Plan Review Details - Permit 15120235
Plan Review Stops For Permit 15120235
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-06-02 Cont ID  
Sent By shill Date 2016-06-02 Time 09:40 Rev Time 0.00
Received By shill Date 2016-06-02 Time 09:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-04-18 Cont ID  
Sent By shill Date 2016-04-18 Time 13:48 Rev Time 0.00
Received By shill Date 2016-04-18 Time 13:48 Sent To  
Notes
2016-04-18 13:49:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE DOCUMENTS SUBMITTED DIGITALLY WERE NOT PROVIDED:
  
 PERMIT APPLICATION, PRODUCT APPROVALS, ESTIMATE, ANY
 OTHER DOCUMENTS REQUESTED IN PREVIOUS PLAN REVIEWS.
  
 A REVIEW WILL BE DONE AFTER A COMPLETE PERMIT SUBMITTAL
 IS PROVIDED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-03-23 Cont ID  
Sent By shill Date 2016-03-23 Time 10:11 Rev Time 0.00
Received By shill Date 2016-03-23 Time 10:11 Sent To  
Notes
2016-03-23 09:36:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO SIGNED, SEALED, DATED ORIGINALS,
 FS471. THE PLAN PROVIDED IS NOT DIGITALLY SIGNED AND
 SEALED; HOW WAS TANER HAMZAWI, PE GOING TO SIGN AND
 SEAL THIS DOCUMENT?
  
 2. A TITLE BLOCK IN ACCORDANCE WITH FAC61G15-23.002 IS
 REQUIRED ON PAGES PREPARED BY TANER HAMZAWI, PE.
  
 3. SEE PREVIOUS LIST REGARDING EXPOSURE CLASSIFICATION
 AND SEE DEFINITION, FBC 5TH EDITION RESIDENTIAL
 301.2.1.4. ENGINEER TO EXPLAIN RATIONALE FOR EXPOSURE
 B.
  
 THE PLAN IN "DRAWINGS" STATES THIS IS EXPOSURE B. THE
 PLAN, DATED 11/23/2015, IN "SUPPORTING DOCUMENTS", IS
 EXPOSURE C. PLAN PAGES BELONG IN THE DRAWINGS FOLDER.
  
 THE PLAN ALSO LACKS DESIGN PRESSURES FOR THE WALL
 COMPONENTS & CLADDING, FBC R 301.
  
 WHY IS THE DATE ON THE PLAN 11/23/15 WHEN THE PLAN
 REVIEW COMMENTS WERE DECEMBER AND MARCH? NO DELTA ON
 THE PLAN INDICATING CHANGES AND VERSION.
  
 4. THE ESTIMATE WAS RECEIVED. WHO WILL BE DOING THE
 LABOR FOR THIS PROJECT? FBC 109.
  
 5. AS DESIGN PRESSURES WERE NOT PROVIDED, THIS HAS NOT
 BEEN REVIEWED. IF MORE THAN ONE INSTALLATION METHOD IS
 INCLUDED IN THE PRODUCT APPROVAL, INDICATE WHICH OPTION
 IS PROPOSED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-01 Cont ID  
Sent By shill Date 2016-03-01 Time 12:16 Rev Time 0.00
Received By shill Date 2016-03-01 Time 12:16 Sent To  
Notes
2016-03-01 12:26:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD AND
 PROFIT, FBC 109. PROVIDE A VERIFIABLE COPY OF THE
 CONTRACT.
  
 2ND REVIEW, NOT ADDRESSED. A COST BREAKDOWN (STICK
 ESTIMATE) MAY ALSO BE REQUIRED.
  
 2. THE DOOR PRODUCT APPROVAL IS EXPIRED AND LACKS THE
 COVER SHEET (WHICH SHOWS THE CODE, STATUS, AND OTHER
 INFORMATION). WWW.FLORIDABUILDING.ORG, FAC9N-3.
  
 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE HARDIPLANK, FAC9N-3, FBC 5TH EDITION 301. REPLACE
 THE ICC EVALUATION REPORT WITH THE FLORIDA STATE
 PRODUCT APPROVAL, INCLUDING THE COVER SHEET.
  
 4. THE FLORIDA STATE PRODUCT APPROVAL SHOULD INCLUDE
 EVALUTION REPORT AND INSTALLATION INSTRUCTIONS. REPLACE
 THE DOCUMENT UPLOADED, HARDIPLANK INSTALLATION
 INSTRUCTIONS, WITH THE INSTALLATION INSTRUCTIONS IN THE
 PRODUCT APPROVAL.
  
 NEW COMMENT:
  
 5. THIS PARCEL IS LOCATED IN EXPOSURE C, REVISE PLAN.
  
 6. TOO MANY DOCUMENTS HAVE BEEN SUBMITTED. SEE PREVIOUS
 LIST, PRODUCT APPROVALS ARE EXPIRED (WRONG CODE).
 PRODUCT APPROVALS HAVE BEEN UPLOADED AS SEVERAL
 DOCUMENTS RATHER THAN ONE DOCUMENT. WHEN RESUBMITTING,
 THE CORRECT DOCUMENT IS TO SUPERSEDE THE DOCUMENT WHICH
 FAILED PLAN REVIEW USING THE SAME NAMING CONVENTION.
 SINCE THIS WAS NOT DONE, IT APPEARS THAT THE OLD
 PRODUCT APPROVALS ARE STILL IN THE FILE, ALONG WITH NEW
 PRODUCT APPROVALS.
  
 ONE OF THE NEW PRODUCT APPROVAL DOCUMENTS UPLOADED
 (FL13192) REFERS TO FBC 2010. IT APPEARS THAT
 ADDITIONAL EXPIRED DOCUMENTS HAVE BEEN UPLOADED.
  
 IF APPLICANT IS UNABLE TO PROPERLY SUBMIT DIGITALLY, IT
 IS RECOMMENDED THAT THIS BE SUBMITTED AS A PAPER
 SUBMITTAL.
  
 IF APPLICANT WOULD LIKE TO CONTINUE WITH THE DIGITAL
 PROCESS, ENSURE THAT EACH PRODUCT APPROVAL IS ONE
 UPLOADED DOCUMENT AND IS CURRENT. EXPIRED DOCUMENTS ARE
 TO BE REMOVED. IT APPEARS THAT, ALTHOUGH ONLY TWO
 PRODUCT APPROVALS ARE REQUIRED (SO THERE SHOULD BE TWO
 DOCUMENTS), THERE ARE EIGHT PRODUCT APPROVAL UPLOADS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-22 Cont ID  
Sent By shill Date 2015-12-22 Time 09:56 Rev Time 0.00
Received By shill Date 2015-12-22 Time 09:56 Sent To  
Notes
2015-12-22 10:00:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD AND
 PROFIT, FBC 109. PROVIDE A VERIFIABLE COPY OF THE
 CONTRACT.
  
 2. THE DOOR PRODUCT APPROVAL IS EXPIRED AND LACKS THE
 COVER SHEET (WHICH SHOWS THE CODE, STATUS, AND OTHER
 INFORMATION). WWW.FLORIDABUILDING.ORG, FAC9N-3.
  
 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE HARDIPLANK, FAC9N-3, FBC 5TH EDITION 301. REPLACE
 THE ICC EVALUATION REPORT WITH THE FLORIDA STATE
 PRODUCT APPROVAL, INCLUDING THE COVER SHEET.
  
 4. THE FLORIDA STATE PRODUCT APPROVAL SHOULD INCLUDE
 EVALUTION REPORT AND INSTALLATION INSTRUCTIONS. REPLACE
 THE DOCUMENT UPLOADED, HARDIPLANK INSTALLATION
 INSTRUCTIONS, WITH THE INSTALLATION INSTRUCTIONS IN THE
 PRODUCT APPROVAL.
  
  

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2016-06-01 Cont ID  
Sent By fmittner Date 2016-06-01 Time 13:58 Rev Time 0.00
Received By fmittner Date 2016-06-01 Time 13:58 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2016-04-11 Cont ID  
Sent By fmittner Date 2016-04-11 Time 12:28 Rev Time 0.00
Received By fmittner Date 2016-04-11 Time 12:28 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2016-03-18 Cont ID  
Sent By fmittner Date 2016-03-18 Time 16:05 Rev Time 0.00
Received By fmittner Date 2016-03-18 Time 16:05 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-02-25 Cont ID  
Sent By fmittner Date 2016-02-25 Time 11:39 Rev Time 0.00
Received By fmittner Date 2016-02-25 Time 11:39 Sent To B
Notes
2016-02-25 11:40:39APPROVED BY HPB, NO STAMP NEEDED VIA SK

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-12-28 Cont ID  
Sent By fmittner Date 2015-12-28 Time 14:53 Rev Time 0.00
Received By fmittner Date 2015-12-28 Time 14:53 Sent To  
Notes
2015-12-28 14:54:17HARDI BOARD NOT PERMITTED IN HSITORIC DISTRICTS. FHM
 E-MAIL CONTRACTOR.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-06-02 Cont ID  
Sent By shill Date 2016-06-02 Time 09:40 Rev Time 0.00
Received By shill Date 2016-05-25 Time 13:03 Sent To  
Notes
2016-05-25 13:03:44RESUB ROUTED TO FMITTNER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-04-18 Cont ID  
Sent By shill Date 2016-04-18 Time 13:50 Rev Time 0.00
Received By shill Date 2016-04-04 Time 11:18 Sent To  
Notes
2016-04-04 11:18:33RESUB ROUTED TO HISTORIC VIA ZONING

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-23 Cont ID  
Sent By shill Date 2016-03-23 Time 10:16 Rev Time 0.00
Received By shill Date 2016-03-16 Time 07:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-01 Cont ID  
Sent By shill Date 2016-03-01 Time 12:27 Rev Time 0.00
Received By shill Date 2016-02-25 Time 08:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-11 Cont ID  
Sent By lmarchan Date 2016-01-11 Time 13:06 Rev Time 0.00
Received By lmarchan Date 2015-12-07 Time 15:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2016-06-02 Cont ID  
Sent By cpuell Date 2016-06-02 Time 13:46 Rev Time 0.00
Received By cpuell Date 2016-06-02 Time 13:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-03-23 Cont ID  
Sent By shill Date 2016-03-23 Time 10:11 Rev Time 0.00
Received By shill Date 2016-03-23 Time 10:11 Sent To  
Notes
2016-03-23 10:15:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. HOW WILL THE DIGITAL SIGNATURE BE PROVIDED? THE
 PLANS ARE NOT DIGITALLY SIGNED AND SEALED. IF PAPER
 DOCUMENTS ARE PROVIDED FOR THE DIGITAL SIGNATURE,
 PLEASE BE AWARE THAT THIS WILL REQUIRE A PLAN REVIEW
 WHICH MAY TAKE UP TO A WEEK.
  
 2. THE PLANS PREPARED BY THE ENGINEER LACK THE TITLE
 BLOCK REQUIRED BY FS 471.
  