Plan Review Details - Permit 15120325
Plan Review Stops For Permit 15120325
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-03 Cont ID  
Sent By shill Date 2016-03-03 Time 10:39 Rev Time 0.00
Received By shill Date 2016-03-03 Time 10:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-23 Cont ID  
Sent By shill Date 2016-02-23 Time 17:28 Rev Time 0.00
Received By shill Date 2016-02-23 Time 17:20 Sent To  
Notes
2016-02-23 18:03:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB VIA
 EMAIL, FBC 109
  
 PLANS HAVE BEEN STAMPED AND ARE READY FOR ISSUANCE
  
 2. THE PERMIT APPLICATION HAS THE FOLLOWING ISSUES:
  
 DESCRIPTION IS FOR DEMOLITION, BUT A RENOVATION IS
 PROPOSED BASED ON THE PLANS REVIEWED.
 THE NAME IN THE LINE FOR "CONTRACTOR (CERT. HOLDER) IS
 DAVID T. SMITH, BUT ROBERT HEALY SIGNED THE PERMIT
 APPLICATION. THE PERMIT IS ASSIGNED TO CONTRACTOR
 ROBERT HEALY, ICONSTRUCTORS, CBC 1256368.
 THE VALUE ON THE PERMIT APPLICATION IS $50,000 WHICH
 APPEARS TO BE A VALUE CONSISTENT WITH THE SCOPE
 (DEMOLITION).
  
  
  
2016-02-23 17:29:46****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVISO - 6TH FLOOR EXISTING DRINKING FOUNTAIN,
 RESTROOMS AND ACCESSIBLE ROUTE TO COMPLY WITH FBC 5TH
 EDITION ACCESSIBILITY
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-29 Cont ID  
Sent By shill Date 2015-12-29 Time 17:42 Rev Time 0.00
Received By shill Date 2015-12-29 Time 07:43 Sent To  
Notes
2015-12-29 17:45:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SHEET A000, PROJECT INFORMATION STATES THAT THE
 CONSTRUCTION TYPE IS IIB, BUT OUR RECORDS SHOW THAT
 THIS BUILDING IS A TYPE I (PERMIT APPLICATION DATE
 1/27/87). PLEASE CLARIFY OR REVISE, FBC 107.
  
 2. SEE FBC 5TH ED. ACCESSIBILITY 404.2.6, TWO DOORS IN
 A SERIES, AND REVISE PLAN TO SHOW DISTANCE FROM THE
 ELEVATOR LOBBY PAIR OF DOORS TO THE LOBBY PAIR OF
 DOORS.
  
 3. SHEETS A003 AND A003A, ASSEMBLY OCCUPANT LOAD IS
 CORRECT IN "EGRESS REQUIREMENTS" AT 15SF/PERSON, BUT
 THE OCCUPANCY CLASSIF. LEGEND STATES THAT THE ACCESSORY
 ASSEMBLY AREA IS 100 SF/PERSON, PLEASE CORRECT.
  
 4. FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS,
 OVERHEAD, PROFIT, DESIGN FEES. PROVIDE A COPY OF THE
 CONTRACT FOR THIS PROJECT.
  
 5. FBC 5TH ED. ACCESSIBILITY 202.4, CONFIRM THAT
 EXISTING DRINKING FOUNTAINS AND RESTROOMS MEET THE
 REQUIREMENTS FOR ACCESSIBLITY.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-16 Cont ID  
Sent By rlecky Date 2016-02-16 Time 10:31 Rev Time 0.00
Received By rlecky Date 2016-02-10 Time 14:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-01-26 Cont ID  
Sent By rlecky Date 2016-01-26 Time 13:00 Rev Time 0.00
Received By rlecky Date 2016-01-26 Time 12:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-11 Cont ID  
Sent By pleduc Date 2016-02-11 Time   Rev Time 0.00
Received By pleduc Date 2016-02-10 Time 16:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-14 Cont ID  
Sent By pleduc Date 2015-12-14 Time   Rev Time 0.00
Received By pleduc Date 2015-12-11 Time 16:52 Sent To  
Notes
2015-12-14 09:52:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS REQUIRE AN EVALUATION.
  
 2. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 3. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-23 Cont ID  
Sent By shill Date 2016-02-23 Time 17:30 Rev Time 0.00
Received By shill Date 2016-02-09 Time 13:59 Sent To  
Notes
2016-02-09 14:00:15C30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-26 Cont ID  
Sent By rlecky Date 2016-01-26 Time 13:00 Rev Time 0.00
Received By rlecky Date 2015-12-09 Time 13:53 Sent To  
Notes
2015-12-09 14:03:17C26

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-02-17 Cont ID  
Sent By ccole Date 2016-02-17 Time 07:37 Rev Time 0.00
Received By ccole Date 2016-02-16 Time 07:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-17 Cont ID  
Sent By ccole Date 2015-12-17 Time 11:49 Rev Time 0.00
Received By ccole Date 2015-12-17 Time 11:48 Sent To  
Notes
2015-12-17 12:10:241ST REVIEW 2014 MECHANICAL
 PERMIT #15120325
 12/17/15
  
 1) PROVIDE THE AC COOLING AND HEATING CALCULATIONS FOR
 THE NEW HEAT PUMPS IN LEVEL 6 - SEE SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 2) REVISE THE SUBMITTED ENERGY EFFICIENCY FORM 506-2014
 TO INCLUDE THE THE CHILLED WATER SYSTEM PIPING. PLEASE
 SEE TABLE C403.2.3(10) FBC-14 ENERGY CONSERVATION.
 3) PROVIDE THE DIMENSIONS OF THE TRANSFER DUCTS SHOWN
 ON THE HVAC PLANS ON LEVEL 6.
 4) REFER TO SECTION 306.1 FBC-14 MECHANICAL AND SHOW ON
 THE PLANS HOW ACCESS FOR REPAIR AND REPLACEMENT OF THE
 HEAT PUMPS WILL BE ACCOMPLISHED. WILL ACCESS PANELS BE
 PROVIDED?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-12-15 Cont ID  
Sent By gjohnson Date 2015-12-15 Time 14:19 Rev Time 0.00
Received By gjohnson Date 2015-12-15 Time 14:19 Sent To  
Notes
***NONE***