| 2015-12-07 16:01:17 | 1ST REVIEW 2014 MECHANICAL |
| | PERMIT #15120216 |
| | 12/7/15 |
| | |
| | 1) THERE IS CURRENTLY A PERMIT APPLICATION AND PLANS |
| | SUBMITTED FOR A CHANGE OF OCCUPANCY AT THIS LOCATION |
| | (428 AVON RD- PERMIT #15100233). I HAVE FAILED THE |
| | SUBMITTED PLAN AND HAVE WRITTEN COMMENTS REQUESTING |
| | ENERGY CALCULATIONS AND VENTILATION CALCULATIONS, |
| | HOWEVER NO AC PLANS WERE SUBMITTED AT THAT TIME. |
| | CONCERNING THIS NEW SUBMITTAL, WHICH HAS BEEN PROCESSED |
| | AS A REVISION TO AN AC CHANGEOUT PERMIT ISSUED AT THE |
| | SAME LOCATION (PERMIT #15100285), PLEASE REVIEW THE |
| | FOLLOWING COMMENTS: |
| | A) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH |
| | SECTION C101.4.5 FBC-14 ENERGY CONSERVATION. |
| | B) PROVIDE THE CFM QUANITIES AT EACH SUPPLY DIFFUSER. |
| | C) PROVIDE THE SIZE OF THE RETURN AIR PLENUM, AND |
| | INDICATE THE TYPE OF DUCTWORK TO BE INSTALLED- SECTION |
| | 603 |
| | D) PROVIDE DUCT HANGING AND CONNECTION DETAILS- SECTION |
| | 603 |
| | E) IDENTIFY ALL ROOMS AND SPACES ON THE PLANS AND |
| | PROVIDE RETURN AIR WHERE REQUIRED- SEE SECTION 601.5. |
| | F) PROVIDE AIR HANDLER INSTALLATION DETAILS. |
| | G) PROVIDE AN AIR DEVICE SCHEDULE. |
| | H) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR |
| | SYSTEM AS REQUIRED BY SECTION 606.2.1. |
| | I) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR |
| | INSTALLING THE EXTERIOR CONDENSER- SECTION 301.15. |
| | PLEASE NOTE THE SUBMITTAL FOR THE ALUMSTAND HAS |
| | ILLEGIBLE PRINT THAT IS TOO SMALL TO READ AND SCAN INTO |
| | THE BUILDING DEPARTMENT RECORDS. |
| | J) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL |
| | PLANS- SECTION 307. |
| | 2) PLEASE NOTE THAT AN ELECTRICAL PLAN AND SUB-PERMIT |
| | WILL BE REQUIRED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |