUILDING
 (VENTING FOR ELEVATOR MACHINE ROOMS). CLARIFY IF THE
 STORAGE ROOM BY THE ELEVATOR MEETS THE CRITERIA LISTED
 IN THE CODE SECTION. PLEASE NOTE AN INDEPENDENT AC
 SYSTEM MAY BE REQUIRED.
 11) M1.0A: THE E90 DIFFUSERS SHOWN AT ELEVATOR 2 AND
 THE SEATING AREA ARE MISLABELED PER THE TERMINAL
 SCHEDULE ON M0.1.
 12) M1.1: THE EXHAUST TERMINATION OUTLETS FOR EF-3, & 4
 ARE NOT SHOWN TO BE DISCHARGING TO THE EXTERIOR OF THE
 BUILDING. PLEASE CLARIFY AND SEE SECTION 501.3.1 FOR
 COMPLIANCE REQUIREMENTS.
 13) M1.2: THE EB150 RETURN GRILLS IN THE LOCKER ROOMS
 ARE MISLABELED PER THE TERMINAL SCHEDULE ON M0.1.
 14) M1.5: CLARIFY HOW MAKE-UP AIR IS BEING PROVIDED FOR
 GARAGE LEVEL 2 EXHAUST, AND PROVIDE A CALCULATION.
 15) PROVIDE A SEQUENCE OF OPERATION FOR THE DUCT SMOKE
 DETECTORS, AND CLARIFY IF SYSTEMS IN THE SAME FIRE
 AREAS OR FLOORS WILL BE LINKED TOGETHER FOR FAN
 SHUTDOWN. IF THESE DETAILS ARE ON THE FIRE ALARM PLANS
 PLEASE REFERENCE THE SHEET NUMBER ON THE MECHANICAL
 PLANS.
 16) PROVIDE SUPPORT AND HANGING DETAILS FOR
 INSTALLATION OF THE AHU'S AND VAV BOXES.
 17) INDICATE HOW ACCESS FOR SERVICING AND REPLACEMENT
 OF THE AHU'S AND VAV BOXES WILL BE PROVIDED- SECTION
 306.1 FBC-14 MECHANICAL.
 18) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE C0 AND
 N02 DETECTORS WITH REVIEW AND APPROVAL SIGNATURES FROM
 THE ENGINEER OF RECORD.
 19) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOA'S FOR THE EXHAUST AND AIR INTAKE LOUVERS, THE ROOF
 STANDS, AND THE RTU CURBS, AND THE ROOF FAN CURBS. ALL
 DOCUMENTS SHALL BEAR REVIEW AND APPROVAL SIGNATURES BY
 THE EOR.
 20) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 PLANS AND DETAILS FOR THE AHU'S AND THE MINI-SPLITS.
 PLEASE SHOW THE PIPING RUNS AND DISCHARGE LOCATIONS ON
 THE PLANS.
 21) SITE SPECIFIC ENEGINEERING IS REQUIRED FOR TIE-DOWN
 OF ALL ROOF TOP MECHANICAL EQUIPMENT- SECTION 301.15
 FBC-14 MECHANICAL. THE DETAILS ON SHEET M5.0 ARE
 INCOMPLETE AND REQUIRE SUBMITTALS FOR CURBS AND STANDS
 THAT HAVE BEEN REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD. THE ENGINEER OF RECORD SHALL PROVIDE THE NOA
 NUMBERS FOR THE COMPONENTS ON THE BOTH THE STRUCTURAL
 AND MECHANICAL PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-05-25 Cont ID  
Sent By gjohnson Date 2016-05-25 Time 15:15 Rev Time 0.00
Received By gjohnson Date 2016-05-23 Time 16:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-04-19 Cont ID  
Sent By gjohnson Date 2016-04-19 Time 09:39 Rev Time 0.00
Received By gjohnson Date 2016-04-19 Time 09:39 Sent To  
Notes
2016-04-19 11:07:57PLUMBING COMMENTS:
  
 1. SHT. P1.1 THE TRENCH DRAIN SHOWS A SECOND PIPE
 CONNECTED TO IT NOT TIED TO OIL SEPARATOR .
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 2. ORIGINAL COMMENT STATES SHT.A2.0 - DETAIL #1 - THE
 DOORS TO RESTROOMS #213 & 214 CANNOT SWING INTO THE
 CLEA R FLOOR SPACE FOR THE LAVATORIES. 2014 FBC-ACCESS.
 SEC.603.2.3. (SEE EXCEPTION #2). 2ND REVIEW YOU SHOW
 COMPLIANCE WITH EXCEPTION IN BATHROOM 213 BUT NO IN 214
 .
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 3.SHT. A2.1 - DETAIL #1 - SHOW THE INSIDE CLEAR
 DIMENSION OF THE ACCESSIBLE STALL IN THE WOMEN'S
 RESTROOM. MINIMUM WIDTH IS 85 INCHES. 86 INCHES ALLOWS
 FOR TOLERANCE. ALSO, SHOW THE FIXTURE CLEARANCE OF THE
 WATER CLOSET IN THE STALL FROM THE SIDE WALL TO THE
 CENTERLINE OF THE WATER CLOSET. 2ND REQUEST
  
 4. SHT. A10.1 THE TOP OF URINAL SCREEN SHOWS 56IN.
 ABOVE FF IT SHALL BE A MIN. OF 60IN.
 PER FBC SEC. 1210.3.2
  
 5. SHT. P1.1 RM # 171
 (A) PROVIDE PIPING DIAGRAM FOR M OIL MANAGEMENT
 CONTROLLER
 (B) THE TANKS THAT ARE LABELED M ARE THEY FOR STORAGE
 OF OIL MEASURED IN GALLONS PLEASE CLARIFY.
 (C) WHAT ARE H AND K FOR PLEASE CLARIFY.
 (D) IT APPEARS THAT THE PARTS WASHER IS LABELED AS M
 FOR OIL MANAGEMENT CONTROLLER PLEASE CLARIFY
 (E) PROVIDE PIPING DIAGRAM FOR BLOWER LABELED P.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 6. THE STACK FOR THE SINK ON THE 5TH FLOOR IS SHOWN ON
 P1.3 AS A 4IN. ON SHT. P2.1 IT IS SHOWN AS 2IN.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 7. SHT. P0.1 THE SPECS GIVEN FOR OIL SEPARATOR DO NOT
 COMPLY WITH FBC PL SEC 1003.4.2.1.
 PROVIDE MANUFACTURE SPECS THAT COMPLY WITH FBC PL SEC
 1003.4.2.1.
  
 8. SHT. P0.3 THE CALCULATION GIVEN FOR OIL SEPARATOR DO
 NOT COMPLY WITH FBCPL SEC 1003.4.2.2 IT APPEARS THAT
 YOU MIGHT HAVE USED CALCULATION FOR SIZING A GREASE
 INTERCEPTOR.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 9. SHT. P1.2 SHOW A PLAN NOTE IN THE AREA RM # 115 AND
 117 THAT INDICATES A WATER HEATER AND MOP SINK .
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 10. THE DIGITAL SIGNATURES ARE INVALID ON PLUMBING
 PAGES THEY SHALL COMPLY WITH FAC 61G15-23.003
  
  
 2ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-24 Cont ID  
Sent By tklarge Date 2016-01-23 Time 03:52 Rev Time 0.00
Received By tklarge Date 2016-01-19 Time 09:08 Sent To  
Notes
2016-01-19 09:49:151) PROVIDE MATCH LINES FOR THE PLUMBING PLAN VIEW
 DRAWINGS. IT IS DIFFICULT TO FOLLOW THE CONTINUATION OF
 THE PLUMBING SYSTEM FROM ONE SHEET TO THE NEXT.WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) CLARIFY THE OCCUPANCY TYPE THAT YOU ARE USING TO
 CALCULATE THE REQUIRED PLUMBING FIXTURES FOR THE
 PORSCHE & BENTLEY AREAS.
 3) THE ARCHITECTURAL PLANS HAVE THE DIFFERENT AREAS
 LABELE "A - F" AND THE PLUMBING PLANS ARE LABELED BY
 THE AREA NAME ( PORSCHE-SOUTH, PORSCHE-NORTH, ROLLS
 ROYCE/BENTLEY ETC.). IT IS EXTREMELY DIFFICULT TO
 REVIEW THESE PLANS WITHOUT CORRELATING NAMING
 CONVENTIONS. PLEASE ATTEMPT TO CORRELATE THE
 IDENTIFICATION OF THESE PLANS IN A MANNER THAT MAKES IT
 EFFICIENT TO PERFORM A COMPREHENSIVE REVIEW.
 4) THE TRENCH DRAINS LOCATED IN THE DETAIL AREA #166
 SHALL DISCHARGE TO THE OIL INTERCEPTOR PER THE 2014
 FBC-PLUMBING SEC.1003.4.2.2.
 5) SHT. A1.1.1E - LOCKER ROOMS #125 & #126 SHOWS A
 HANDICAPPED ACCESSIBLE TOILET COMPARTMENT WITH A
 LAVATORY IN IT BUT NO WATER CLOSET. CLARIFY. 2014
 FBC-ACCESS. SEC.213.3.1 & 604.8.1.
 6) SHT. A1.1.1E - LOCKER RM. 3126 - SHOWS THE DOOR FOR
 THE ACCESSIBLE STALL SWINGING INTO THE CLEAR FLOOR
 SPACE FOR WHAT APPEARS TO BE AN ACCESSIBLE URINAL. THE
 DOOR CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE
 FIXTURE PER 2014 FBC-ACCESS.SEC.603.2.3.
 7) SHT. A1.2.1 - THE BREAK ROOM SINK IN ROOM #209 SHALL
 COMPLY WITH 2014 FBC-ACCESS. SEC.212 & 606.
 8) SHT. A1.5.1 - TOILET ROOM # 500A - SHOW THE WIDTH OF
 THE TOILET ROOM ON DETAIL #2. THE MINIMUM WIDTH IS 85
 INCHES. 86 INCHES ALLOWS FOR TOLERANCE.
 9).SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF ALL SINGLE
 USER TOILET ROOMS. WPB AMEND. TO FBC SEC. 107.2.1.
 10) SHT. A2.0 - DETAILS #2 & #4 - IDENTIFY THE
 HANDICAPPED ACCESSIBLE URINAL IN BOTH RESTROOMS. COMPLY
 WITH 2014 FBC - ACCESS. SEC.605.
 11) SHT. A2.0 - SHOW THE FIXTURE CLEARANCE DIMENSION
 FROM THE CENTERLINE OF THE ACCESSIBLE WATER CLOSET TO
 THE SIDE WALL. COMPLY WITH 2014 FBC-ACCESS. SEC. 604.2.
 12) SHT.A2.0 - DETAIL #1 - THE DOORS TO RESTROOMS #213
 & 214 CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORIES. 2014 FBC-ACCESS. SEC.603.2.3. (SEE
 EXCEPTION #2).
 13) SHT. A2.0 - SHOW THE FIXTURE CLEARANCES OF THE
 URINALS ON SHT. A2.0, DETAIL #2 AND ALSO DETAIL #4.
 .COMPLY WITH 2014 FBC-PLUMBING, SEC.405.3.1.
 14) SHT. A2.1 - SHOW THE FIXTURE CLEARANCE FOR THE
 URINALS IN THE ENLARGED STAFF LOCKERS/RESTROOMS, DETAIL
 #2. COMPLY WITH 2014 FBC-PLUMBING SEC. 405.3.1.
 15) SHT. A2.0 - DETAIL #4 - THE DRINKING FOUNTAINS
 SHALL CCOMPLY WITH 2014 FBC-ACCESS. SEC.307.2 FOR
 PROTRUDING OBJECTS.
 16) SHT. A2.1 - DETAIL #2 - SHOW THE REQUIRED TURNING
 SPACE IN THE MEN'S & WOMEN'S RESTROOMS PER THE 2014
 FBC- ACCESS. SEC.304.3.1.
 17) SHT. A2.1 - DETAIL #1 - SHOW THE INSIDE CLEAR
 DIMENSION OF THE ACCESSIBLE STALL IN THE WWOMEN'S
 RESTROOM. MINIMUM WIDTH IS 85 INCHES. 86 INCHES ALLOWS
 FOR TOLERANCE. ALSO, SHOW THE FIXTURE CLEARANCE OF THE
 WATER CLOSET IN THE STALL FROM THE SIDE WALL TO THE
 CENTERLINE OF THE WATER CLOSET.
 18) SHT. A10.1 - THE URINAL SCREEN SHALL EXTEND NOT
 LESS THAN 60 INCHES ABOVE THE FINISH FLOOR.2014 FBC
 SEC. 1210.3.2.
 19) SHT. A10.1 - SHOW THE REQUIRED CLEAR FLOOR SPACE
 UNDER THE LAVATORY IN DETAIL #7. COMPLY WITH 2014
 FBC-ACCESS. SEC.305, 306.
 20) SHT.A10.3 - DETAILS #7 & #8 - THE HEIGHT OF THE
 WATER CLOSET IS SHOWN AS 15 INCHES ABOVE THE FINISH
 FLOOR. THE HEIGHT OF THE ACCESSIBLE WATER CLOSET SHALL
 BE BETWEEN 17" & 19 " ABOVE THE FINISH FLOOR. 2014 FBC-
 ACCESS. SEC.604.4.
 21) SHT. A10.7 - DETAIL #6 - THE URINAL LIP IS SHOWN AS
 1'-7" ABOVE THE FINISH FLOOR. IF THIS IS A HANDICAPPED
 URINAL, THE MAX. HEIGHT TO THE URINAL LIP SHALL BE 17
 INCHES. FBC-ACCESS. SEC. 605.2.
 22) SHT.A10.7 - DETAIL # 16 - THE URINAL LIP IS SHOWN
 AS 1'-7" ABOVE THE FINISH FLOOR. IF THIS IS A
 HANDICAPPED URINAL, THE MAX. HEIGHT TO THE URINAL LIP
 SHALL BE 17 INCHES. FBC-ACCESS. SEC. 605.2.
 23) SHT. P1.1 - IDENTIFY ALL THE EQUIPMENT & TANKS IN
 ROMM #171. WPB AMEND. TO FBC SEC.107.2.1.
 24) SUBMIT A PIPING RISER FOR THE COMPRESSED AIR
 SYSTEM.WPB AMEND. TO FBC SEC.107.2.1.
 25) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB
 AMEND. TO FBC SEC.107.2.1.
 26) CLEARLY SHOW THE DRAIN LINES FROM THE ELEVATOR
 SUMPS TO THE OIL WASTE SYSTEM ON THE PLUMBING RISER.WPB
 AMEND. TO FBC SEC.107.2.1.
 27) SHT.P2.2 - MEN'S & WOMEN'S TOILET ROOMS #154 & #155
 - THE CIRCUIT VENT SHALL BE LOCATED BETWEEN THE THE TWO
 MOST UPSTREAM FIXTURE DRAINS. AS DRAWN, THE VENT IS
 LOCATED DOWNSTREAM OF THE TWO MOST UPSTREAM WATER
 CLOSETS.2014 FPC SEC.914.2.
 28) SHT. P2.1 - SANITARY RISER #2 - TECH RESTROOMS -
 SIZE THE VENTS FOR THE URINALS.
 29) SHT. P2.1 - RISER #1 - ROLLS ROYCE/BENTLEY - TWO
 LAVATORIES ARE SHOWN ON THE SANITARY RISER FOR ROOM
 #126 AND ONLY ONE IS SHOWN ON SHT. P1.3. CLARIFY.
 30) SHT.P1.3 SHOWS A 4"SANITARY RISER ON COLUMN LINE BB
 BETWEEN COLS. #7 & #8 BUT IS NOT SHOWN ON THE SANITARY
 RISER SHT. P2.1.. CLARIFY.
 31) SHT.P1.3 - SHOWS A SANITARY BRANCH FROM THE
 BUILDING DRAIN GOING OVER TO STAIR #2 WITH A NOTE " 2"
 SANITARY FROM ABOVE" BUT IT IS NOT SHOWN ON SHT. P2.1,
 RISER #1(ROLLS ROYCE/BENTLEY0. CLARIFY.
 32) SHT. P1.6 - THE DISCHARGE FROM THE WASH BAYS SHALL
 DISCHARGE THROUGH THE OIL SEPARATOR. 2014 FPC SEC.
 1003.4.
 33) SHT.P2.4 - WATER RISER #5 - HOT WATER IS REQUIRED
 TO THE MOP SINK IN ROOM #156. 2014 FBC SEC.607.1.
 34) SHT.P0.3 - PROVIDE THE DIMENSIONS OF THE OIL
 SEPARATOR.THE OIL SEPARATOR SHALL BE SIZED IN
 ACCCORDANCE WITH THE 2014 FPC SECS. 1003.4.2,
 1003.4.2.1, 1003.4.2.2.
 35) SHT.P1.0 - THE DRINKING FOUNTAINS ARE SHOWN ON THE
 FLOOR PLAN BUT ARE NOT SHOWN ON THE WATER RISER ON SHT.
 P2.4 (RISER #5 RESTROOMS #154 & 155 ) . CLARIFY.
 36) SHT.P1.0A - DRINKING FOUNTAINS IN PASSAGE AREA #206
 ARE SHOWN ON THE FLOOR PLAN BUT NOT ON THE WATER RISER
 ON SHT.P2.4. CLARIFY.SEE AREA BY COLS.15 & 0.2.
 37) SHT. P2.3 - HOT WATER IS REQUIRED TO THE MOP SINK
 BY STORAGE ROOM #116. 2014 FPC SEC.607.1.
 38) SHT. P1.2 - THE PLAN VIEW FOR THE AREA NEAR STORAGE
 ROOM #116 DOES NOT CORRELATE WITH SHT. A1.1. CLARIFY.
 39) SHT.P2.5 - THE MAXIMUM SQUARE FOOTAGE TO BE DRAINED
 BY AN 8" HORIZONTAL DRAIN IS 9200 SQ. FT.PER 2014 FBC
 TABLE 1106.3. RISER S-1 SHOWS AN 8" DRAIN DRAINING
 11,500 SQ. FT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-06-16 Cont ID  
Sent By skennedy Date 2016-06-16 Time 09:52 Rev Time 0.00
Received By skennedy Date 2016-06-16 Time 09:52 Sent To  
Notes
2016-06-07 11:10:0406/07/2016 SIGNATURES: BUILDING/ PASSED. JW

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2016-06-07 Cont ID  
Sent By jwitmer Date 2016-06-07 Time 08:56 Rev Time 0.00
Received By jwitmer Date 2016-06-07 Time 08:56 Sent To  
Notes
2016-06-07 08:56:46THRESHOLD DOCUMENTS FIRST FILED WITH FOUNDATION PERMIT:
 16020586
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-06-07 Cont ID  
Sent By eschneid Date 2016-06-07 Time 13:55 Rev Time 8.00
Received By eschneid Date 2016-06-03 Time 09:15 Sent To  
Notes
2016-06-07 13:55:32PASSED W/PROVISOS
  
 1) THE FOLLOWING SHEETS SHALL WERE NOT CORRECTED FROM
 THE APRIL PLAN REVIEW AND SHALL BE UPDATED WITH A
 REVISION SUBMITTED TO THE BUILDING DIVISION AND
 APPROVED PRIOR TO THE FIRST INSPECTION.
  
 SHEET A1-1-1
 SHEET A1-1-1B
 SHEET A1-1-1C
  
 2) PRIOR TO FIRST INSPECTION A REVISION SHALL BE
 SUBMITTED TO THE BUILDING DIVISION AND APPROVED WHICH
 SHOWS THE INTERIM PARKING PLAN IN ACCORDANCE WITH THE
 MARK-UP SENT TO URBAN DESIGN KILDAY STUDIOS. THE
 PARKING PLAN SHALL BE MAINTAINED THROUGHOUT THE
 CONSTRUCTION OF PHASES I & II. PLEASE NOTE THAT THE
 PORSCHE SITE PLAN REQUIRES A TOTAL OF 56 PARKING SPACES
 AND ONLY 19 ARE PROVIDED ON THE PORSCHE PHASE. THE PLAN
 SHALL SHOW AN ADDITIONAL 37 PARKING SPACES.
  
 3) IN ACCORDANCE WITH RESOLUTION NO. 207-15, PRIOR TO
 THE CONSTRUCTION IN THE EXCHANGE COURT RIGHT-OF-WAY,
 THE APPLICANT SHALL:
  
 A. SECURE A CITY RIGHT-OF-WAY PERMIT.
 B. SECURE APPROVAL FROM THE ENGINEERING SERVICES
 DIVISION FOR THE PLANTING AND IRRIGATION IN THE
 EXCHANGE COURT RIGHT-OF-WAY.
 C. PROVIDE THE INFORMATION REQUIRED FOR THE CITY TO
 DRAFT A MAINTENANCE AND REPLACEMENT AGREEMENT FOR THE
 TREES AND IRRIGATION WITHIN THE EXCHANGE COURT
 RIGHT-OF-WAY TO THE PLANNING DIVISION FOR REVIEW AND
 APPROVAL BY THE CITY ATTORNEY'S OFFICE. THE APPROVED
 AGREEMENT SHALL BE RECORDED BY THE APPLICANT PRIOR TO
 THE COMMENCEMENT OF SITE WORK.
  
 4) PRIOR TO BEGINNING THE PHASE II (BUILDING D)
 CONSTRUCTION, THE APPLICANT SHALL PROVIDE VERIFICATION
 THAT THE UTILITY EASEMENTS IN CONFLICT WITH THE
 BUILDING LOCATION HAVE BEEN ABANDONED.
  
 5) PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY FOR THE PORSCHE DEALERSHIP (BUILDING E), THE
 APPLICANT SHALL SUBMIT A MINOR PD AMENDMENT FOR THE
 AS-BUILT CHANGES, TO INCLUDE THE ELEVATIONS AND GARAGE
 FLOOR PLANS.
  
 6) THE CIVIL PLANS DID NOT CORRECT THE DRAWINGS TO SHOW
 A BARRIER THE FULL DEPTH OF THE ADA PARKING SPACE BY
 THE EXIT TO THE PROPOSED MINI SERVICE TO PREVENT CARS
 EXITING THE SERVICE AREA FROM DRIVING INTO THE SIDE OF
 THE SPACE. THIS SHALL BE SHOWN CORRECTLY ON THE PERMIT
 PLANS FOR THIS PHASE OF CONSTRUCTION.
  
 7) SEPARATE PERMITS ARE REQUIRED FOR THE FOLLOWING:
  
 A. PARKING LOT STRIPING
 B. LANDSCAPE
 C. SITE LIGHTING
 D. FENCES AND GATES
 E. DUMPSTER ENCLOSURE
 F. BICYCLE RACK
 G. SIGNAGE
 H. GENERATOR
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-04-27 Cont ID  
Sent By eschneid Date 2016-04-27 Time 18:36 Rev Time 6.00
Received By eschneid Date 2016-04-27 Time 18:36 Sent To  
Notes
2016-04-27 18:37:03FAILED
  
 RESPOND TO COMMENTS IN WRITING.
  
 1) REPEAT COMMENT: PROVIDE VERIFICATION THAT ALL THE
 REQUIREMENTS FROM RESOLUTION NO. 207-15, INCLUDING
 THOSE LISTED BELOW, HAVE BEEN SATISFIED.
  
 A. PRIOR TO THE APPROVAL OF ANY SITE WORK PERMIT (THIS
 INCLUDES DEMOLITION OF THE STRUCTURES), THE APPLICANT
 SHALL:
  
 1. SECURE A CITY RIGHT-OF-WAY PERMIT FOR THE WORK
 WITHIN THE EXCHANGE COURT RIGHT-OF-WAY.
 2. SECURE APPROVAL FROM THE ENGINEERING SERVICES
 DIVISION FOR THE PLANTING AND IRRIGATION IN THE
 EXCHANGE COURT RIGHT-OF-WAY.
 3. PROVIDE THE INFORMATION REQUIRED FOR THE CITY TO
 DRAFT A MAINTENANCE AND REPLACEMENT AGREEMENT FOR THE
 TREES AND IRRIGATION WITHIN THE EXCHANGE COURT
 RIGHT-OF-WAY TO THE PLANNING DIVISION FOR REVIEW AND
 APPROVAL BY THE CITY ATTORNEY'S OFFICE. THE APPROVED
 AGREEMENT SHALL BE RECORDED BY THE APPLICANT PRIOR TO
 THE COMMENCEMENT OF SITE WORK.
 4. SECURE ENGINEERING DEVELOPMENT APPROVAL, TO INCLUDE
 ALL TECHNICAL DATA.
  
 B. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE PLANNING
 DIVISION.
  
 C. PRIOR TO CONDUCTING ANY LAND DISTURBING OR LAND
 DEVELOPMENT ACTIVITIES, THE APPLICANT SHALL POST A BOND
 OR DEPOSIT IN AN AMOUNT COVERING THE COST ASSOCIATED
 WITH IMPLEMENTATION OF THE STORMWATER POLLUTANT
 PREVENTION PLAN (SWPPP) AND A LAND STABILIZATION BOND
 FOR THE SITE SHALL BE SUBMITTED TO THE PUBLIC WORKS
 DEPARTMENT. THE BOND WILL BE RELEASED UPON APPROVED
 INSPECTION OF TIE-BEAMS OR SIMILAR VERTICAL
 CONSTRUCTION.
  
 D. BUILDING PERMIT: PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR BUILDING D/E, THE APPLICANT SHALL PROVIDE
 VERIFICATION THAT THE UTILITY EASEMENTS IN CONFLICT
 WITH THE BUILDING LOCATIONS HAVE BEEN ABANDONED.
  
 2) ARCHITECTURAL PLANS
  
 A. THE LAYOUT OF THE GARAGE LEVELS DO NOT MATCH THE
 LAYOUT ON THE ARCHITECTURAL PLANS APPROVED AS PART OF
 RES. NO. 74-16.
 B. THE PROGRAMMING BAYS ARE SERVICE BAYS AND THUS SHALL
 PROVIDE PARKING AT A RATIO OF 1 SPACE PER 3 SERVICE
 BAYS.
 C. PARKING COUNTS AND PARKING DATA TABLES SHALL BE
 REVISED TO REFLECT ACCURATE NUMBERS.
 D. MINIMUM PARKING STANDARDS SHALL CONTINUE TO BE MET.
 E. THE BUILDING EXCEEDS 80 FEET IN HEIGHT (77.75 FEET
 PLUS 2.5 FEET = 80.25 FEET) AND THUS REQUIRES AN
 ADDITIONAL SIX (6) FEET OF SETBACK. RESOLUTION NO.
 74-16 DID NOT GRANT THE WAIVER FOR A BUILDING THIS
 TALL. THIS IS SHOWN ON THE NORTH ELEVATION.
 F. THE ELEVATIONS HAVE CHANGED FROM THOSE APPROVED BY
 RESOLUTION NO. 74-16. A MINOR AMENDMENT IS REQUIRED FOR
 THE REVISED ELEVATIONS PRIOR TO C.O.
  
 3) RESOLUTION NO. 74-16 REQUIRES THAT PARKING AND
 LANDSCAPE COMPLIANCE IN ACCORDANCE WITH THE ZONING AND
 LAND DEVELOPMENT REGULATIONS IS REQUIRED FOR EACH
 BUILDING THAT IS OCCUPIED DURING EACH PHASE OF
 DEVELOPMENT. EACH BUILDING PERMIT FOR DEMOLITION AND
 NEW CONSTRUCTION SHALL INCLUDE PLANS TO DEMONSTRATE
 COMPLIANCE AS THE PHASES OF CONSTRUCTION AND COMPLETION
 OCCUR. FOR EXAMPLE, THE EXISTING PORSCHE DEALERSHIP
 SHALL MEET MINIMUM PARKING REQUIREMENTS DURING
 CONSTRUCTION OF THE NEW PORSCHE BUILDING. ONCE THE NEW
 PORSCHE BUILDING IS OPERATIONAL, THE PORSCHE DEALERSHIP
 SHALL MEET MINIMUM PARKING REQUIREMENTS DURING THE
 DEMOLITION AND CONSTRUCTION OF THE VACATED PORSCHE
 BUILDING. THE PLANS SEEM TO INDICATE THAT ALL OF THE
 DEMOLITION AND CONSTRUCTION WILL OCCUR IN ONE PHASE. IF
 THIS IS THE CASE, THEN THIS PROVISION DOES NOT APPLY.
 HOWEVER, STAFF HAS BEEN TOLD THAT THE CONSTRUCTION WILL
 BE IN PHASES. IF THIS IS STILL THE CASE, THEN THE PLANS
 SHALL SHOW PHASING LINES AND COMPLIANCE WITH THE ABOVE
 CITED DEVELOPMENT REGULATION.
  
 4) ITEMS NOTED ON THE CIVIL PLANS:
  
 A. THE FULL DEPTH OF THE ADA PARKING SPACE BY THE EXIT
 TO THE PROPOSED MINI SERVICE SHALL HAVE A BARRIER TO
 PREVENT CARS EXITING THE SERVICE AREA FROM DRIVING INTO
 THE SIDE OF THE SPACE.
 B. THE DRIVE AISLE WEST OF BUILDING D SHALL HAVE A
 TURNAROUND SPACE OF A WIDTH A CAR CAN USE DEMARCATED.
 THE ONE SHOWN APPEARS TO NARROW WHEN COMPARED TO THE
 APPROVED SITE PLAN.
 C. THE LANDSCAPE ISLANDS BETWEEN BUILDING D AND E ARE
 SHOWN AT DIFFERENT WIDTHS THAN THE SITE PLAN. WHILE
 STAFF LIKES THAT THE INTERIOR ISLANDS ARE SHOWN AT 8
 FEET WIDE INSTEAD OF 5 FEET WIDE, THE 3 FEET WAS TAKEN
 OUT OF THE TERMINAL ISLANDS ADJACENT TO THE BUILDING
 AND THIS MAY PRESENT CONFLICTS WITH THE PROPOSED
 LANDSCAPE.
 D. IT IS ZONING STAFF?S UNDERSTANDING THAT ONLY
 BUILDING E IS BEING BUILT AT THIS TIME, YET THE CIVIL
 PLANS SHOW DEMOLITION AND CONSTRUCTION OF THE ENTIRE
 SITE, TO INCLUDE THE LOCATION OF THE SILT FENCE.
 E. MULTIPLE CONFLICTS WITH PROPOSED WATER AND
 WASTEWATER LINES, BACKFLOW PREVENTERS, FIRE HYDRANTS,
 ETC. AND REQUIRED, APPROVED LANDSCAPE.
 F. AUTOTURN DOES NOT USE FINAL BASE PLAN.
  
 5) SEPARATE PERMITS ARE REQUIRED FOR THE FOLLOWING:
  
 A. PARKING LOT STRIPING
 B. LANDSCAPE
 C. SITE LIGHTING
 D. FENCES AND GATES
 E. DUMPSTER ENCLOSURE
 F. BICYCLE RACK
 G. SIGNAGE
 H. GENERATOR
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-01-12 Cont ID  
Sent By eschneid Date 2016-01-12 Time 11:04 Rev Time 0.75
Received By eschneid Date 2016-01-12 Time 10:41 Sent To  
Notes
2016-01-12 11:27:33FAILED
  
 1) THIS PLAN HAS NOT BEEN APPROVED BY THE CITY
 COMMISSION. ZONING STAFF WILL NOT REVIEW THE PERMIT
 UNTIL THE CITY COMMISSION HAS APPROVED THE PLAN. STAFF
 IS CURRENTLY RECOMMENDING CONDITIONS WHICH WOULD CHANGE
 SOME ELEMENTS OF THE SITE PLAN, LANDSCAPE PLAN, CIVIL
 PLAN AND ARCHITECTURAL SITE PLAN.
  
 2) PROVIDE VERIFICATION THAT ALL THE REQUIREMENTS FROM
 RESOLUTION NO. 207-15, INCLUDING THOSE LISTED BELOW,
 HAVE BEEN SATISFIED.
  
 A. PRIOR TO THE APPROVAL OF ANY SITE WORK PERMIT, THE
 APPLICANT SHALL:
  
 1. PROVIDE THE FLORIDA DEPARTMENT OF TRANSPORTATION
 RIGHT-OF-WAY PERMIT FOR THE WORK WITHIN THE OKEECHOBEE
 BOULEVARD RIGHT-OF-WAY TO THE PLANNING DIVISION.
 2. SECURE A CITY RIGHT-OF-WAY PERMIT FOR THE WORK
 WITHIN THE EXCHANGE COURT RIGHT-OF-WAY.
 3. SECURE APPROVAL FROM THE ENGINEERING SERVICES
 DIVISION FOR THE PLANTING AND IRRIGATION IN THE
 EXCHANGE COURT RIGHT-OF-WAY.
 4. PROVIDE THE INFORMATION REQUIRED FOR THE CITY TO
 DRAFT A MAINTENANCE AND REPLACEMENT AGREEMENT FOR THE
 TREES AND IRRIGATION WITHIN THE EXCHANGE COURT
 RIGHT-OF-WAY TO THE PLANNING DIVISION FOR REVIEW AND
 APPROVAL BY THE CITY ATTORNEY?S OFFICE. THE APPROVED
 AGREEMENT SHALL BE RECORDED BY THE APPLICANT PRIOR TO
 THE COMMENCEMENT OF SITE WORK.
 5. SECURE ENGINEERING DEVELOPMENT APPROVAL, TO INCLUDE
 ALL TECHNICAL DATA.
  
 B. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE PLANNING
 DIVISION.
  
 C. PRIOR TO CONDUCTING ANY LAND DISTURBING OR LAND
 DEVELOPMENT ACTIVITIES, THE APPLICANT SHALL POST A BOND
 OR DEPOSIT IN AN AMOUNT COVERING THE COST ASSOCIATED
 WITH IMPLEMENTATION OF THE STORMWATER POLLUTANT
 PREVENTION PLAN (SWPPP) AND A LAND STABILIZATION BOND
 FOR THE SITE SHALL BE SUBMITTED TO THE PUBLIC WORKS
 DEPARTMENT. THE BOND WILL BE RELEASED UPON APPROVED
 INSPECTION OF TIE-BEAMS OR SIMILAR VERTICAL
 CONSTRUCTION.
  
 D. BUILDING PERMIT: PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR BUILDING D/E, THE APPLICANT SHALL
 PROVIDE VERIFICATION THAT THE UTILITY EASEMENTS IN
 CONFLICT WITH THE BUILDING LOCATIONS HAVE BEEN
 ABANDONED.
  
 3) THIS DOES NOT COUNT AS A PERMIT REVIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2015-12-28 16:03:5212/28/15