Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-12-15 Cont ID  
Sent By albarran Date 2015-12-15 Time 14:45 Rev Time 0.00
Received By albarran Date 2015-12-15 Time 13:54 Sent To I
Notes
2015-12-15 14:50:57THIS PERMIT IS BEING CONDITIONALLY APPROVED AS NOTED:
 1. RECORDS INDICATE THAT THIS WORK WAS BEGUN WITHOUT
 THE BENEFIT OF A PERMIT.
 2. THE INTER-SYSTEM BONDING TERMINAL SHALL BE INSTALLED
 AS REQUIRED BY NEC 250.94.
 3. THE SUPPLEMENTAL GROUNDING ELECTRODE SHALL BE
 INSTALLED AS REQUIRED IN NEC 250.53
 4. SMOKE DETECTORS SHALL BE INSTALLED AS REQUIRED IN
 FBC-R 314.
 5. PROVIDED LOAD CALCS DO NOT APPEAR CORRECT AND WILL
 BE VERIFIED BE FIELD INSPECTOR.
  
 ALL WORK SUBJECT TO FIELD INSPECTOR'S APPROVAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-15 Cont ID  
Sent By albarran Date 2015-12-15 Time 14:51 Rev Time 0.00
Received By albarran Date 2015-12-10 Time 14:19 Sent To  
Notes
2015-12-15 14:53:1212/15/15 CONDITIONALLY APPROVED AS NOTED. 4 X FEE ADDED
 FOR WORK W/O PERMIT. CONTRACTOR NOTIFIED VIA EMAIL.
 SENT TO SMALL READY BIN "R". MA
2015-12-10 14:19:31ELEC <5K