Plan Review Details - Permit 15120482
Plan Review Stops For Permit 15120482
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-01-27 Cont ID  
Sent By skennedy Date 2016-01-27 Time 16:31 Rev Time 0.00
Received By skennedy Date 2016-01-27 Time 16:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-05 Cont ID  
Sent By skennedy Date 2016-01-05 Time 09:02 Rev Time 0.00
Received By skennedy Date 2016-01-05 Time 09:02 Sent To  
Notes
2016-01-05 09:09:251ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PROVIDE A REVISED ENERGY SUBMITTAL:
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 PROVIDE PRODUCT APPROVAL FOR THE NEW ROOF COVERING.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING.
  
 PLEASE REVISE PLAN TO SHOW PROVISIONS FOR ATTIC
 VENTILATION, INSULATION AND INSULATION CLEARENCE, ATTIC
 ACCESS: A SECTION FOR THE NEW HIP ROOF TO CLEARLY
 DEMONSTRATE DETAILS MAY BE HELPFUL.
  
 R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL
 HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS
 HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM)
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM)
 MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF
 FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF
 SECTION R802.1.8. REQUIRED VENTILATION OPENINGS SHALL
 OPEN DIRECTLY TO THE OUTSIDE AIR.
  
 R806.3 VENT AND INSULATION CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, INSULATION
 SHALL NOT BLOCK THE FREE FLOW OF AIR. A MINIMUM OF A
 1-INCH (25 MM) SPACE SHALL BE PROVIDED BETWEEN THE
 INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION
 OF THE VENT.
  
 R807.1 ATTIC ACCESS.
 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION
 SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT
 EXCEED 30 SQUARE FEET (2.8 M2) AND HAVE A VERTICAL
 HEIGHT OF 30 INCHES (762 MM) OR GREATER. THE VERTICAL
 HEIGHT SHALL BE MEASURED FROM THE TOP OF THE CEILING
 FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF FRAMING
 MEMBERS.
  
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. WHEN LOCATED IN A WALL, THE OPENING SHALL BE
 A MINIMUM OF 22 INCHES WIDE BY 30 INCHES HIGH (559 MM
 WIDE BY 762 MM HIGH). WHEN THE ACCESS IS LOCATED IN A
 CEILING, MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC
 SPACE SHALL BE 30 INCHES (762 MM) AT SOME POINT ABOVE
 THE ACCESS MEASURED VERTICALLY FROM THE BOTTOM OF
 CEILING FRAMING MEMBERS. SEE SECTION M1305.1.3 FOR
 ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-27 Cont ID  
Sent By skennedy Date 2016-01-27 Time 16:31 Rev Time 0.00
Received By skennedy Date 2016-01-27 Time 16:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-05 Cont ID  
Sent By skennedy Date 2016-01-05 Time 08:24 Rev Time 0.00
Received By skennedy Date 2016-01-05 Time 08:24 Sent To  
Notes
2016-01-05 08:46:131ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 1) THE CODE REFERENCE OF NEC 2008 ON SHEET E01 IS
 INCORRECT, THE CORRECT CODE REFERENCE IS FBC 2014 5TH
 ED. RESIDENTIAL AND IT CONTAINS ELECTRICAL REQUIREMENTS
 IN THE ELECTRICAL SECTION. PLEASE REVISE.
  
 2) THE PANEL SCHEDULE NOR CIRCUTING ON THE PLAN
 INDICATE PROVISIONS FOR TWO KITCHEN/DINING CIRCUITS.
 FBCRE3703.2 KITCHEN AND DINING AREA RECEPTACLES. A
 MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL BE
 PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE OUTLETS
 LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA, DINING
 AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN
 COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF
 TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER
 RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY,
 BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS
 FOR REFRIGERATION APPLIANCES.
  
 3) THE PANEL SCHEDULE AND AIR CONDITIONING EQUIPMENT
 ARE NOT CONSISTENT IN TERMS OF THE NUMBER OF SYSTEMS.
  
 4) PLEASE INDICATE THE LOCATION OF THE ELECTRICAL
 SERVICE EQUIPMENT ON THE PLAN.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-12-16 Cont ID  
Sent By gjohnson Date 2015-12-16 Time 09:17 Rev Time 0.00
Received By gjohnson Date 2015-12-16 Time 09:17 Sent To HIST
Notes
2015-12-16 09:20:111ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 A GAS REVIEW HAS NOT BEEN DONE UNDER THIS PERMIT A
 SEPERATE PERMIT IS REQUIERED. GAS PERMIT APPLICATION
 REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-01-27 Cont ID  
Sent By fmittner Date 2016-01-27 Time 14:25 Rev Time 0.00
Received By fmittner Date 2016-01-27 Time 14:25 Sent To B
Notes
2016-01-27 14:36:35REQUIRES ADDITION OF WINDOW ON WEST ELEVATION PER
 ARCHITECTS SUBMITTAL TO HPB.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-12-28 Cont ID  
Sent By fmittner Date 2015-12-28 Time 14:38 Rev Time 0.00
Received By fmittner Date 2015-12-28 Time 14:38 Sent To  
Notes
2015-12-28 14:38:41REQUIRES COA SUBMITTAL FOR ROOF CHANGE AND WINDOW
 ENCLOSURE ON SIDES. FHM SPOKE TO SAM FISCH AND
 EXPLAINED PROCESS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-27 Cont ID  
Sent By skennedy Date 2016-01-27 Time 16:33 Rev Time 0.00
Received By skennedy Date 2016-01-20 Time 15:08 Sent To  
Notes
2016-01-21 15:09:10ROUTED TO FMITTNER VIA SGRAHAM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-05 Cont ID  
Sent By skennedy Date 2016-01-05 Time 10:10 Rev Time 0.00
Received By skennedy Date 2015-12-14 Time 10:55 Sent To  
Notes
2015-12-15 10:55:32REVISION ROUTED TO GJOHNSON

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-01-27 Cont ID  
Sent By skennedy Date 2016-01-27 Time 16:33 Rev Time 0.00
Received By skennedy Date 2016-01-27 Time 16:33 Sent To  
Notes
2016-01-27 16:35:03PROVIDE REVISED EQUIPMENT SIZING CALCULATIONS AND
 ENERGY SUBMITTAL AS PREVIOUSLY REQUESTED AS REVISION.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-05 Cont ID  
Sent By skennedy Date 2016-01-05 Time 08:46 Rev Time 0.00
Received By skennedy Date 2016-01-05 Time 08:46 Sent To  
Notes
2016-01-05 09:02:361ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PROVIDE AN UPDATED ENERGY SUBMITTAL AND EQUIPMENT
 SIZING CALCULATION TO MATCH THE REVISED MECHANICAL HVAC
 DESIGN AND DEMONSTRATE COMPLIANCE WITH THE BELOW:
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
  
 R403.6.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
 R403.6.1.1 COOLING EQUIPMENT CAPACITY.
 COOLING ONLY EQUIPMENT SHALL BE SELECTED SO THAT ITS
 TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED TOTAL
 LOAD, BUT NOT MORE THAN 1.15 TIMES GREATER THAN THE
 TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE
 SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE
 SIZE PROVIDED BY THE MANUFACTURER?S PRODUCT LINES. THE
 CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL
 NOT BE LESS THAN THE CALCULATED LATENT LOAD.
 .
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-12-15 Cont ID  
Sent By gjohnson Date 2015-12-15 Time 13:28 Rev Time 0.00
Received By gjohnson Date 2015-12-15 Time 13:28 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-01-27 Cont ID  
Sent By skennedy Date 2016-01-27 Time 16:31 Rev Time 0.00
Received By skennedy Date 2016-01-27 Time 16:31 Sent To  
Notes
2016-01-27 16:32:48PROVIDE PRODUCT APPROVAL AS A REVISION OR PROVIDE
 SEPARATE ROOFING APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-01-05 Cont ID  
Sent By skennedy Date 2016-01-05 Time 09:09 Rev Time 0.00
Received By skennedy Date 2016-01-05 Time 09:09 Sent To  
Notes
2016-01-05 09:10:27ROOFING
  
 SEE BUILDING REVIEW AS TO ROOFING SUBMITTAL REQUIRED..