Plan Review Details - Permit 15120386
Plan Review Stops For Permit 15120386
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-06 Cont ID  
Sent By jwitmer Date 2016-05-06 Time 15:10 Rev Time 0.00
Received By jwitmer Date 2016-05-06 Time 14:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-04-06 Cont ID  
Sent By jwitmer Date 2016-04-06 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2016-04-06 Time 06:31 Sent To  
Notes
2016-04-06 07:11:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120386
 ADD: 2087 PALM BEACH LAKES BLVD./ DUNKIN DONUTS
 CONT: VENTURA ARCHITECTURE/ DEVELOPMENT INC.
 TEL: (954)423-1362
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: APRIL 06/2016
 ACTION: DENIED
  
 1) 2ND REQUEST. PLEASE NOTE THE SHELL BUILDING IS NOT
 COMPLETE. A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (LM DEVELOPMENT GROUP) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER.
 PLEASE PROVIDE THE PERMIT NUMBER, ADDRESS WITHIN THE
 DOCUMENT.
  
 2) COMPLIED.THE COVERSHEET CS-1 INDICATES THE TENANT
 BUILD OUT PLANS ARE DESIGNED TO THE 2010 FBC-B. JUNE
 30/ 2015 THE FIFTH EDITION OF THE FLORIDA BUILDING CODE
 WAS ADOPTED STATEWIDE. PLEASE UPDATE THE PLANS TO THE
 CURRENT CODE.
  
 3) SEMI-COMPLIED. ONCE THE ENERGY GAUGE TOTAL BUILDING
 PERFORMANCE AND INPUT DATA REPORT FORMS ARE CODE
 COMPLIANT, THEY WILL NEED TO BE SUBMITTED UNDER THE
 BASE SHELL PERMIT AS WELL FOR FIELD VARIFICATION OF
 MATERIALS USED AND INSTALLED MATCH THAT OF THE INPUT
 DATA REPORT. COOPERATION BETWEEN THE SHELL AND TENANT
 BUILD-OUT CONTRACTORS IS VITAL TO KEEP THIS PROJECT
 MOVING FORWARD.
  
 4A) PROVISO: THIS WORK TO BE COMPLETED UNDER THE SHELL
 PERMIT. SHEET M-1 DETAIL # 2 FOR ROOF TOP A/C STAND
 PLEASE PROVIDE A PRODUCT APPROVAL. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) RROOFING PRODUCTS, ROOF CURBS AND ROOF TOP
 FANS, INTAKE AND EXHAUST.
 (G) PRE-ENGINEERED A/C STANDS
  
 4B) PROVISO: THIS WORK TO BE COMPLETED UNDER THE SHELL
 PERMIT. SHEET M-1 DETAIL # 4 SHOWS A EXHAUST FAN AND
 CURB. A PRODUCT APPROVAL WILL ALSO BE REQUIRED FOR ALL
 ROOF TOP EXHAUST FANS.
  
 4C) PROVISO: THIS WORK TO BE COMPLETED UNDER THE SHELL
 PERMIT. NOTE, TO DATE THE SHELL CONTRACTOR HAS
 REQUESTED ALL OF THE PRODUCT APPROVALS TO BE DEFERRED
 UNTIL AFTER PERMIT ISSUANCE. WE HAVE NOT SEEN ANY ROOF
 TOP CURBS FOR THE ROOF TOP A/C DOWN UNIT, NOR FASTENING
 OF THE CURB TO THE ROOF. 107.2.1.3 ADDITIONAL
 INFORMATION THAT MAY VERY FROM WHAT YOU HAVE DESIGN
 FOR. THE SHELL BUILDING PERMIT IS JUST THAT A SHELL
 BUILDING NO A/C EQUIPMENT.
  
 4D) PROVISO: THIS WORK TO BE COMPLETED UNDER THE SHELL
 PERMIT. 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5) 2ND REQUEST. PUTTING A NOTE ON THE PLANS TO COMPLY
 WITH THE CODE SECTION DOES NOT CONSTITUTE COMPLIANCE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART.
  
 SHEET A-1 PLEASE SHOW COMPLIANCE WITH THE 2014 FLORIDA
 ACCESSIBILITY :
  
 5A)2ND REQUEST. 226.1 GENERAL. WHERE DINING SURFACES
 ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT
 LEAST 5 PERCENT OF THE SEATING SPACES AND STANDING
 SPACES AT THE DINING SURFACES SHALL COMPLY WITH 902. IN
 ADDITION, WHERE WORK SURFACES ARE PROVIDED FOR USE BY
 OTHER THAN EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY
 WITH 902.
  
 5B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 5C) 2ND REQUEST. 227 SALES AND SERVICE 227.1 GENERAL.
 WHERE PROVIDED, CHECK-OUT AISLES, SALES COUNTERS,
 SERVICE COUNTERS, FOOD SERVICE LINES, QUEUES, AND
 WAITING LINES SHALL COMPLY WITH 227 AND 904.
  
 5D) 2ND REQUEST. 902.4.2 HEIGHT. THE TOPS OF TABLES AND
 COUNTERS SHALL BE 26 INCHES (660 MM) MINIMUM AND 30
 INCHES (760 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-15 Cont ID  
Sent By jwitmer Date 2015-12-15 Time 16:48 Rev Time 0.00
Received By jwitmer Date 2015-12-15 Time 13:53 Sent To  
Notes
2015-12-15 15:30:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120386
 ADD: 2087 PALM BEACH LAKES BLVD./ DUNKIN DONUTS
 CONT: VENTURA ARCHITECTURE/ DEVELOPMENT INC.
 TEL: (954)423-1362
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE NOTE THE SHELL BUILDING IS NOT COMPLETE. A
 LETTER FROM THE QUALIFIER OF BOTH THE SHELL CONTRACTOR
 (LM DEVELOPMENT GROUP) AND TENANT BUILD-OUT CONTRACTOR
 MUST BE PROVIDED BEFORE TENANT BUILD-OUT PERMIT CAN BE
 ISSUED, IF THE TENANT BUILD-OUT CONTRACTOR WISHES TO
 START WORK BEFORE THE SHELL WORK HAS RECEIVED A
 CERTIFICATE OF COMPLETION, AGREEING THEY WILL WORK
 TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE DOCUMENTS
 WILL NEED TO BE SIGNED BY THE QUALIFIER. PLEASE PROVIDE
 THE PERMIT NUMBER, ADDRESS WITHIN THE DOCUMENT.
  
 2) THE COVERSHEET CS-1 INDICATES THE TENANT BUILD OUT
 PLANS ARE DESIGNED TO THE 2010 FBC-B. JUNE 30/ 2015 THE
 FIFTH EDITION OF THE FLORIDA BUILDING CODE WAS ADOPTED
 STATEWIDE. PLEASE UPDATE THE PLANS TO THE CURRENT CODE.
  
 3) PLEASE NOTE THERE ARE DESIGN CONCEPTS WITHIN THE
 TENANT BUILD OUT PLANS THAT VARIES FROM THE SHELL
 PERMIT. ON THE M-1 SHEET DETAILS 2 & 4 BOTH INDICATE A
 CONCRETE TYPE ROOF DECK. THE SHELL PERMITED SET OF
 PLANS SHOWS A BAR JOIST SYSTEM, 1 1/2 INCH 22 GAGE G90
 "B" TYPE DECK ON SHEET S-2. ON THE A5 SHEET
 THE PLANS CALL OUT IN DETAILS 6 & 7 FOR R-19 RIGID
 INSULATION AND A TPO 60 MIL ROOFING SYSTEM. IN THE
 TENANT BUILD-OUT ENERGY INPUT DATA REPORT THE ROOF
 INDICATES A R-30 VALUE FOR THE INSULATION BOARD. THESE
 DISCREPANCIES WILL NEED TO BE WORKED OUT BETWEEN THE
 TWO DESIGN TEAMS BEFORE PERMIT ISSUANCE CAN OCCUR ON
 THE TENANT BUILD OUT. DISCREPANCY IN PLANS. 107.2.1.3.
  
 4A) SHEET M-1 DETAIL # 2 FOR ROOF TOP A/C STAND PLEASE
 PROVIDE A PRODUCT APPROVAL. FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) RROOFING PRODUCTS, ROOF CURBS AND ROOF TOP
 FANS, INTAKE AND EXHAUST.
 (G) PRE-ENGINEERED A/C STANDS
  
 4B) SHEET M-1 DETAIL # 4 SHOWS A EXHAUST FAN AND CURB.
 A PRODUCT APPROVAL WILL ALSO BE REQUIRED FOR ALL ROOF
 TOP EXHAUST FANS.
  
 4C) NOTE, TO DATE THE SHELL CONTRACTOR HAS REQUESTED
 ALL OF THE PRODUCT APPROVALS TO BE DEFERRED UNTIL AFTER
 PERMIT ISSUANCE. WE HAVE NOT SEEN ANY ROOF TOP CURBS
 FOR THE ROOF TOP A/C DOWN UNIT, NOR FASTENING OF THE
 CURB TO THE ROOF. 107.2.1.3 ADDITIONAL INFORMATION THAT
 MAY VERY FROM WHAT YOU HAVE DESIGN FOR. THE SHELL
 BUILDING PERMIT IS JUST THAT A SHELL BUILDING NO A/C
 EQUIPMENT.
  
 4D) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5) SHEET A-1 PLEASE SHOW COMPLIANCE WITH THE 2014
 FLORIDA ACCESSIBILITY :
  
 5A) 226.1 GENERAL. WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION,
 WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN
 EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
  
 5B) 226.2 DISPERSION.
 DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES AND WORK SURFACES.
  
 5C) 227 SALES AND SERVICE 227.1 GENERAL. WHERE
 PROVIDED, CHECK-OUT AISLES, SALES COUNTERS, SERVICE
 COUNTERS, FOOD SERVICE LINES, QUEUES, AND WAITING LINES
 SHALL COMPLY WITH 227 AND 904.
  
 5D) 902.4.2 HEIGHT. THE TOPS OF TABLES AND COUNTERS
 SHALL BE 26 INCHES (660 MM) MINIMUM AND 30 INCHES (760
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-24 Cont ID  
Sent By mvaldes Date 2016-03-24 Time 13:00 Rev Time 0.00
Received By mvaldes Date 2016-03-24 Time 13:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-06 Cont ID  
Sent By mvaldes Date 2016-01-06 Time 14:26 Rev Time 0.00
Received By mvaldes Date 2016-01-06 Time 14:03 Sent To  
Notes
2016-01-06 15:46:591ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 1- PLEASE SITE CURRENT CODE STANDARDS NEC 2011 FBC 2014
 2- RECEPTACLES WITHIN 6' OF SINK REQUIRE GFCI 210.8.A7
 3- COMMERCIAL KITCHENS GFCI 15 / 20 AMP OUTLETS NEC
 210.8B2
 4- FBC E C-405 LIGHTING CONTROLS IN INTERIOR /
 BATHROOMS AND RECCESSED
 LIGHTS MUST BE IC RATED AND SEALED.
 5- FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 6- PLEASE PROVIDE AIC CALCS OF OCPD AND SHORT CIRCUIT
 RATING OF EQUIPMENT NEC 110.10 / 110.9
 7- FIRE ALARM ON A SEPERATE PERMIT. IMPORTANT NOTICE
 ALL AUXILIARY AUDIO SYSTEMS SHALL BE AUTOMATICALLY
 MUTED BY THE FIRE ALARM CONTROL PANEL IN THE EVENT OF
 AN ALARM CONDITION
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-30 Cont ID  
Sent By scaldero Date 2016-03-30 Time 11:05 Rev Time 0.00
Received By scaldero Date 2016-03-30 Time 11:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-16 Cont ID  
Sent By scaldero Date 2015-12-16 Time 13:34 Rev Time 0.00
Received By scaldero Date 2015-12-16 Time 13:14 Sent To  
Notes
2015-12-16 13:30:39PERMIT # 15120386
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COMMENTS:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SHEET A-2 HAS A NOTE THAT READS "MENU BOARD SIZE AND
 LOCATION TO BE DETERMINED ON A SITE BY SITE BASIS." IT
 HAS BEEN OBSERVED AT OTHER DD LOCATIONS THAT THE MENU
 BOARD IS INSTALLED DIRECTLY ABOVE THE OVEN(S) AND/OR
 DIRECTLY UNDER THE HOOD SYSTEM. THIS PRACTICE IS NOT
 RECOMMENDED DUE TO THE DIRECT EXPOSURE TO HEAT AND
 SHOULD BE AVOIDED.
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM. (NFPA 72 IS REFERENCED
 UNDER APPLICABLE CODES.)
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-05-13 Cont ID  
Sent By ccole Date 2016-05-13 Time 07:39 Rev Time 0.00
Received By ccole Date 2016-05-11 Time 10:09 Sent To  
Notes
2016-05-12 10:09:52RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-06 Cont ID  
Sent By jwitmer Date 2016-05-06 Time 15:10 Rev Time 0.00
Received By jwitmer Date 2016-04-19 Time 11:04 Sent To  
Notes
2016-04-20 11:04:34B28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-12 Cont ID  
Sent By gjohnson Date 2016-04-12 Time 13:56 Rev Time 0.00
Received By gjohnson Date 2016-03-24 Time 09:28 Sent To  
Notes
2016-03-24 09:28:39B30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-06 Cont ID  
Sent By lmarchan Date 2016-01-06 Time 16:12 Rev Time 0.00
Received By lmarchan Date 2015-12-10 Time 09:36 Sent To  
Notes
2015-12-11 09:37:08B30

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-05-13 Cont ID  
Sent By ccole Date 2016-05-13 Time 07:39 Rev Time 0.00
Received By ccole Date 2016-05-13 Time 07:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-04-26 Cont ID  
Sent By ccole Date 2016-04-26 Time 09:21 Rev Time 0.00
Received By ccole Date 2016-04-26 Time 09:20 Sent To  
Notes
2016-04-26 09:49:343RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120386
 4/26/16
  
 A SEPARATE PERMIT IS REQUIRED FOR THE KITCHEN EXHAUST
 HOODS IN THE SPACE, HOWEVER THE FOLLOWING COMMENTS
 REGARDING THE HOODS WILL ALSO AFFECT HOW THE MAIN PLANS
 HVAC SYSTEMS ARE DESIGNED.
  
 1) THE REVISED PLAN SHOWS THE HOOD FOR THE CONVECTION
 OVEN HAS BEEN REMOVED. REFER TO SECTION 507.2.2 AND
 PROVIDE A TYPE II HOOD FOR THE OVEN OR VERIFY THAT THE
 HEAT AND MOISTURE LOAD HAS BEEN INCORPORATED INTO THE
 HVAC SYSTEM DESIGN, AND THE SPACE CONTAINING THE OVEN
 WILL BE PROVIDED WITH EXHAUST AT A RATE OF .70 CFM PER
 SF. PLEASE NOTE THAT THE AIR BALANCE CALCULATIONS MAY
 HAVE TO BE REVISED.
 2) REFER TO SECTION 508.1 AND INDICATE HOW THE MAKEUP
 AIR FOR HOOD A WILL BE AUTOMATICALLY CONTROLLED TO
 START AND OPERATE SIMULTANEOUSLY WITH THE MAKEUP AIR
 SYSTEM. PLEASE NOTE THAT COMPLIANCE WITH SECTION 508.2
 FOR MAKEUP AIR TEMPERATURE WILL ALSO HAVE TO BE
 VERIFED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-28 Cont ID  
Sent By ccole Date 2016-03-28 Time 13:43 Rev Time 0.00
Received By ccole Date 2016-03-28 Time 13:43 Sent To  
Notes
2016-03-28 14:14:502ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120386
 3/28/16
  
 1) SHEET M-1: THE O/A CALCULATIONS MUST INCLUDE THE
 REQUIRED 7.5 CFMS OF O/A PER PERSON AS REQUIRED BY
 TABLE 403,3.2
 2) M-1: EF-1, SHOWN AT THETYPE II HOOD LOCATION ON THE
 PLAN, IS NOTED TO BE 350 CFMS, BUT EF-1 IS LISTED AT 75
 CFMS IN THE SCHEDULE- PLEASE CLARIFY AND ALSO SHOW THE
 LOCATIONS OF EF-2 AND EF-3 ON THE PLANS. HOW MANY
 EXHAUST HOODS ARE IN THIS SPACE? PLEASE SHOW THE
 LOCATIONS OF THE HOODS ON THE PLANS AND INCLUDE THEM IN
 THE KITCHEN EQUIPMENT SCHEDULE.
 3) PLEASE SUBMIT MANUFACTURER'S CUT SHEETS AND
 MIAMI-DADE NOAS FOR THE ROOF FANS WITH REVIEW AND
 APPROVAL SIGNATURES BY THE E.O.R.
 4) PROVIDE A DUPLICATE SET OF ENERGY AND AC LOAD
 CALCULATIONS- ONLY ONE SET HAS BEEN SUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-18 Cont ID  
Sent By ccole Date 2015-12-18 Time 09:37 Rev Time 0.00
Received By ccole Date 2015-12-18 Time 09:37 Sent To E
Notes
2015-12-18 10:23:461ST REVIEW 2014 MECHANICAL
 PERMIT 15120386
 12/18/15
  
 1) SHEET M1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF RTU- 1 & 2 PER SECTION 606.2.1.
 INDICATE THE LOCATIONS OF THE REQUIRED DEVICES ON THE
 PLAN AND PROVIDE A SUBMITTAL REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL.
 2) AN EXHAUST RATE OF 0.7 CFM PER SQ.FT. IS REQUIIRED
 FOR THE KITCHEN PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A CALCULATION TO VERIFY COMPLIANCE.
 3) THE AC CALCULATIONS PASTED ON THE M1 SHEET IS
 INCOMPLETE AND IS SPECIFYING THE WRONG LOCATION. PLEASE
 PROVIDE CALCULATIONS FOR THE WEST PALM BEACH SUBMITTED
 IN HARD COPY, AND INCLUDE HEAT LOAD FROM APPLIANCES.
 4) PROVIDE SITE SPECIFIC WIND LOAD TIE DOWN
 ENGIONEERING FOR THE RTU'S IN COMPLIANCE WITHN SECTION
 301.15 FBC-14 MECHANICAL. INCLUDE DESIGN CRITERIA AND
 SHOW DETAILS FOR ATTACHING THE CURB TO THE STRUCTURE,
 AND THE RTU TO THE CURB, PROVIDE A SUBMITTAL OR PRODUCT
 APPROVAL FOR THE CURB REVIEWED AND APPROVED BY THE
 DESIGN PROFESSIONAL.
 5) PLACE A NOTE ON THE PLAN INDICATING SEPARATE PERMITS
 REQUIRED FOR THE HOOD, AND THE WALK-IN COOLER/FREEZER.
 6) SHOW COMPLIANCE WITH SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION- SHUTOFF DAMPER CONTROLS FOR O/A
 AIR.
 7) PROVIDE AN MECHANICAL ROOF PLAN INDICATING LOCATIONS
 OF ALL EXHAUST OUTLETS AND AIR INLETS, AND CLEARANCE
 DISTANCE MEASUREMENTS- SEE SECTIONS 401.4, 501.3.1
 FBC-10 MECHANICAL. PLEASE ALSO REVIEW SECTIONS 304.11
 AND 306.5 FOR APPLICABILITY TO THE PROPOSED ROOFTOP
 EQUIPMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-05-12 Cont ID  
Sent By gjohnson Date 2016-05-12 Time 13:40 Rev Time 0.00
Received By gjohnson Date 2016-05-12 Time 13:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-05-12 Cont ID  
Sent By gearl Date 2016-05-02 Time 11:16 Rev Time 0.00
Received By gjohnson Date 2016-05-02 Time 11:16 Sent To  
Notes
2016-05-02 11:19:36 
  
 1.RUN HAND SINK TO SANITARY NOT GREASE TRAP
  
 2. NEED TRAP RESEAL ON FLOOR DRAINS MARK ON PLANS
 DATED5/2/16
  
  
 GEORGE EARL PLUMBING PLANS REVIEWER

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-04-12 Cont ID  
Sent By gjohnson Date 2016-04-12 Time 13:55 Rev Time 0.00
Received By gjohnson Date 2016-04-12 Time 13:55 Sent To  
Notes
2016-04-12 13:55:50PLUMBING COMMENTS:
  
 1. SHT A-5 SHOW COMPLIANCE WITH FBC ACC.SEC. 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 2. SHT. A-5 SHOW THE LAVS IN COMPLIANCE WITH FBC
 ACC.SEC 306.3 KNEE AND TOE CLEARANCE.
  
 3.SIZE ALL PIPING ON GREASE,SANITARY AND WATER RISER
 DIAGRAMS. PER WPB AMEND. TO FBC 107.2.1
  
 4. THE FLOOR DRAINS IN BATHROOMS SHALL CONNECT TO WET
 VENT INDIVIDUALLY. PER FBC PLSEC. 912.1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-16 Cont ID  
Sent By gjohnson Date 2015-12-16 Time 16:16 Rev Time 0.00
Received By gjohnson Date 2015-12-16 Time 16:15 Sent To  
Notes
2015-12-16 16:16:28 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
 1.SHEET CS1 PLUMBING TO BE DESIGNED TO FBC PL 2014 5TH
 ADDITION.
 2.SHEET A-5 DETAIL D WOMAN'S BATHROOM COAT HOOK SHALL
 BE 48" MAX TO COMPLY WITH FBC ACC 603.4
 3.GRAB BARS SHALL BE MEASURE TO TOP OF GRIPPING SURFACE
 TO FF 33" MIN -36" MAX TO COMPLY WITH FBC ACC SEC 609.4
 4. SHEET A-5 SHOW LAVS TO COMPLY WITH FBC ACC SEC606.2
 AND 306
 5. SHEET P-1 GREASE RISER DIAGRAM IS MISSING P6 UNDER
 ICE COFFEE MACHINE NEXT TO BAKERY CASE ALSO MISSING P18
 NEXT TO WALK IN FREEZER . IT SHOWS A P4 WHERE THE MOP
 SINK IS IT SHOULD BE A P8. SHOW VENTS OFF WET VENT NOT
 OFF FLOOR SINKS.PER FBC PL SEC 912
 5. PROVIDE SANITARY RISER DIAGRAM. PER WPB AMEND. TO
 FBC SEC 107.3.5.1.3(13)
 6.SHOW WC AND MOP SINK AND P15,P11 ON WATER RISER
 DIAGRAM. PER WPB AMEND. TO FBC SEC 107.2.1
 7. NOTE MANUFACTURE AND MODEL OF WATER FILTER TO COMPLY
 WITH APPLICABLE STANDARDS.
 8. PROVIDE MODEL AND SIZING CALCULATION FROM
 MANUFACTURE FOR GREASE TRAP. PER WPB AMEND. TO FBC SEC
 107.2.1