Plan Review Details - Permit 15120220
Plan Review Stops For Permit 15120220
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-10 Cont ID  
Sent By ccole Date 2015-12-10 Time 17:30 Rev Time 0.00
Received By ccole Date 2015-12-09 Time 09:58 Sent To  
Notes
2015-12-10 09:58:22RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-07 Cont ID  
Sent By ccole Date 2015-12-07 Time 15:33 Rev Time 0.00
Received By ccole Date 2015-12-04 Time 10:03 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-10 Cont ID  
Sent By ccole Date 2015-12-10 Time 17:30 Rev Time 0.00
Received By ccole Date 2015-12-10 Time 17:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-07 Cont ID  
Sent By ccole Date 2015-12-07 Time 15:33 Rev Time 0.00
Received By ccole Date 2015-12-07 Time 14:17 Sent To  
Notes
2015-12-07 14:44:211ST REVIEW 2014 MECHANICAL
 PERMIT #15120220
 12/7/15
  
 1) THERE ARE SEVERAL NEW LINEAR RETURN GRILLS, AND SOME
 SUPPLY DIFFUSERS THAT DO NOT HAVE CFM QUANTITIES
 LABELED. I HAVE HIGHLIGHTED THESE LOCATIONS. PLEASE
 REVIEW AND REVISE.
 2) PLEASE REVISE THE AIR DEVICE SCHEDULE ON M0.1 TO
 INCLUDE THE THE LINEAR GRILLS.
 3) THE PLAN APPEARS TO INDICATE UNBALANCED AIR FLOWS AT
 RECEPTION ROOM 100 ( 185 CFM'S SUPPLY AIR FROM AHU-4
 WITH 370 CFM'S RETURN AIR TO AHU-3), AND THE OPERATIONS
 ROOM (600 CFM'S OF SUPPLY AIR FROM AHU-4 NOT BEING
 RETURN TO THE UNIT).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  