Plan Review Details - Permit 15120320
Plan Review Stops For Permit 15120320
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-04-01 Cont ID  
Sent By cthroop Date 2016-04-01 Time 08:32 Rev Time 0.00
Received By cthroop Date 2016-04-01 Time 08:32 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-16 Cont ID  
Sent By cthroop Date 2016-03-16 Time 13:17 Rev Time 0.00
Received By cthroop Date 2016-03-16 Time 09:12 Sent To  
Notes
2016-03-16 13:28:012ND REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. BUILDING VALUATION TOO LOW. VALUATION ADJUSTED UP
 FROM $500,000.00 TO $635,457.00 PER THE ICC BUILDING
 EVALUATION DATA TABLE.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2. PROVIDE ELEVATION CERTIFICATE.
 FBC 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) &
 R322.2.1 ELEVATION REQUIREMENTS. BUILDINGS AND
 STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS
 COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED
 TO OR ABOVE THE DESIGN FLOOD ELEVATION. PROVIDE FLOOD
 DESIGN INFORMATION ON THE PROPOSED SURVEY AND PROVIDE
 FLOOD ELEVATION CERTIFICATE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-01-11 Cont ID  
Sent By cthroop Date 2016-01-11 Time 14:10 Rev Time 0.00
Received By cthroop Date 2016-01-11 Time 14:10 Sent To E
Notes
2015-12-11 10:20:1612/11/15 ZONING FAILED
 1. SUBMIT TWO CERTIFIED UP TO DATE SURVEYS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-03 Cont ID  
Sent By mvaldes Date 2016-03-03 Time 15:54 Rev Time 0.00
Received By mvaldes Date 2016-03-03 Time 15:54 Sent To  
Notes
2016-03-03 15:58:49ROUTED BACK TO R 30

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-11 Cont ID  
Sent By mvaldes Date 2016-01-11 Time 16:39 Rev Time 0.00
Received By mvaldes Date 2016-01-11 Time 16:39 Sent To  
Notes
2016-01-11 17:02:121ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 1- POOL ON A SEPERATE PERMIT
 2- PROVIDE GFCI PROTECTION ON KITCHEN COUNTERTOP ,
 GARAGE DOOR, FRONT AND BACK OF RESIDENCE. NEC 210.8 A /
 NEC 210.52 E
 3- 210.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 (A) DWELLING UNITS. ALL 120-VOLT, SINGLE PHASE, 15- AND
 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED
 IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION
 ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS
 SHALL
 BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER,
 COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF
 THE
 BRANCH CIRCUIT. ( MAKE SURE AFCI PROTECTION IS ON ALL
 THESE AREAS. )
 4-NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
 5- NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT. ( SHOW AC UNITS ON FLOOR
 PLAN.)
 6-FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN
 10 FEET OF EACH SLEEPING ROOM.
 7- FBC-ER 404.1.1 / 402.4.4
 RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT
 AS WELL AS IC RATED AND SEALED TO NOT COMPROMISE
 BUILDING THERMAL ENVELOPE. ( 2 CFM )
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-02-28 Cont ID  
Sent By tklarge Date 2016-02-28 Time 04:23 Rev Time 0.00
Received By tklarge Date 2016-02-28 Time 04:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-04-05 Cont ID  
Sent By dkittred Date 2016-04-05 Time 10:35 Rev Time 0.00
Received By dkittred Date 2016-03-31 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-30 Cont ID  
Sent By cthroop Date 2016-03-30 Time 13:47 Rev Time 0.00
Received By cthroop Date 2016-03-25 Time 13:21 Sent To  
Notes
2016-03-25 13:21:37RESUB ROUTED TO DKITTREDGE VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-16 Cont ID  
Sent By cthroop Date 2016-03-16 Time 13:17 Rev Time 0.00
Received By cthroop Date 2016-02-22 Time 09:24 Sent To  
Notes
2016-02-23 09:25:05R30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-13 Cont ID  
Sent By cthroop Date 2016-01-13 Time 16:06 Rev Time 0.00
Received By cthroop Date 2015-12-08 Time 10:26 Sent To  
Notes
2015-12-09 10:26:35R30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2016-01-13 Cont ID  
Sent By cthroop Date 2016-01-13 Time 16:05 Rev Time 0.00
Received By cthroop Date 2016-01-13 Time 16:05 Sent To  
Notes
2016-01-13 16:06:19IMPACR FEE - MV 2015-28326

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-15 Cont ID  
Sent By ccole Date 2016-03-15 Time 12:28 Rev Time 0.00
Received By ccole Date 2016-03-15 Time 12:28 Sent To  
Notes
2016-03-15 12:30:58MECHANICAL PROVISIOS:
 3/15/16
  
 1) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE AC SYSTEMS SHALL BE ON-SITE AT
 TIME OF INSPECTION.
 2) THE AC CONDENSERS SHALL BE INSTALLED AT OR ABOVE THE
 REQUIRED FLOOD ELEVATION HEIGHT PER SECTION R322.1.6
 FBC-14 RESIDENTIAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-13 Cont ID  
Sent By ccole Date 2016-01-13 Time 13:57 Rev Time 0.00
Received By ccole Date 2016-01-13 Time 09:58 Sent To  
Notes
2016-01-13 14:59:491ST REVIEW: FBC 2014 RESIDENTIAL MECHANICAL
  
 1) THE MANUAL J WORKSHEETS SHOW HIGHER U-VALUES FOR THE
 WINDOWS THAT DON'T MATCH THE U-VALUES SHOWN ON THE
 ENERGY CALCULATION FORM R405-2014. PLEASE CORRECT.
 2) THERE IS NO DATA LISTED ON THE MANUAL J WORKSHEETS
 FOR THE EXTERIOR DOORS AT THE FOYER AND AT GUEST BATH,
 AND THE ENERGY FORM DOES NOT LIST ANY DATA FOR THE
 FRONT ENTRY DOORS, AND REAR DOOR AT THE GUEST BATH.
 3) REFER TO SECTION M1305.1.1 FBC-14 RESIDENTIAL AND
 INDICATE COMPLIANCE FOR THE SIZE OF THE AC CLOSETS: THE
 WIDTH OF THE ENCLOSING SPACES AT LEAST 12 INCHES WIDER
 THAN THE AIR HANDLERS.
 4) REFER TO SECTION R322.1.6 AND SHOW THE LOCATIONS OF
 THE AC CONDENSERS ON THE PLANS, AND THE ELEVATION
 HEIGHT OF THE MOUNTING PADS. PLEASE ALSO PROVIDE
 DETAILS FOR CONSTRUCTION OF THE PADS.
 5) CORRECT THE 2010 FBC REFERENCE SHOWN IN THE ACCU
 DETAIL ON SHEET 1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2016-03-30 Cont ID  
Sent By cthroop Date 2016-03-30 Time 13:48 Rev Time 0.00
Received By cthroop Date 2016-03-30 Time 13:48 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2016-03-16 Cont ID  
Sent By cthroop Date 2016-03-16 Time 13:15 Rev Time 0.00
Received By cthroop Date 2016-03-16 Time 13:15 Sent To  
Notes
2016-03-16 13:17:252ND REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PREVIOUS COMMENTS NOT ADDRESSED. PLEASE RESPOND TO
 ITEMS # 1, 4 & 5 FROM REVIEW DATED 12/14/15.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2015-12-14 Cont ID  
Sent By shill Date 2015-12-14 Time 08:24 Rev Time 0.00
Received By shill Date 2015-12-14 Time 08:24 Sent To  
Notes
2015-12-14 08:47:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 2014 RESIDENTIAL, CITY OF WEST PALM BEACH MUNICIPAL
 CODE 94-546(B), FBC 107, FBC 110.7, FBC 104.1, THIS
 IMPROVEMENT APPEARS TO BE LOCATED IN THE SPECIAL HAZARD
 FLOOD AREA. PROVIDE THE FOLLOWING INFORMATION:
  
 1. SURVEY OF THE PROPERTY INCLUDING ELEVATIONS
 (TOPOGRAPHIC INFORMATION). THE SURVEY IS TO INCLUDE THE
 FOLLOWING:
  
 NORTH ORIENTATION
 PARCEL BOUNDARIES AND LOCATION AND NAMES OF ADJACENT
 STREETS
 FLOOD BOUNDARIES THAT RUN THROUGH THE PARCEL IF
 APPLICABLE
 ALL DRAINAGE AND UTILITY EASEMENTS
 ALL AREAS TO BE CLEARED, CUT, GRADED, OR FILLED
 THE LOCATION OF ALL EXISTING AND PROPOSED FENCES,
 WALLS, AND OTHER STRUCTURES
 FOOTPRINT OF ALL EXISTING AND PROPOSED BUILDINGS
 THE ELEVATION OF THE LOWEST FLOOR OF THE BUILDING AND
 OF THE ATTACHED GARAGE
 THE LOCATION AND ELEVATION OF ALL MECHANICAL AND
 UTILITY EQUIPMENT SERVICING THE BUILDING
  
 2. SHEET S1 AND OTHER PAGES, REVISE PLANS TO CLARIFY
 PROPOSED DESIGN FLOOR ELEVATION OF FINISHED FLOOR FOR
 THE RESIDENCE.
  
 3. SHEET S1 AND OTHER PAGES, REVISE PLANS TO CLARIFY
 PROPOSED DESIGN FLOOR ELEVATION FOR THE GARAGE. THE
 GARAGE FINISHED FLOOR ELEVATION IS TO BE A MINIMUM OF
 7'6" OR IS TO INCLUDE ENOUGH FLOOD VENTS TO COMPLY WITH
 THE REQUIREMENTS OF NFIP TECHNICAL BULLETIN #1
 (OPENINGS IN FOUNDATION WALLS AND WALLS OF
 ENCLOSURES"). IF FLOOD VENTS ARE PROPOSED, REVISE PLAN
 TO SHOW SIZE AND LOCATION. IF ENGINEERED FLOOD VENTS
 ARE PROPOSED, PROVIDE ENGINEERING OR PRODUCT APPROVAL.
  
 4. SHEETS S1 AND OTHER PAGES, REVISE PLANS TO INCLUDE
 PROPOSED ELEVATION AND LOCATION OF EQUIPMENT SERVICING
 THE BUILDING.
  
 5. A "CONSTRUCTION DOCUMENT" ELEVATION CERTIFICATE IS
 RECOMMENDED AT THIS TIME TO AVOID INSPECTION AND C.O.
 DELAYS. THIS DOCUMENT WILL BE REVIEWED AND ANY ISSUES
 WILL BE REQUIRED TO BE CORRECTED PRIOR TO C.O. BUT WILL
 NOT DELAY ISSUANCE OF THIS PERMIT.
  
 6. ADVISORY ONLY, A "BUILDING UNDER CONSTRUCTION"
 ELEVATION CERTIFICATE IS RECOMMENDED AT TIME OF FORM
 BOARD INSPECTION. A FORM BOARD SURVEY WILL BE REQUIRED.
  
 7. ADVISORY ONLY, A "FINISHED CONSTRUCTION" ELEVATION
 CERTIFICATE WILL BE REQUIRED AFTER THE FINAL FINISHED
 GRADE, BEFORE FINAL INSPECTION/CERTIFICATE OF OCCUPANCY
 (C.O.).
  
  
  
  
  
  
 B. THE FINISHED FLOOR DFE IS TO BE A MINIMUM OF 6"
 ABOVE BFE. REVISE PLAN TO SHOW PROPOSED FINISHED FLOOR
 ELEVATION.
  
 C.

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-02-28 Cont ID  
Sent By tklarge Date 2016-02-28 Time 04:04 Rev Time 0.00
Received By tklarge Date 2016-02-28 Time 03:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-12 Cont ID  
Sent By gjohnson Date 2015-12-12 Time 12:22 Rev Time 0.00
Received By gjohnson Date 2015-12-12 Time 12:22 Sent To  
Notes
2015-12-12 12:40:051ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.PLUMBING FOR POWDER ROOM NOT SHOWN ON RISER DIAGRAM
 P-LEASE PROVIDE COMPLETE RISER DIAGRAM. PER WPB
 AMEND.TO FBC SEC 107.2.1
 2. THE FIXTURE DRAIN FOR THE SHOWER OR TUB CANNOT TIE
 INTO FIXTURE DRAIN OF WATER CLOSET EACH FIXTURE DRAIN
 SHALL TIE IN INDEPENDENTLY TO THE WET VENT .PER FBC PL
 SEC 912.1
 3. THE FIXTURE DRAIN FOR THE WATER CLOSET AND SHOWER IN
 GUEST BATH #3 NEED TO TIE IN TO THE HORIZONTAL WET VENT
 NOT VERTICAL.PER WPB AMEND.TO FBC SEC 107.2.1
 4.SHOW LOCATION OF WATER HEATER AND PROVIDE SPECS FOR
 WATER HEATER. PER WPB AMEND.TO FBC SEC 107.2.1
 5. SEPARATE PERMIT REQUIRED FOR GAS GAS PERMIT
 APPLICATION REQUIREMENTS
  
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-01-11 Cont ID  
Sent By cthroop Date 2016-01-11 Time 14:09 Rev Time 0.00
Received By cthroop Date 2016-01-11 Time 14:09 Sent To  
Notes
2016-01-07 18:13:43ROOFING

Review Stop Z ZONING
Rev No 4 Status P Date 2016-04-05 Cont ID  
Sent By dkittred Date 2016-04-05 Time 10:34 Rev Time 0.00
Received By dkittred Date 2016-04-04 Time 16:15 Sent To  
Notes
2016-04-05 10:35:194/5/16 - CONDITIONAL APPROVAL ISSUED.
 LANDSCAPE/IRRIGATION PERMIT REQUIRED TO BE SUBMITTED,
 APPROVED, AND INSTALLED PRIOR TO ISSUANCE OF A C.O. FOR
 THE NEW HOUSE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2016-03-30 Cont ID  
Sent By dkittred Date 2016-03-30 Time 10:24 Rev Time 0.00
Received By dkittred Date 2016-03-25 Time 17:11 Sent To B
Notes
2016-03-30 10:29:01PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/30/16
  
 1. ELEVATION SHEETS A202, A203, A301, AND A302 WERE NOT
 REVISED TO REFLECT CHANGES TO THE HEIGHT OF THE
 BUILDING. PLEASE REVISE SHEETS AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-02-01 Cont ID  
Sent By dkittrid Date 2016-02-29 Time 08:09 Rev Time 0.00
Received By dkittred Date 2016-02-29 Time 10:08 Sent To  
Notes
2016-02-29 12:56:47PLANNING AND ZONING COMMENTS: ***FAILED***
  
 2/29/16
  
 1. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH
 ARTICLE XIV SHALL BE SUBMITTED. (NOTE: ZLDR SEC.
 94-442(B)(2)A. - FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF.)
  
 2. REAR SETBACK MUST BE A MINIMUM OF 15 FEET OR 10% THE
 DEPTH OF THE LOT, WHICHEVER IS LESS. 10% OF THE LOT
 DEPTH IS 9.583 FEET OR 9'-7". THE PLAN SHOWS 9.5 AND
 9'-6". PLEASE REVISE. [ZLDR SEC, 94-72(A)(2)(C)].
  
 3. PLEASE DIMENSION ON THE SITE PLAN THE ENCROACHMENT
 OF THE BALCONY (SOUTH ELEVATION) INTO THE FRONT
 SETBACK. MAXIMUM ENCROACHMENT FOR THE BALCONY IS 3 FEET
 [ZLDR SEC. 94-305(B)(2)].
  
 4. IT IS UNCLEAR THE SETBACK OF THE CHIMNEY ON THE EAST
 ELEVATION. PLEASE DIMENSION AND NOTE THAT CHIMNEY
 ELEMENTS ARE PERMITTED TO ENCROACH A MAXIMUM OF 18
 INCHES INTO A REQUIRED SETBACK [ZLDR SEC.
 94-305(B)(10)].
  
 5. MECHANICAL EQUIPMENT (A/C UNITS) MAY NOT ENCROACH
 MORE THAN 4 FEET INTO A REQUIRED SETBACK. PLEASE
 INDICATE COMPLIANCE [ZLDR SEC. 94-305(B)(4)].
  
 6. ROOF OVERHANGS MAY NOT PROJECT MORE THAN 3 FEET INTO
 A REQUIRED SETBACK. THE PLANS SHOW THE OVERHANGS
 DIMENSIONED AT 2'-6", BUT THE DIMENSION IS NOT MEASURED
 FROM THE WALL OF THE HOUSE TO THE VERY EDGE OF THE
 OVERHANG. PLEASE INCLUDE A DIMENSION ON THE PLAN THAT
 THE OVERHANG WILL NOT ENCROACH GREATER THAN 3 FEET INTO
 A REQUIRED SETBACK [ZLDR SEC. 94-305(B)(2)].
  
 7. SUBMITTED PLOT PLAN ON THE SURVEY AND SITE PLAN
 WITHIN THE HOUSE PLANS SET SHOW SLIGHTLY DIFFERENT SIDE
 SETBACKS. PLEASE CLARIFY WHICH ONES WILL BE USED.
  
 8. THE MAXIMUM BUILDING HEIGHT IN THE SF7 ZONING
 DISTRICT IS 30 FEET. THERE ARE SEVERAL ISSUES WITH THE
 MEASUREMENTS ON THE DRAWINGS AND DEFINITIONS FOR HEIGHT
 MEASUREMENT ARE PROVIDED IN THE DEFINITIONS SECTION OF
 THE CITY'S ZLDRS.
  
 A. THE HEIGHT OF THE STRUCTURE NEEDS TO BE MEASURED
 FROM THE FINISHED GRADE RATHER THAN THE SLAB OF THE
 HOUSE.
  
 B. FOR A GABLE, HIP, OR GAMBREL ROOFS, HEIGHT OF THE
 BUILDING IS MEASURED FROM THE FINISHED GRADE TO THE
 MEAN HEIGHT BETWEEN THE EAVES AND RIDGE OF THE ROOF
 STRUCTURE. THE PORTION OF THE HOUSE WITH THE HIGHEST
 ROOF APPEARS TO EXCEED THE MAXIMUM HEIGHT BY A FOOT OR
 MORE. PLEASE DIMENSION TO DEMONSTRATE COMPLIANCE.
  
 C. THE HEIGHT OF THE CHIMNEY IS NOT MEASURED TO THE
 VERY TOP OF THE CHIMNEY. CHIMNEYS ARE PERMITTED UP TO
 10% ADDITIONAL HEIGHT OVER THE MAXIMUM ALLOWABLE HEIGHT
 IN THE DISTRICT. IN THE SF7 ZONING DISTRICT WITH A 30
 MAXIMUM HEIGHT, THE CHIMNEY WOULD BE PERMITTED AN
 ADDITIONAL 3 FEET IN HEIGHT. THE PLANS SHOWS
 APPROXIMATELY 6 ADDITIONAL FEET. PLEASE REVISE.
  
 GENERAL COMMENTS:
  
 9. THE SF7 ZONING DISTRICT DOES HAVE A MAXIMUM LOT
 COVERAGE AND FAR REQUIREMENT AS INDICATED ON THE PLANS.
  
 10, SEPARATE PERMITS REQUIRED FOR DRIVEWAY, POOL,
 FENCING, AND LANDSCAPING.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-12-11 Cont ID  
Sent By sgraham Date 2015-12-11 Time   Rev Time 0.00
Received By sgraham Date 2016-01-08 Time 08:47 Sent To  
Notes
2016-01-08 08:48:211/8/16 ZONING FAILED
  
 1. SUBMIT TWO UP TO DATE CERTIFIED SURVEYS


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved