Plan Review Details - Permit 15120480
Plan Review Stops For Permit 15120480
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-20 Cont ID  
Sent By hmoser Date 2016-05-20 Time 11:03 Rev Time 0.00
Received By hmoser Date 2016-05-18 Time 15:01 Sent To  
Notes
2016-05-19 15:01:39RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-15 Cont ID  
Sent By hmoser Date 2015-12-15 Time 15:38 Rev Time 0.00
Received By hmoser Date 2015-12-14 Time 10:05 Sent To  
Notes
2015-12-15 10:05:33MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-05-20 Cont ID  
Sent By hmoser Date 2016-05-20 Time 11:03 Rev Time 0.00
Received By hmoser Date 2016-05-20 Time 10:49 Sent To  
Notes
2016-05-20 11:03:34PASS PROVISO
 MASTER BEDROOM RETURN TO SMALL
 GYM RETURN TO SMALL REFER TO SECTION
 M1602.4 BALANCED RETURN AIR.
 2014 RESIDENTIAL CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-15 Cont ID  
Sent By hmoser Date 2015-12-15 Time 15:38 Rev Time 0.00
Received By hmoser Date 2015-12-15 Time 14:20 Sent To  
Notes
2015-12-15 15:38:37PLAN DENIED
  
 1) MASTER BEDROOM GRILL IS R-3 OTHER SIDE IS R-4 WHAT
 SIZE IS THE RETURN AIR DUCT.
 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR 2014
 RESIDENTIAL CODE
 3) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 KITCHEN HOOD
 SECTION M1401.1 2014 RESIDENTIAL CODE
 4) PROVIDE AHRI SHEET WITH APPLICATION.
  
 PLAN REVIEW BY HAROLD MOSER
 OFFICE 561-805-6732
 FAX 561-805-6676