Plan Review Details - Permit 15120279
Plan Review Stops For Permit 15120279
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-17 Cont ID  
Sent By jwitmer Date 2016-02-17 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2016-02-17 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-15 Cont ID  
Sent By   Date 2016-01-15 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2016-01-15 Time 07:15 Sent To  
Notes
2016-01-15 07:36:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120279
 ADD: 515 N FLAGLER DR SUITE # 201
 CONT: CUTTING EDGE BUILDING SYSTEMS
 TEL: 561-625-4545
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: FRI. JAN.15/ 2016
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) 2ND REQUEST. THE COVER SHEET 1.1 INDICATES THE PLANS
 WERE DESIGNED TO THE 2010 FBC FAMILY OF CODES. THE
 FIFTH EDITION OF THE 2014 FBC (2014 ED.) WAS ADOPTED
 STATWIDE ON JUNE 30/ 2015. PLEASE UPDATE THE PLANS TO
 THE CURRENT CODE.
  
 2) 2ND REQUEST. SHEET 3.1 THE FLOOR PLAN INDICATES THE
 USE OF TPG FIREGLASS 20 AND METAL FRAME. PLEASE PROVIDE
 COMPLIANCE WITH:
  
 2A)2ND REQUEST. FBC-B 716.2 FIRE-RESISTANCE-RATED
 GLAZING. FIRE-RESISTANCE-RATED GLAZING TESTED AS PART
 OF A FIRE-RESISTANCE-RATED WALL ASSEMBLY IN ACCORDANCE
 WITH ASTM E 119 OR UL 263 AND LABELED IN ACCORDANCE
 WITH SECTION 703.6 SHALL BE PERMITTED IN FIRE DOORS AND
 FIRE WINDOW ASSEMBLIES WHERE TESTED AND INSTALLED IN
 ACCORDANCE WITH THEIR LISTINGS AND SHALL NOT OTHERWISE
 BE REQUIRED TO COMPLY WITH THIS SECTION.
  
 2B) 2ND REQUEST. FBC-B 716.3 MARKING FIRE-RATED GLAZING
 ASSEMBLIES. FIRE-RATED GLAZING ASSEMBLIES SHALL BE
 MARKED IN ACCORDANCE WITH TABLES 716.3, 716.5, AND
 716.6.
  
 2C) 2ND REQUEST. FBC-B 716.3.1 FIRE-RATED GLAZING THAT
 EXCEEDS THE CODE REQUIREMENTS. FIRE-RATED GLAZING
 ASSEMBLIES MARKED AS COMPLYING WITH HOSE STREAM
 REQUIREMENTS (H) SHALL BE PERMITTED IN APPLICATIONS
 THAT DO NOT REQUIRE COMPLIANCE WITH HOSE STREAM
 REQUIREMENTS. FIRE-RATED GLAZING ASSEMBLIES MARKED AS
 COMPLYING WITH TEMPERATURE RISE REQUIREMENTS (T) SHALL
 BE PERMITTED IN APPLICATIONS THAT DO NOT REQUIRE
 COMPLIANCE WITH TEMPERATURE RISE REQUIREMENTS.
 FIRE-RATED GLAZING ASSEMBLIES MARKED WITH RATINGS (XXX)
 THAT EXCEED THE RATINGS REQUIRED BY THIS CODE SHALL BE
 PERMITTED.
  
 2D) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE 226.1 GENERAL. WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. IN ADDITION, WHERE WORK SURFACES ARE PROVIDED
 FOR USE BY OTHER THAN EMPLOYEES, AT LEAST 5 PERCENT
 SHALL COMPLY WITH 902.
  
 2E) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH: 2014
 FBC-ACCESSIBILITY CODE 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2F) NEW COMMENT. TENANT ENTRY DOOR NEEDS TO PROVIDE
 COMPLIANCE WITH THE 2014 FBC-B 404.2.4 MANEUVERING
 CLEARANCES, SEE FIGURE 404.2.4.1(A).
 WHEN THERE IS EXISTING ACCESSIBILIITY ISSUES THE 2014
 FBC-ACCESSIBILITY CODE UNDER SECTION 202.4.1
 DISPROPORTIONATE COST REQUIRES THE TENANT TO SPEND 20%
 OF THE CONTRACT VALUE IN ACCESSIBLE UPGRADES. AN
 ACCESSIBLE ENTRANCE IS THE 1ST ITEM ON THE LIST.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-16 Cont ID  
Sent By jwitmer Date 2015-12-16 Time 13:09 Rev Time 0.00
Received By jwitmer Date 2015-12-16 Time 08:55 Sent To E
Notes
2015-12-16 13:09:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120279
 ADD: 515 N FLAGLER DR SUITE # 201
 CONT: CUTTING EDGE BUILDING SYSTEMS
 TEL: 561-625-4545
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. DEC. 16/ 2015
 ACTION: DENIED
  
 1) THE COVER SHEET 1.1 INDICATES THE PLANS WERE
 DESIGNED TO THE 2010 FBC FAMILY OF CODES. THE FIFTH
 EDITION OF THE 2014 FBC (2014 ED.) WAS ADOPTED STATWIDE
 ON JUNE 30/ 2015. PLEASE UPDATE THE PLANS TO THE
 CURRENT CODE.
  
 2) SHEET 3.1 THE FLOOR PLAN INDICATES THE USE OF TPG
 FIREGLASS 20 AND METAL FRAME. PLEASE PROVIDE COMPLIANCE
 WITH:
  
 2A) FBC-B 716.2 FIRE-RESISTANCE-RATED GLAZING.
 FIRE-RESISTANCE-RATED GLAZING TESTED AS PART OF A
 FIRE-RESISTANCE-RATED WALL ASSEMBLY IN ACCORDANCE WITH
 ASTM E 119 OR UL 263 AND LABELED IN ACCORDANCE WITH
 SECTION 703.6 SHALL BE PERMITTED IN FIRE DOORS AND FIRE
 WINDOW ASSEMBLIES WHERE TESTED AND INSTALLED IN
 ACCORDANCE WITH THEIR LISTINGS AND SHALL NOT OTHERWISE
 BE REQUIRED TO COMPLY WITH THIS SECTION.
  
 2B) FBC-B 716.3 MARKING FIRE-RATED GLAZING ASSEMBLIES.
 FIRE-RATED GLAZING ASSEMBLIES SHALL BE MARKED IN
 ACCORDANCE WITH TABLES 716.3, 716.5, AND 716.6.
  
 2C) FBC-B 716.3.1 FIRE-RATED GLAZING THAT EXCEEDS THE
 CODE REQUIREMENTS. FIRE-RATED GLAZING ASSEMBLIES MARKED
 AS COMPLYING WITH HOSE STREAM REQUIREMENTS (H) SHALL BE
 PERMITTED IN APPLICATIONS THAT DO NOT REQUIRE
 COMPLIANCE WITH HOSE STREAM REQUIREMENTS. FIRE-RATED
 GLAZING ASSEMBLIES MARKED AS COMPLYING WITH TEMPERATURE
 RISE REQUIREMENTS (T) SHALL BE PERMITTED IN
 APPLICATIONS THAT DO NOT REQUIRE COMPLIANCE WITH
 TEMPERATURE RISE REQUIREMENTS. FIRE-RATED GLAZING
 ASSEMBLIES MARKED WITH RATINGS (XXX) THAT EXCEED THE
 RATINGS REQUIRED BY THIS CODE SHALL BE PERMITTED.
  
 2D) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY
 CODE 226.1 GENERAL. WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION,
 WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN
 EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
  
 2E) PLEASE SHOW COMPLIANCE WITH: 2014 FBC-ACCESSIBILITY
 CODE 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-02 Cont ID  
Sent By mvaldes Date 2016-03-02 Time 15:44 Rev Time 0.00
Received By mvaldes Date 2016-03-02 Time 15:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-01-27 Cont ID  
Sent By mvaldes Date 2016-01-27 Time 18:13 Rev Time 0.00
Received By mvaldes Date 2016-01-26 Time 19:14 Sent To  
Notes
2016-01-27 19:13:572ND REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 JOB PERMIT NUMBER: 15120279
 JOB ADDRESS: 515 NORTH FLAGLER DRIVE
 SUITE 201 WEST PALM BEACH FLORIDA
 DATE: JAN 27 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1 PLEASE SITE CURRENT CODE STANDARDS NEC 2011 AND FBC
 5TH EDITION 2014
 2 PROVIDE GFCI PROTECTION FOR COMMERCIAL KITCHENS AND
 SINKS NEC 210.8 B
 ( EITHER ADD TO ELECTRICAL NOTES OR SHOW ON FLOOR
 PLANS. )
 3 ILLUMINATION IS REQUIRED IN WORKING SPACES
 SURROUNDING SERVICE EQUIPMENT NEC 110.26 D ( PLANS SHOW
 NO LIGHTING WERE PANELS ARE LOCATED. )
 4 ADD A NOTE REFERENCING FBC-E SECTION C 405 MANDATORY
 LIGHTING CONTROLS.
 5 FLOOR PLAN LIGHTING ISN?T REFLECTED ON PANEL H
 SCHEDULE ?
 6 PROVIDE ARC FLASH FIELD MARKING ON ELECTRICAL
 EQUIPMENT NEC 110.16
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-06 Cont ID  
Sent By mvaldes Date 2016-01-06 Time 13:08 Rev Time 0.00
Received By mvaldes Date 2016-01-06 Time 13:08 Sent To  
Notes
2016-01-06 13:31:161ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 1- SITE CURRENT CODE STANDARDS NEC 2011 , FBC 2014
 2- NEC 210.8 B2 COMMERCIAL KITCHENS AND SINKS GFCI
 PROTECTED 15/20 AMP OUTLETS.
 3- EXIT LIGHT REQUIRED IN KITCHEN AREA NEC 700.16
 EMERGENCY ILLUMINATION.
 4- ILLUMINATION. ILLUMINATION SHALL BE PROVIDED FOR ALL
 WORKING SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS,
 PANELBOARDS, OR MOTOR CONTROL CENTERS INSTALLED INDOORS
 AND
 SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. NEC
 110.26 D
 5- PLEASE MAKE NOTE OF FBC E SECTION C 405 LIGHTING
 CONTROLS
 6- PLEASE SHOW LUMINAIRE DISCONNECTING MEANS 430.130 G
 AND LUMINAIRE
 SUPPORT NEC 410.36 B
 7- DOESN'T SHOW LIGHTING IN 277/480 PANEL H REFERENCE
 FIXTURE SCHEDULE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-02-18 Cont ID  
Sent By pleduc Date 2016-02-18 Time   Rev Time 0.00
Received By pleduc Date 2016-02-18 Time 10:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-01-08 Cont ID  
Sent By pleduc Date 2016-01-08 Time   Rev Time 0.00
Received By pleduc Date 2016-01-08 Time 11:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-12-10 Cont ID  
Sent By pleduc Date 2015-12-10 Time   Rev Time 0.00
Received By pleduc Date 2015-12-10 Time 13:03 Sent To  
Notes
2015-12-10 15:15:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET 1.1 - AN INCORRECT REFERENCE TO THE FIRE CODE
 IS INDICATED.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 A RE-REVIEW OF THE DESIGN MAY BE NECESSARY TO ENSURE
 COMPLIANCE WITH THE NEWER EDITION OF THE CODE.
  
 2. SHEET 3.1 - TWO OVENS ARE INDICATED. NO REFERENCE IS
 INDICATED AS TO THE TYPE OF COOKING IS INDICATED. ALL
 COOKING EQUIPMENT SHALL COMPLY WITH NFPA 1 CHAPTER 50
 AND NFPA 96.
  
 3. SHEET 3.1 - THE PROPOSED PLAN INDICATES ONE EXIT
 FROM THE OCCUPANCY. PLEASE PROVIDED JUSTIFICATION IN
 COMPLICANCE WITH NFPA 101, CHAPTER 36, 36.2.4.3 AND
 36.2.4.4 OR PROVIDE A SECOND EXIT TO THE OCCUPANCY. THE
 ENTIRE BUILDING OCCUPANCY IS NOT A MALL OR 2ND FLLOR
 CORRIDOR IS NOT MALL PEDESTRIAN WAY.
  
 4. SHEET 3.1 - THE PROPOSED PLAN INDICATES A NEW 1-HOUR
 WALL AT THE REAR OF THE KITCHEN AREA. THIS CREATES A
 NEW SPACE/CORRIDOR. PLEASE PROVIDE A STATEMENT
 INDICATED THAT THIS SHALL SHALL ALSO COMPLY WITH ALL
 APPROPRIATE CODE AND STANDARDS, INCLUDING, BUT NOT
 LIMITED TO, FIRE SPRINKLERS, EXIT AND EMERGECNY
 LIGHTING, EXIT DOOR HARDWARE, ETC.
  
 5. ADDITIONAL COMMNETS MAY BE GENERATED ON RE-SUBMITTAL
 OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-02 Cont ID  
Sent By mvaldes Date 2016-03-02 Time 15:45 Rev Time 0.00
Received By mvaldes Date 2016-02-10 Time 10:15 Sent To  
Notes
2016-02-11 10:15:20B05

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-28 Cont ID  
Sent By cpuell Date 2016-01-27 Time 08:06 Rev Time 0.00
Received By cpuell Date 2016-01-07 Time 14:12 Sent To  
Notes
2016-01-07 14:13:10B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-06 Cont ID  
Sent By cpuell Date 2016-01-06 Time 14:19 Rev Time 0.00
Received By cpuell Date 2015-12-07 Time 11:12 Sent To  
Notes
2015-12-08 11:13:06B07

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-03-07 Cont ID  
Sent By ccole Date 2016-03-07 Time 12:07 Rev Time 0.00
Received By ccole Date 2016-03-07 Time 12:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-02-19 Cont ID  
Sent By ccole Date 2016-02-19 Time 15:15 Rev Time 0.00
Received By ccole Date 2016-02-19 Time 15:15 Sent To  
Notes
2016-02-19 15:35:043RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120279
 2/19/16
  
 1) ADDITIONAL INFORMATION AND CLEAR, LEGIBLE SUBMITTALS
 ARE REQUIRED TO APPROVE THE INSTALLATION OF THE AMANA
 AXP OVEN WITHOUT A TYPE 1 GREASE HOOD. PLEASE REFER TO
 SECTION 507.2.1 TYPE 1 HOODS EXCEPTION: A TYPE I HOOD
 SHALL NOT BE REQUIRED FOR AN ELECTRIC COOKING APPLIANCE
 WHERE AN APPROVED TESTING AGENCY PROVIDES DOCUMENTATION
 THAT THE APPLIANCE EFFLUENT CONTAINS 5 MG/M3 OR LESS OF
 GREASE WHEN TESTED AT AN EXHAUST FLOW RATE OF 500 CFM
 (0.236 M3/S) IN ACCORDANCE WITH SECTION 17 OF UL 710B.
 THE SUBMITTED SPECIFICATIONS ARE NOT PROVIDING EVIDENCE
 OF COMPLIANCE WITH THIS EXCEPTION, AND MOST OF THE
 SUBMITTAL SHEETS HAVE PRINT TO FAINT TO READ AND
 UNACCEPTABLE FOR REVIEW- SEE SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC-14 BUILDING CODE.
 2) ADDITIONAL INFORMATION IS REQUIRED FOR THE MOFFAT
 E25 CONVECTION OVEN TO BE APPROVED FOR INSTALLATION
 WITHOUT A VENT HOOD. THE SUBMITTAL DOES NOT PROVIDE ANY
 VENTING INFORMATION.PLEASE REFER TO SECTION 507.2.1 AND
 THE EXCEPTION PRINTED ABOVE IN COMMENT #1.
 3) PLEASE NOTE THAT WHICHEVER OVENS ARE SELECTED AND
 APPROVED, THE MAKES AND MODEL NUMBERS OF THOSE SHALL BE
 PLACED ON THE KITCHEN EQUIPMENT SCHEDULE, AND THE
 DESIGN PROFESSIONAL SHALL PROVIDE A REVIEW AND APPROVAL
 SIGNATURE ON THE PRODUCT SPEC SHEETS.
 4) THE NOTES AND CALCULATIONS ON SHEET M1.1 FOR THE
 EXHAUST FAN MAKE-UP AIR INDICATE ALL OUTSIDE AIR
 REQUIRED FOR THE DINING ROOM OCCUPANTS WILL BE
 TRANSFERRED AS MAKE-UP AIR FOR THE EXHAUST FAN IN THE
 KITCHEN. IT APEARS THAT THIS WILL CAUSE AN IMBALANCE
 AND ALSO NEGATIVE PRESSURE IN THE DINING ROOM.: PLEASE
 CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-01-13 Cont ID  
Sent By ccole Date 2016-01-13 Time 08:25 Rev Time 0.00
Received By ccole Date 2016-01-13 Time 08:24 Sent To  
Notes
2016-01-13 08:31:112ND REVIEW 2014 MECHANICAL
 PERMIT #15120279
 01/13/16
  
 ALL COMMENTS LISTED BELOW FROM THE 1ST REVIEW HAVE NOT
 BEEN RESPONDED TO EITHER ON THE PLANS, OR IN THE
 NARRATIVES FROM THE DESIGN PROFESSIONALS. PLEASE REVIEW
 AND COMPLY.
  
 1) PROVIDE THE SEQUENCE OF OPERATION FOR THE NEW
 KITCHEN EXHAUST FAN. WILL IT BE MAUTO OR MANUALLY
 CONTROLLED?
 2) INDICATE HOW MAKE-UP AIR WILL BE PROVIDED TO THE NEW
 KITCHEN EXHAUST FAN.
 3) THE OUTDOOR AIR CALCULATIONS ARE NOT IN COMPLIANCE
 WITH TABLE 403.3: DINING ROOMS REQUIRE 7.5 CFM PER
 PERSON AND 0.18 CFM PER SQ.FT. PLEASE CORRECT AND
 PROVIDE AN AIR BALANCE CALCULATION.
 4) PROVIDE AN INSTALLATION DETAIL FOR THE RELOCATED
 HEAT PUMP, AND PROVIDE DETAILS FOR CONDENSATE DISPOSAL
 INCLUDING DISCHARGE LOCATION.
 5) PROVIDE A MIAMI-DADE NOA FOR THE EXHAUST LOUVER.
 6) REFER TO SECTION 501.3.1 AND PROVIDE CLEARANCE
 DISTANCE MEASUREMENTS FOR THE NEW KITCHEN EXHAUST
 TERMINATION.
 7) SUBMIT MANUFACTURER'S CUT SHEETS FOR THE NEW OVENS
 REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. PLEASE
 NOTE GREASE OR HEAT HOODS FOR EXHAUST MAY BE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-15 Cont ID  
Sent By ccole Date 2015-12-15 Time 17:16 Rev Time 0.00
Received By ccole Date 2015-12-15 Time 17:16 Sent To  
Notes
2015-12-15 17:30:321ST REVIEW 2014 MECHANICAL
 PERMIT #15120279
 12/15/15
  
 1) PROVIDE THE SEQUENCE OF OPERATION FOR THE NEW
 KITCHEN EXHAUST FAN. WILL IT BE MAUTO OR MANUALLY
 CONTROLLED?
 2) INDICATE HOW MAKE-UP AIR WILL BE PROVIDED TO THE NEW
 KITCHEN EXHAUST FAN.
 3) THE OUTDOOR AIR CALCULATIONS ARE NOT IN COMPLIANCE
 WITH TABLE 403.3: DINING ROOMS REQUIRE 7.5 CFM PER
 PERSON AND 0.18 CFM PER SQ.FT. PLEASE CORRECT AND
 PROVIDE AN AIR BALANCE CALCULATION.
 4) PROVIDE AN INSTALLATION DETAIL FOR THE RELOCATED
 HEAT PUMP, AND PROVIDE DETAILS FOR CONDENSATE DISPOSAL.
 5) PROVIDE A MIAMI-DADE NOA FOR THE EXHAUST LOUVER.
 6) REFER TO SECTION 501.3.1 AND PROVIDE CLEARANCE
 DISTANCE MEASUREMENTS FOR THE NEW KITCHEN EXHAUST
 TERMINATION.
 7) SUBMIT MANUFACTURER'S CUT SHEETS FOR THE NEW OVENS
 REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. PLEASE
 NOTE GREASE OR HEAT HOODS FOR EXHAUST MAY BE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-02-19 Cont ID  
Sent By gjohnson Date 2016-02-19 Time 17:14 Rev Time 0.00
Received By gjohnson Date 2016-02-19 Time 17:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-01-22 Cont ID  
Sent By gjohnson Date 2016-01-22 Time 13:24 Rev Time 0.00
Received By gjohnson Date 2016-01-22 Time 13:24 Sent To  
Notes
2016-01-22 13:31:36 
 2ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. A GREASE TRAP FOR 3 COMP SINK WILL BE REQUIRED TO
 COMPPLY WITH FBC EXIST.
 SECSECTION 810 PLUMBING
  
 810.1 MINIMUM FIXTURES.
 WHERE THE OCCUPANT LOAD OF THE STORY IS INCREASED BY
 MORE THAN 20 PERCENT, PLUMBING FIXTURES FOR THE STORY
 SHALL BE PROVIDED IN QUANTITIES SPECIFIED IN THE
 FLORIDA BUILDING CODE, PLUMBING BASED ON THE INCREASED
 OCCUPANT LOAD.
 FBC PLUMB. SECTION 1003 INTERCEPTORS AND SEPARATORS
  
 1003.1 WHERE REQUIRED.
 INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO
 PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER
 SUBSTANCES HARMFUL OR HAZARDOUS TO THE PUBLIC SEWER,
 THE PRIVATE SEWAGE SYSTEM OR THE SEWAGE TREATMENT PLANT
 OR PROCESSES
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES; WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. WHERE LACK
 OF SPACE OR OTHER CONSTRAINTS PREVENT THE INSTALLATION
 OR REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE
 GREASE INTERCEPTORS SHALL BE PERMITTED TO BE INSTALLED
 ON OR ABOVE THE FLOOR AND UPSTREAM OF AN EXISTING
 GREASE INTERCEPTOR

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-12 Cont ID  
Sent By gjohnson Date 2015-12-12 Time 07:55 Rev Time 0.00
Received By gjohnson Date 2015-12-12 Time 07:55 Sent To  
Notes
2015-12-12 08:19:251ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.IS MOP SINK EXISTING ? IF IT IS NEW PROVIDE WATER AND
 SANITARY RISER DIAGRAM. PER WPB AMEND. TO FBC SEC
 107.2.1
 2. PROVIDE BACK FLOW PREVENTERS FOR COFFEE MACHINE AND
 ANY OTHER DRINK DISPENSERS . PER FBC PL. SEC 608.16.1
 +608.16.10
 3. THE 15 GAL WATER HEATER APPEARS TO BE TO SMALL TO
 PROVIDE ADEQUATE HOT WATER FOR THE THREE COMPARTMENT
 SINK AND TWO HAND SINKS PLEASE PROVIDE CALCULATIONS
 SHOWING ADEQUATE SUPPLY OF HOT WATER TO MEET POSSIBLE
 DEMAND. PER WPB AMEND TO FBC SEC 107.2.1
 4. SHOW OCCUPANT LOAD FOR ENTIRE FLOOR AND NUMBER OF
 FIXTURES PROVIDED. EPR WPB AMEND TO FBC SEC 107.2.1