| Plan Review Stops For Permit 15120326 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-02-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-26 |
Time |
18:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-26 |
Time |
17:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-12-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-12-29 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-12-29 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2015-12-29 17:55:57 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SHEET A000, PROJECT INFORMATION STATES THAT THE | | | CONSTRUCTION TYPE IS IIB, BUT OUR RECORDS SHOW THAT | | | THIS BUILDING IS A TYPE I (PERMIT APPLICATION DATE | | | 1/27/87). PLEASE CLARIFY OR REVISE, FBC 107. | | | | | | 2. SEE FBC 5TH ED. ACCESSIBILITY 404.2.6, TWO DOORS IN | | | A SERIES, AND REVISE PLAN TO SHOW DISTANCE FROM THE | | | ELEVATOR LOBBY PAIR OF DOORS TO THE LOBBY PAIR OF | | | DOORS. | | | | | | 3. SHEETS A003 AND A003A, ASSEMBLY OCCUPANT LOAD IS | | | CORRECT IN "EGRESS REQUIREMENTS" AT 15SF/PERSON, BUT | | | THE OCCUPANCY CLASSIF. LEGEND STATES THAT THE ACCESSORY | | | ASSEMBLY AREA IS 100 SF/PERSON, PLEASE CORRECT. | | | | | | 4. FBC 5TH ED. ACCESSIBILITY 202.4, CONFIRM THAT | | | EXISTING DRINKING FOUNTAINS AND RESTROOMS MEET THE | | | REQUIREMENTS FOR ACCESSIBLITY. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-02-11 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2016-02-11 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2016-02-10 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-02-01 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-02-01 |
Time |
19:50 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-02-01 |
Time |
19:50 |
Sent To |
|
|
| Notes |
| 2016-02-01 19:54:19 | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | PASS WITH A PROVISO. | | | | | | - 4TH AND 17 TH FLOOR EXTERIOR SIGNAGE NEEDS TO BE ON A | | | COMBINATION OF A PHOTO SENSOR AND A TIME SWITCH OR AN | | | ASTRONAMICAL TIMER . FBC- E C405.2.4 EXTERIOR LIGHTING | | | CONTROLS. | | | - AVAILABLE FAULT CURRENT LABEL IS REQUIRED NEC 110.24 | | | A & B | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
N |
Date |
2016-02-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-26 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-26 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2016-02-26 17:30:15 | SEE PREVIOUS FIRE REVIEW (AND FIRE REVIEW UNDER PERMIT | | | 15120325). | | | THE DESIGN WAS NOT MODIFIED; NOTES AND DIMENSIONS WERE | | | ADDED. THE FIRE STAMPED APPROVED DRAWINGS ARE BEING | | | RETAINED. | | | ALSO SEE PERMIT #15120325, WHICH HAS BEEN REVIEWED AND | | | PASSED BY FIRE. PLANS FOR BOTH 6TH AND 13TH FLOORS WERE | | | SUBMITTED; THE PLANS FOR THIS PERMIT 15120326 ARE | | | IDENTICAL TO THE PLANS REVIEWED BY FIRE UNDER 15120325. | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-12-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-12-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-12-11 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2015-12-11 14:30:36 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | 2. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | 3. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-02-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-26 |
Time |
18:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-09 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-02-03 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-02-03 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-12-09 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2016-02-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-25 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-25 |
Time |
11:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-12-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-12-17 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-12-17 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2015-12-17 12:28:14 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15120326 | | | 12/17/15 | | | | | | 1) PROVIDE THE AC COOLING AND HEATING CALCULATIONS FOR | | | THE NEW HEAT PUMPS IN LEVEL 13 - SEE SECTION C403.2.1 | | | FBC-14 ENERGY CONSERVATION. | | | 2) REVISE THE SUBMITTED ENERGY EFFICIENCY FORM 506-2014 | | | TO INCLUDE THE CRAC-1, AND THE CHILLED WATER SYSTEM | | | PIPING. PLEASE SEE TABLE C403.2.3(10) FBC-14 ENERGY | | | CONSERVATION. | | | 3) PROVIDE THE DIMENSIONS OF THE TRANSFER DUCTS SHOWN | | | ON THE HVAC PLANS ON LEVEL 13. | | | 4) REFER TO SECTION 306.1 FBC-14 MECHANICAL AND SHOW ON | | | THE PLANS HOW ACCESS FOR REPAIR AND REPLACEMENT OF THE | | | HEAT PUMPS WILL BE ACCOMPLISHED. WILL ACCESS PANELS BE | | | PROVIDED? | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2015-12-14 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-12-14 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-12-14 |
Time |
16:58 |
Sent To |
|
|
| Notes |
|
|