| Plan Review Stops For Permit 15120325 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-03-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-03-03 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-03-03 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-02-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-23 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-23 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2016-02-23 18:03:30 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB VIA | | | EMAIL, FBC 109 | | | | | | PLANS HAVE BEEN STAMPED AND ARE READY FOR ISSUANCE | | | | | | 2. THE PERMIT APPLICATION HAS THE FOLLOWING ISSUES: | | | | | | DESCRIPTION IS FOR DEMOLITION, BUT A RENOVATION IS | | | PROPOSED BASED ON THE PLANS REVIEWED. | | | THE NAME IN THE LINE FOR "CONTRACTOR (CERT. HOLDER) IS | | | DAVID T. SMITH, BUT ROBERT HEALY SIGNED THE PERMIT | | | APPLICATION. THE PERMIT IS ASSIGNED TO CONTRACTOR | | | ROBERT HEALY, ICONSTRUCTORS, CBC 1256368. | | | THE VALUE ON THE PERMIT APPLICATION IS $50,000 WHICH | | | APPEARS TO BE A VALUE CONSISTENT WITH THE SCOPE | | | (DEMOLITION). | | | | | | | | | | | 2016-02-23 17:29:46 | ****PROVISO**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PROVISO - 6TH FLOOR EXISTING DRINKING FOUNTAIN, | | | RESTROOMS AND ACCESSIBLE ROUTE TO COMPLY WITH FBC 5TH | | | EDITION ACCESSIBILITY | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-12-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-12-29 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-12-29 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2015-12-29 17:45:45 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SHEET A000, PROJECT INFORMATION STATES THAT THE | | | CONSTRUCTION TYPE IS IIB, BUT OUR RECORDS SHOW THAT | | | THIS BUILDING IS A TYPE I (PERMIT APPLICATION DATE | | | 1/27/87). PLEASE CLARIFY OR REVISE, FBC 107. | | | | | | 2. SEE FBC 5TH ED. ACCESSIBILITY 404.2.6, TWO DOORS IN | | | A SERIES, AND REVISE PLAN TO SHOW DISTANCE FROM THE | | | ELEVATOR LOBBY PAIR OF DOORS TO THE LOBBY PAIR OF | | | DOORS. | | | | | | 3. SHEETS A003 AND A003A, ASSEMBLY OCCUPANT LOAD IS | | | CORRECT IN "EGRESS REQUIREMENTS" AT 15SF/PERSON, BUT | | | THE OCCUPANCY CLASSIF. LEGEND STATES THAT THE ACCESSORY | | | ASSEMBLY AREA IS 100 SF/PERSON, PLEASE CORRECT. | | | | | | 4. FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS, | | | OVERHEAD, PROFIT, DESIGN FEES. PROVIDE A COPY OF THE | | | CONTRACT FOR THIS PROJECT. | | | | | | 5. FBC 5TH ED. ACCESSIBILITY 202.4, CONFIRM THAT | | | EXISTING DRINKING FOUNTAINS AND RESTROOMS MEET THE | | | REQUIREMENTS FOR ACCESSIBLITY. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-02-16 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2016-02-16 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2016-02-10 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2016-01-26 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2016-01-26 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2016-01-26 |
Time |
12:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-02-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-02-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-02-10 |
Time |
16:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-12-14 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-12-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-12-11 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2015-12-14 09:52:39 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF | | | THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE | | | AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF | | | WALLS REQUIRE AN EVALUATION. | | | | | | 2. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | 3. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-02-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-23 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-09 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2016-01-26 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2016-01-26 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2015-12-09 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2016-02-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-17 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-16 |
Time |
07:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-12-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-12-17 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-12-17 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2015-12-17 12:10:24 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15120325 | | | 12/17/15 | | | | | | 1) PROVIDE THE AC COOLING AND HEATING CALCULATIONS FOR | | | THE NEW HEAT PUMPS IN LEVEL 6 - SEE SECTION C403.2.1 | | | FBC-14 ENERGY CONSERVATION. | | | 2) REVISE THE SUBMITTED ENERGY EFFICIENCY FORM 506-2014 | | | TO INCLUDE THE THE CHILLED WATER SYSTEM PIPING. PLEASE | | | SEE TABLE C403.2.3(10) FBC-14 ENERGY CONSERVATION. | | | 3) PROVIDE THE DIMENSIONS OF THE TRANSFER DUCTS SHOWN | | | ON THE HVAC PLANS ON LEVEL 6. | | | 4) REFER TO SECTION 306.1 FBC-14 MECHANICAL AND SHOW ON | | | THE PLANS HOW ACCESS FOR REPAIR AND REPLACEMENT OF THE | | | HEAT PUMPS WILL BE ACCOMPLISHED. WILL ACCESS PANELS BE | | | PROVIDED? | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2015-12-15 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-12-15 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-12-15 |
Time |
14:19 |
Sent To |
|
|
| Notes |
|
|