| Plan Review Stops For Permit 15120430 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-03-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-03-16 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-03-16 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-12-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-12-30 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-12-30 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2015-12-30 13:42:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC | | | 107, FBC 705.3, 705.8. | | | | | | 2. CVR 1, TOP CENTER STATES THAT THIS IS A COMMERCIAL | | | REMODEL, PLEASE REVISE, FBC 107. | | | | | | 3. FOR SHEETS WHICH ARE REVISED, INCLUDE THE FOLLOWING | | | INFORMATION IN THE TITLE BLOCK AS REQUIRED BY | | | 61G1-16.004: | | | | | | FIRM LICENSE NUMBER | | | THE PRINTED NAME AND THE LICENSE LUMBER OF THE PERSON | | | SEALING THE DOCUMENT | | | | | | PLEASE INCORPORATE REQUIRED INFORMATION INTO THE TITLE | | | BLOCK OF FUTURE SUBMITTALS. | | | | | | 4. PROVIDE A SITE PLAN WHICH SHOWS THE FOLLOWING: | | | | | | LOCATION OF ASSUMED PROPERTY LINE BETTWEEN THE EXISTING | | | BUILDING(S) AND THE PROPOSED NEW BUILDING, FBC 705.3 | | | UNLESS USING THE EXCEPTION. | | | | | | BUILDING TYPE OF THE EXISTING BUILDING(S) | | | DISTANCE OF EXISTING BUILDING(S) TO THE ASSUMED | | | PROPERTY LINE | | | COMPLIANCE WITH FBC 602, 705.8 | | | | | | DISTANCE OF PROPOSED NEW CAR WASH BUILDING TO THE | | | ASSUMED PROPERTY LINE AND ACTUAL PROPERTY LINES | | | COMPLIANCE WITH FBC 602, 705.8 | | | | | | IF USING THE EXCEPTION, SHOW COMPLIANCE WITH FBC TABLE | | | 503. | | | | | | 5. CVR 1, BUILDING CODE DATA, USE IS MIXED USE, BUT | | | ONLY ONE OCCUPANCY DECLARED (B), PLEASE CLARIFY, FBC | | | 107, CHAPTER 3. | | | | | | 6. CVR 1, CONSTRUCTION TYPE DECLARED IS 1B. EITHER | | | REVISE BUILDING TYPE OR SHOW COMPLIANCE WITH FBC TABLE | | | 601 (2 HOUR EXTERIOR BEARING WALL, 1 HOUR ROOF). IF THE | | | BUILDING TYPE REMAINS 1B, PROVIDE INFORMATION FOR THE | | | EIFS SYSTEM TO DEMONSTRATE THAT IT IS NON COMBUSTIBLE | | | OR INCOPORATE THE APPLICABLE EXCEPTION INTO THE PLAN. | | | | | | 7. CVR 1, OCCUPANT LOAD CALCULATION MAKES REFERENCE TO | | | FBC 2010, PLEASE REVISE TO FBC 2014 (5TH EDITION) AS | | | GOVERNING CODE CHANGED ON JUNE 30, 2015, FS553, FBC | | | 107. | | | | | | 8. PROVIDE TWO SETS OF ALL PRODUCT APPROVALS, FBC 107. | | | THEY ARE REQUIRED FOR PLAN REVIEW AND FOR INSPECTIONS. | | | AS THE PRODUCT APPROVAL NUMBERS HAVE BEEN INCORPORATED | | | INTO THE PLAN, | | | | | | 9. THE STO PRODUCT SPECIFIED ON A1.0 APPEARS TO INCLUDE | | | A TYPO; 15-1226.03 IS NOT A VALID NOA NUMBER. | | | | | | 10. PROVIDE THE GEOTECHNICAL REPORT FOR PROPOSED SITE, | | | REVIEWED BY DESIGNER OF RECORD, FBC 1803.2. | | | | | | 11. REVISE PLAN TO INCLUDE SCUPPER AND OVERFLOW SIZING | | | CALCULATIONS, FBC 1503. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-02-18 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2016-02-18 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2016-02-18 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2016-01-27 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2016-01-27 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2016-01-26 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2016-01-27 10:46:43 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | | MEANS. NEC 110.16, 110.22 | | | PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE | | | RECEPTACLES. NEC 210.8 | | | PROVIDE A INTERSYSTEM BONDING BAR AT THE ELECTRICAL | | | SERVICE. NEC 250 .94 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2016-03-17 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2016-03-17 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2016-03-17 |
Time |
|
Sent To |
I |
|
| Notes |
| 2016-03-17 09:33:47 | PROVISO: | | | | | | PROVIDE TOTALS FOR PERVIOUS AND IMPERVOUS AREA TO | | | UPDATE STORMWATER ACCOUNT. | | | VIA E-MAIL TO [email protected] | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2016-02-16 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2016-02-16 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2016-02-16 |
Time |
|
Sent To |
Z |
|
| Notes |
| 2016-02-16 14:31:22 | PLEASE ADDRESS PLANNING AND ZONING COMMENTS. | | | | | | PROVIDE TOTALS FOR PERVIOUS AND IMPERVOUS AREA TO | | | UPDATE STORMWATER ACCOUNT. | | | VIA E-MAIL TO [email protected] | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-03-07 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2016-03-07 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2016-03-07 |
Time |
11:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-12-30 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-12-30 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-12-30 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2015-12-30 14:16:26 | PERMIT #15120430 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | 2) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY | | | THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS | | | HAVE BEEN SATISFIED. | | | | | | SUE ELLEN CALDERON | | | ASST. FIRE MARSHAL | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-03-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-03-17 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-17 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-02-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-16 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-12-11 |
Time |
17:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2016-04-12 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-04-12 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-04-12 |
Time |
13:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-12-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-12-30 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-12-30 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2015-12-30 13:13:01 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED. | | | THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING | | | THAT FEES DUE HAVE BEEN PAID IS TO BE PROVIDED. CONTACT | | | 561-233-5025 FOR MORE INFORMATION. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2016-02-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-29 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-29 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-12-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-12-18 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-12-18 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2015-12-18 11:14:11 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15120430 | | | 12/18/15 | | | | | | 1) INDICATE IF MECHANICAL VENTILATION WILL BE PROVIDED | | | FOR THE CAR WASH AND ATTACHED EQUIPMENT ROOM, AND | | | PROVIDE DETAILS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-02-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-02-28 |
Time |
05:31 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-02-28 |
Time |
05:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-12-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-12-16 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-12-16 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2015-12-16 14:46:06 | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | 1. PLEASE SHOW CALCULATION FOR ROOF CUPPERS AND DOWN | | | SPOUTS AND ENERGENCY SCUPPERS. PER WPB AMEND TO FBC SEC | | | 107.2.1 | | | 2. SHOW TAVEL DISTANCE TO EMPLOYEE BATHROOM SHALL | | | COMPLY WITH . FBC PL SEC 403.3.3 | | | 3.SHOW CALCULATION FOR SIZING DRAIN LINES IN GPM PER | | | WPB AMEND. TO FBC SEC 107.2.1 | | | 4 SHEET P2.4 MISSING UG4 ON DRAWING PLEASE CLEARIFY. | | | PER WPB AMEND. TO FBC SEC 107.2.1 | | | 5. PLEASE PROVIDE MANUFACTURE CALCULATION FOR OIL | | | SEPERATOR. PER WPB AMEND. TO FBC SEC 107.2.1 | | | 6.PROVIDE MANUFATURE INSULATION GUIDE FOR COMPRESSED | | | AIR LINES. PER WPB AMEND. TO FBC SEC 107.2.1 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2016-03-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-03-16 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-03-16 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2016-03-16 16:47:17 | NOA 15-0203.15 SUBMITTED | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2015-12-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-12-30 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-12-30 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2015-12-30 13:24:33 | A SEPARATE PERMIT APPLICATION AND PRODUCT APPROVAL | | | REVIEWED BY DESIGNER OF RECORD IS REQUIRED. ENGINEERING | | | FOR ENHANCED FASTENING IS REQUIRED IF APPLICABLE. | | | | | | DESIGN PRESSURES ON SHEET S2: | | | | | | ZONE 1 -29 | | | XONE 2 -65.5 | | | ZONE 3 -98.52 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2016-03-10 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2016-03-10 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2016-03-10 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2016-03-10 08:49:33 | PLANNING AND ZONING COMMENTS: | | | | | | 3/10/16 | | | | | | 1. CAR WASH USE APPROVED FOR THE PROPERTY BY ZBA - CASE | | | NO. 3334. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2016-03-01 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2016-03-01 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2016-03-01 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2016-03-01 08:41:24 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | | | 3/1/16 | | | | | | PREVIOUS ZONING COMMENT FROM 12/31/15 IS STILL | | | APPLICABLE. CLASS B SPECIAL USE PERMIT PENDING ZBA | | | HEARING (3/3/16) AND SITE PLAN STILL UNDER REVIEW WITH | | | THE PLANNING DIVISION. SUBMITTED PLAN MUST MATCH | | | APPROVED SITE PLAN ONCE APPROVED. | | | | | | 1. PROPOSAL INCLUDES AN APPROXIMATELY 1,300 SF | | | BUILDING. BECAUSE THE ADDITIONAL SQUARE FOOTAGE ON THE | | | SITE EXCEEDS 1,000 SF, A LEVEL - INFORMAL SITE PLAN | | | REVIEW APPROVAL IS REQUIRED. ADDITIONALLY, THE CAR WASH | | | USE REQUIRES ISSUANCE OF A CLASS B SPECIAL USE PERMIT | | | THROUGH THE ZONING BOARD OF APPEALS. BOTH APPLICATIONS | | | HAVE BEEN SUBMITTED TO PLANNING AND ZONING AND ARE | | | CURRENTLY UNDER REVIEW. ISSUANCE OF THE CLASS B SPECIAL | | | USE PERMIT AND INFORMAL SITE PLAN REVIEW APPROVAL ARE | | | REQUIRED PRIOR TO ZONING APPROVAL OF THIS BUILDING | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-12-31 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2015-12-31 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2015-12-31 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2015-12-31 11:49:16 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | | | 12/31/15 | | | | | | 1. PROPOSAL INCLUDES AN APPROXIMATELY 1,300 SF | | | BUILDING. BECAUSE THE ADDITIONAL SQUARE FOOTAGE ON THE | | | SITE EXCEEDS 1,000 SF, A LEVEL - INFORMAL SITE PLAN | | | REVIEW APPROVAL IS REQUIRED. ADDITIONALLY, THE CAR WASH | | | USE REQUIRES ISSUANCE OF A CLASS B SPECIAL USE PERMIT | | | THROUGH THE ZONING BOARD OF APPEALS. BOTH APPLICATIONS | | | HAVE BEEN SUBMITTED TO PLANNING AND ZONING AND ARE | | | CURRENTLY UNDER REVIEW. ISSUANCE OF THE CLASS B SPECIAL | | | USE PERMIT AND INFORMAL SITE PLAN REVIEW APPROVAL ARE | | | REQUIRED PRIOR TO ZONING APPROVAL OF THIS BUILDING | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | | | 2015-12-16 17:14:08 | 12/16/15 |
|
|