Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-15 Cont ID  
Sent By rmcdouga Date 2015-12-15 Time 07:20 Rev Time 0.00
Received By rmcdouga Date 2015-12-15 Time 07:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-08 Cont ID  
Sent By rmcdouga Date 2015-12-08 Time 17:31 Rev Time 0.00
Received By rmcdouga Date 2015-12-08 Time 17:31 Sent To  
Notes
2015-12-08 18:01:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD (
 RICHARD BOYETTE). FBC 107.3.4.1
  
 2) THE NEW DOOR PRODUCT APPROVALS THAT WERE SUBMITTED
 ARE NOT LARGE MISSILE IMPACT RATED. SHOW COMPLIANCE
 WITH FBC-R 301.2.1.2 FOR PROTECTION FROM WINDBORNE
 DEBRIS. SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD ALONG WITH A KEY PLAN AND INSTALLATION SCHEDULE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-15 Cont ID  
Sent By rmcdouga Date 2015-12-15 Time 07:20 Rev Time 0.00
Received By rmcdouga Date 2015-12-14 Time 10:20 Sent To  
Notes
2015-12-14 10:20:16RESUB ROUTED TO RMCDOUGAL