Plan Review Details - Permit 15120385
Plan Review Stops For Permit 15120385
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-01-29 Cont ID  
Sent By jwitmer Date 2016-01-29 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2016-01-29 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-28 Cont ID  
Sent By jwitmer Date 2015-12-28 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2015-12-28 Time 11:28 Sent To  
Notes
2015-12-28 11:57:02BUILDING PLAN REVIEW
 REVISION: 15120385
 PERMIT: 14050151
 ADD: 1950 GOLDEN LAKES BLVD.
 CONT: ANTIOCH CONSTRUCTION
 TEL: (813)220-0281
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MON. DEC. 28/2015
 ACTION: DENIED
  
 1) REVISION OF PRODUCT APPROVALS, THE SUBMITTED NOA
 14-1112.06 ALDORA ALUMINUM & GLASS PRODUCTS WAS NOT
 PART OF THE PRODUCT APPROVALS REVIEWED BY THE DESIGNER
 OF RECORD.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.3.4.1
 THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 2) CONTRACTOR TO IDENTIFY THE TYPE OF GLAZING, SIZE OF
 GLAZING, TYPE OF ANCHORS, MULLION SIZE, RE-INFORCED OR
 NOT, AND PRESSURES BEFORE REVIEW OF DESIGNER OF RECORD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-29 Cont ID  
Sent By   Date 2016-01-29 Time   Rev Time 0.00
Received By tklarge Date 2016-01-29 Time 03:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-28 Cont ID  
Sent By jwitmer Date 2015-12-28 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2015-12-10 Time 09:09 Sent To  
Notes
2015-12-11 09:10:35REVISION ROUTED TO TKLARGE

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-01-29 Cont ID  
Sent By tklarge Date 2016-01-29 Time 03:42 Rev Time 0.00
Received By tklarge Date 2016-01-29 Time 03:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-15 Cont ID  
Sent By tklarge Date 2015-12-15 Time 13:51 Rev Time 0.00
Received By tklarge Date 2015-12-14 Time 05:01 Sent To  
Notes
2015-12-15 13:19:231) PLEASE SUBMIT A NARRATIVE FROM THE DESIGN
 PROFESSIONAL THAT CLEARLY DESCRIBES THE CHANGES THAT
 WERE MADE. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT A COMPRESSED AIR RISER SHOWING THE TYPE OF
 PIPE MATERIAL, PIPE SIZES, VALVE LOCATION, SUPPORTS,
 ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHOW THE LOCATION OF THE AIR COMPRESSORS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 4) WHERE ARE THE RELOCATED VACUUM UNITS THAT WERE IN
 THE CENTRAL VACUUM BUILDING?
 5) SHT. P-2 - PART OF THE SANITARY AND WATER RISER IS
 CUT OFF ON DETAIL #6 ON P-2.
 6) SHT. P-4 SHOWS 4 OIL SEPARATORS ON THE RISER AND
 ONLY 3 ON P-1. CLARIFY.
 7) THE SANITARY RISER ON P-4 FOR THE UNDERGROUND
 EXTERIOR SANITARY LINE DOES NOT MATCH THE PLAN VIEW ON
 SHT.P-1. CLARIFY,
 8) SHT. P-4 - PLEASE IDENTIFY THE OIL SEPARATORS AS
 SUCH. THEY ARE LABELED AS GREASE TRAPS.
 9) A LINT INTERCEPTOR WITH A WIRE BASKET SHALL BE
 INSTALLED ON THE WASHING MACHINE DRAIN PER FBC-PLUMBING
 SEC.1003.6.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  