Plan Review Details - Permit 15120326
Plan Review Stops For Permit 15120326
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-26 Cont ID  
Sent By shill Date 2016-02-26 Time 18:16 Rev Time 0.00
Received By shill Date 2016-02-26 Time 17:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-29 Cont ID  
Sent By shill Date 2015-12-29 Time 17:55 Rev Time 0.00
Received By shill Date 2015-12-29 Time 15:11 Sent To  
Notes
2015-12-29 17:55:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SHEET A000, PROJECT INFORMATION STATES THAT THE
 CONSTRUCTION TYPE IS IIB, BUT OUR RECORDS SHOW THAT
 THIS BUILDING IS A TYPE I (PERMIT APPLICATION DATE
 1/27/87). PLEASE CLARIFY OR REVISE, FBC 107.
  
 2. SEE FBC 5TH ED. ACCESSIBILITY 404.2.6, TWO DOORS IN
 A SERIES, AND REVISE PLAN TO SHOW DISTANCE FROM THE
 ELEVATOR LOBBY PAIR OF DOORS TO THE LOBBY PAIR OF
 DOORS.
  
 3. SHEETS A003 AND A003A, ASSEMBLY OCCUPANT LOAD IS
 CORRECT IN "EGRESS REQUIREMENTS" AT 15SF/PERSON, BUT
 THE OCCUPANCY CLASSIF. LEGEND STATES THAT THE ACCESSORY
 ASSEMBLY AREA IS 100 SF/PERSON, PLEASE CORRECT.
  
 4. FBC 5TH ED. ACCESSIBILITY 202.4, CONFIRM THAT
 EXISTING DRINKING FOUNTAINS AND RESTROOMS MEET THE
 REQUIREMENTS FOR ACCESSIBLITY.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-11 Cont ID  
Sent By rlecky Date 2016-02-11 Time 13:03 Rev Time 0.00
Received By rlecky Date 2016-02-10 Time 14:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-02-01 Cont ID  
Sent By mvaldes Date 2016-02-01 Time 19:50 Rev Time 0.00
Received By mvaldes Date 2016-02-01 Time 19:50 Sent To  
Notes
2016-02-01 19:54:19FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 PASS WITH A PROVISO.
  
 - 4TH AND 17 TH FLOOR EXTERIOR SIGNAGE NEEDS TO BE ON A
 COMBINATION OF A PHOTO SENSOR AND A TIME SWITCH OR AN
 ASTRONAMICAL TIMER . FBC- E C405.2.4 EXTERIOR LIGHTING
 CONTROLS.
 - AVAILABLE FAULT CURRENT LABEL IS REQUIRED NEC 110.24
 A & B
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2016-02-26 Cont ID  
Sent By shill Date 2016-02-26 Time 17:29 Rev Time 0.00
Received By shill Date 2016-02-26 Time 17:29 Sent To  
Notes
2016-02-26 17:30:15SEE PREVIOUS FIRE REVIEW (AND FIRE REVIEW UNDER PERMIT
 15120325).
 THE DESIGN WAS NOT MODIFIED; NOTES AND DIMENSIONS WERE
 ADDED. THE FIRE STAMPED APPROVED DRAWINGS ARE BEING
 RETAINED.
 ALSO SEE PERMIT #15120325, WHICH HAS BEEN REVIEWED AND
 PASSED BY FIRE. PLANS FOR BOTH 6TH AND 13TH FLOORS WERE
 SUBMITTED; THE PLANS FOR THIS PERMIT 15120326 ARE
 IDENTICAL TO THE PLANS REVIEWED BY FIRE UNDER 15120325.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-11 Cont ID  
Sent By pleduc Date 2015-12-11 Time   Rev Time 0.00
Received By pleduc Date 2015-12-11 Time 09:45 Sent To  
Notes
2015-12-11 14:30:36THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 2. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 3. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-26 Cont ID  
Sent By shill Date 2016-02-26 Time 18:16 Rev Time 0.00
Received By shill Date 2016-02-09 Time 14:03 Sent To  
Notes
2016-02-09 14:03:16C31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-03 Cont ID  
Sent By lmarchan Date 2016-02-03 Time 13:29 Rev Time 0.00
Received By lmarchan Date 2015-12-09 Time 10:45 Sent To  
Notes
2015-12-09 10:51:01C29

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-02-25 Cont ID  
Sent By ccole Date 2016-02-25 Time 11:45 Rev Time 0.00
Received By ccole Date 2016-02-25 Time 11:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-17 Cont ID  
Sent By ccole Date 2015-12-17 Time 12:23 Rev Time 0.00
Received By ccole Date 2015-12-17 Time 12:23 Sent To  
Notes
2015-12-17 12:28:141ST REVIEW 2014 MECHANICAL
 PERMIT #15120326
 12/17/15
  
 1) PROVIDE THE AC COOLING AND HEATING CALCULATIONS FOR
 THE NEW HEAT PUMPS IN LEVEL 13 - SEE SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 2) REVISE THE SUBMITTED ENERGY EFFICIENCY FORM 506-2014
 TO INCLUDE THE CRAC-1, AND THE CHILLED WATER SYSTEM
 PIPING. PLEASE SEE TABLE C403.2.3(10) FBC-14 ENERGY
 CONSERVATION.
 3) PROVIDE THE DIMENSIONS OF THE TRANSFER DUCTS SHOWN
 ON THE HVAC PLANS ON LEVEL 13.
 4) REFER TO SECTION 306.1 FBC-14 MECHANICAL AND SHOW ON
 THE PLANS HOW ACCESS FOR REPAIR AND REPLACEMENT OF THE
 HEAT PUMPS WILL BE ACCOMPLISHED. WILL ACCESS PANELS BE
 PROVIDED?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-12-14 Cont ID  
Sent By gjohnson Date 2015-12-14 Time 16:58 Rev Time 0.00
Received By gjohnson Date 2015-12-14 Time 16:58 Sent To  
Notes
***NONE***