| 2015-12-15 17:50:25 | RE-ROOF SECOND BUILDING REVIEW CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- ACCORDING TO SEC. 1609.4 OF FBC-BUILDING, 5TH |
| | EDITION THIS BUILDING IS LOCATED IN EXPOSURE "D" NOT |
| | "C". ENGINEER DOING THE RAS 117 CALCULATIONS TO REVISE |
| | CALCULATIONS AS REQUIRED.. NOTE: NEED TO SELECT ANOTHER |
| | FLAT ROOF ASSEMBLY THAT MEETS THE CALCULATED REVISED |
| | DESIGN PRESSURES. |
| | |
| | RESPONSE: THE CALCULATIONS WERE REVISED. THERE WERE TWO |
| | NEW ROOF ASSEMBLIES SELECTED FROM FLORIDA PRODUCT |
| | APPROVAL FL2948-R10. ASSEMBLY # C-54 IS A NON-INSULATED |
| | ASSEMBLY. AND, ASSEMBLY #R-23 IS A RECOVER INSULATED |
| | ASSEMBLY. THE FOLLOWING IS REQUIRED. |
| | A) ACCORDING TO NOTE #11 OF FLORIDA PRODUCT APPROVAL |
| | FL2648-R10 SUBMITTED THE EXISTING ROOF SURFACE SHALL BE |
| | FIELD TESTED FOR RECOVER ASSEMBLIES. SEE NOTE #11 FOR |
| | FIELD TEST STANDARD OPTIONS AND PROVIDE 2 SIGNED AND |
| | SEALED COPIES. |
| | |
| | B) PROVIDE SKETCH (2 COPIES) CLEARLY SHOWING AREAS TO |
| | HAVE NON-INSULATED ROOF ASSEMBLY AND AREA TO HAVE |
| | INSULATED ROOF ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- THE BUILDING HEIGHT OF THIS BUILDING IS 110'. |
| | PROVIDE SIGNED AND SEALED DETAILS AND SPECIFICATIONS |
| | FOR THE ATTACHMENT OF THE COPING CAPS AND DRIP EDGE |
| | SHOWING COMPLIANCE WITH THE WIND LOADS OF SEC. 1609 OF |
| | FBC-BUILDING, 5TH EDITION. |
| | RESPONSE: THE DRAWINGS SUBMITTED WERE NOT SIGNED AND |
| | SEALED BY THE ENGINEER. |
| | |
| | 3- SCOPE OF WORK SUBMITTED INCLUDES MECHANICAL UNITS |
| | STANDS, MECHANICAL SHROUDS, CONSTRUCTION OF KNEE WALL, |
| | REPLACE DOOR. THIS SCOPE OF WORK TO BE DONE UNDER |
| | SEPARATE PERMITS. PROVIDE COMPLETE DETAILS/ |
| | SPECIFICATIONS AND PRODUCT APPROVALS UNDER SEPARATE |
| | PERMITS. NOTE: THIS SCOPE OF WORK CAN NOT BE DONE BY |
| | THE ROOFING CONTRACTOR UNLESS THE ROOFING CONTRACTOR |
| | POSSES A LICENSE TO PERFORM SUCH SCOPE OF WORK. SEC. |
| | 489.113 FLORIDA STATUTES. |
| | RESPONSE: THIS ITEM WAS NOT ADDRESSED. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |