Plan Review Details - Permit 15120393
Plan Review Stops For Permit 15120393
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-07-25 Cont ID  
Sent By cthroop Date 2016-07-25 Time 13:09 Rev Time 0.00
Received By cthroop Date 2016-07-25 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-06-30 Cont ID  
Sent By cthroop Date 2016-06-30 Time 14:02 Rev Time 0.00
Received By cthroop Date 2016-06-30 Time 14:02 Sent To  
Notes
2016-06-30 14:05:12BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 ACTION: DENIED
 DATE: DECLINE
  
 1. VALUE APPEARS LOW. PROVIDE COPY OF CONTRACT AND/OR
 OTHER DOCUMENTATION ESTABLISHING TOTAL COST OF PROJECT
 EXCLUDING COST OF LAND.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-17 Cont ID  
Sent By cthroop Date 2016-03-17 Time 09:53 Rev Time 0.00
Received By cthroop Date 2016-03-17 Time 09:53 Sent To  
Notes
2016-03-17 10:09:232ND REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. SCOPE OF WORK REQUIRES A FLORIDA LICENSED GENERAL,
 BUILDING OR RESIDENTIAL CONTRACTOR.
 2. PROVIDE ENERGY SUBMITTAL FOR THIS PROJECT. ENERGY
 SUBMITTAL SUBMITTED IS FOR A PORCH ENCLOSURE.
 3. STATED VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK.
 4. PROVIDE DETAIL FOR FIRE RESISTANT RATING AT
 HORIZONTAL ASSEMBLY.
 5. PROVIDE DETAIL FOR VERTICAL RE-INFORCEMENT AT NEW
 FOUNDATION.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
 711.3 FIRE-RESISTANCE RATING.
 THE FIRE-RESISTANCE RATING OF FLOOR AND ROOF ASSEMBLIES
 SHALL NOT BE LESS THAN THAT REQUIRED BY THE BUILDING
 TYPE OF CONSTRUCTION. WHERE THE FLOOR ASSEMBLY
 SEPARATES MIXED OCCUPANCIES, THE ASSEMBLY SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN THAT REQUIRED
 BY SECTION 508.4 BASED ON THE OCCUPANCIES BEING
 SEPARATED. WHERE THE FLOOR ASSEMBLY SEPARATES A SINGLE
 OCCUPANCY INTO DIFFERENT FIRE AREAS, THE ASSEMBLY SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN THAT
 REQUIRED BY SECTION 707.3.10. HORIZONTAL ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDING AND
 HORIZONTAL ASSEMBLIES SEPARATING SLEEPING UNITS IN THE
 SAME BUILDING SHALL BE A MINIMUM OF 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-05 Cont ID  
Sent By cthroop Date 2016-01-05 Time 15:05 Rev Time 0.00
Received By cthroop Date 2016-01-05 Time 15:05 Sent To E
Notes
2016-01-05 15:20:34CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 FULL REVIEW CANNOT BE PERFORMED AT THIS TIME.
 PROVIDE A SCOPE OF WORK. CANNOT DETERMINE WHAT WORK IS
 BEING PROPOSED. POSSIBLE ALTERATION LEVEL II.
 VALUATION ($15,000) MAY BE UNDERVALUED.
 BASED ON REQUESTED SOW, DEMO PERMIT MAY BE REQUIRED.
  
 APPLICANT OF RECORD IS A ROOFING CONTRACTOR. A BUILDING
 OR GENERAL CONTRACTOR IS REQUIRED.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-06-27 Cont ID  
Sent By mvaldes Date 2016-06-27 Time 18:56 Rev Time 0.00
Received By mvaldes Date 2016-06-27 Time 18:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-16 Cont ID  
Sent By mvaldes Date 2016-03-16 Time 11:34 Rev Time 0.00
Received By mvaldes Date 2016-03-16 Time 11:34 Sent To  
Notes
2016-03-16 13:11:55REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
 ALTERNATE CONTACT
  
  
 NEC 230.23 A SERVICE CONDUCTORS SHALL HAVE SUFFICIENT
 AMPACITY TO CARRY CURRENT FOR THE LOAD AS CACULATED IN
 ACCORDANCE WITH ARTICLE 220.
 BOTH YOUR DEMAND LOADS ADD UP TOO 184 AMPS ( 92 + 92 )
 , THEREFORE A 150 AMP SERVICE IS NON-COMPLIANT MUST
 UPGRADE TO 200 OR RECALCULATE TO MATCH
 EXISTING RISER DIAGRAM. TABLE 310.16 B7 SHOWS 1/0 AWG
 IS GOOD FOR 175 AMPS NOT ENOUGH FOR LOAD CAPACITY.
  
 THE GROUNDING DETAIL RISER DIAGRAM SHOWS EACH 125 MCB
 PANEL RUNING AN INDIVIDUAL GROUNDING CONDUCTOR TO THE
 ELECTRODE THIS WILL PROVIDE A PARALLEL PATH FOR THE
 GROUNDED CONDUCTOR.
 PLEASE MAKE SURE ALL DISCONNECTS ARE SERVICE RATED A
 NOTE WILL SUFFICE. NEC 250, 300
  
 L

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-07 Cont ID  
Sent By mvaldes Date 2016-01-07 Time 13:50 Rev Time 0.00
Received By mvaldes Date 2016-01-07 Time 13:50 Sent To  
Notes
2016-01-07 14:15:171ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 DEFINE SCOPE OF WORK 107.3.5.2
 SHOW PANEL LOCATIONS ON FLOOR PLANS
 MEANS OF EGRESS ILLUMANATION FOR EXTERIOR STAIRS 210.70
 A NEC
 SITE CURRENT CODE STANDARDS. NEC 2011

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-07-25 Cont ID  
Sent By cthroop Date 2016-07-25 Time 13:00 Rev Time 0.00
Received By cthroop Date 2016-07-25 Time 13:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-13 Cont ID  
Sent By tklarge Date 2016-07-13 Time 11:55 Rev Time 0.00
Received By tklarge Date 2016-06-21 Time 10:04 Sent To  
Notes
2016-07-12 18:58:09TIM LARGE
2016-06-23 10:16:51R10
2016-06-22 10:04:49LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-07 Cont ID  
Sent By lmarchan Date 2016-04-07 Time 14:09 Rev Time 0.00
Received By lmarchan Date 2016-03-10 Time 15:31 Sent To  
Notes
2016-03-10 15:31:41R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-20 Cont ID  
Sent By skennedy Date 2016-01-20 Time 12:20 Rev Time 0.00
Received By skennedy Date 2015-12-10 Time 09:03 Sent To  
Notes
2015-12-11 09:03:32R13

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-07-12 Cont ID  
Sent By jvalido Date 2016-07-12 Time 18:56 Rev Time 0.00
Received By jvalido Date 2016-07-12 Time 18:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-07 Cont ID  
Sent By jvalido Date 2016-04-07 Time 09:38 Rev Time 0.00
Received By jvalido Date 2016-04-07 Time 09:14 Sent To  
Notes
2016-04-07 09:34:58CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE (FBC) 2010
 CHAPTER 1 ADMINISTRATION
  
 107.2.1 - PROVIDE EQUIPMENT SCHEDULE OF NEW A/C WALL
 UNITS. INCLUDE MANUFACTURER, MODEL NUMBER, TOTAL BTU,
 KW HEATER SIZE OR BTU OF HEAT, VOLTAGE AND MINIMUM/MAX
 FUSE SIZE.
  
 FLORIDA BUILDING CODE 5TH EDITION (2014)
 ENERGY CONSERVATION
  
 R403.6.1 - PROVIDE HEAT LOAD CALCULATIONS. INCLUDE FORM
 R402-2014. FORM MUST BE SIGNED BY "PREPARED BY" AND
 "OWNER AGENT"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-01-20 Cont ID  
Sent By skennedy Date 2016-01-20 Time 12:20 Rev Time 0.00
Received By skennedy Date 2016-01-20 Time 12:20 Sent To  
Notes
2016-01-20 12:20:41NO MECHANICAL PLAN PROVIDED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-07-13 Cont ID  
Sent By tklarge Date 2016-07-13 Time 11:53 Rev Time 0.00
Received By tklarge Date 2016-07-13 Time 09:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-03-24 Cont ID  
Sent By gjohnson Date 2016-03-24 Time 15:39 Rev Time 0.00
Received By gjohnson Date 2016-03-24 Time 15:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-16 Cont ID  
Sent By gjohnson Date 2015-12-16 Time 17:17 Rev Time 0.00
Received By gjohnson Date 2015-12-16 Time 17:16 Sent To  
Notes
2015-12-16 17:20:53 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
 1. PROVIDE SCOPE OF WORK FOR PLUMBING. PER WPB AMEND TO
 FBC SEC 107.2.1
 A COMPREHENSIVE REVIEW CAN NOT BE DONE AT THIS TIME DO
 TO LACK OF INFORMATION, THERE MAYBE ADDITIONAL
 COMMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2016-06-30 Cont ID  
Sent By cthroop Date 2016-06-30 Time 14:02 Rev Time 0.00
Received By cthroop Date 2016-06-30 Time 14:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-03-17 Cont ID  
Sent By cthroop Date 2016-03-17 Time 09:49 Rev Time 0.00
Received By cthroop Date 2016-03-17 Time 09:49 Sent To  
Notes
2016-03-17 09:53:242ND REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE ROOF SHEATHING AND FASTENER DETAIL FOR PROPOSED
 HIP ROOF.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-01-05 Cont ID  
Sent By cthroop Date 2016-01-05 Time 15:20 Rev Time 0.00
Received By cthroop Date 2016-01-05 Time 15:20 Sent To  
Notes
2016-01-05 15:23:46CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE ROOF SHEATHING DETAIL. PROVIDE FASTENER
 SCHEDULE. IDENTIFY UNDERLAYMENT.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  