Plan Review Details - Permit 15120203
Plan Review Stops For Permit 15120203
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-15 Cont ID  
Sent By jwitmer Date 2015-12-15 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2015-12-15 Time 06:29 Sent To  
Notes
2015-12-15 07:41:53BUILDING PLAN REVIEW
 W. P. B. MASTER: 14071105
 REVISION: 15120203
 ADD: 1517 CAMERON SAMUEL LN.
 CONT: KAST
 TEL: 561-345-4994
 E-MAIL: ?????????????
  
 2010 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: TUES. DEC. 15/2015
 ACTION: DENIED
  
 1) CABANA.THE COVERSHEET SHEET A-1 INDICATES THIS
 STRUCTURE WAS DESIGNED TO THE 2014 FBC-B, NOTE THIS WAS
 SUBMITTED AS A REVISION TO THE MASTER. FOR IT TO BE A
 REVISION IT HAS TO HAVE SHEETS ALREADY ON FILE STAMPED
 AND APPROVED. THIS IS NEW WORK AND SHOULD BE UNDER
 SEPERATE PERMIT AND ASSOCIATED FEES. SUBMIT ON THE NEXT
 REVIEW A PERMIT APPLICATION AND ASSOCIATED FEES. THIS
 TRACKING NUMBER CAN BE MADE FROM A REVISION INTO A
 PERMIT. W P B ADMINISTRATIVE CODE 108.2 .
  
 2) CABANA.SHEET A-1 IN INK HAND WRITTEN NOTE THAT A
 ALTERNANTE FOUNDATION FOR CABANA # 1. NO INFORMATION AS
 TO WHO HAS PUT NOTE ON PLANS. PLANS ARE COPRIGHTED ONLY
 THE DESIGNER OF RECORD CAN PUT INK NOTES ON PLANS, THEY
 NEED TO INITIAL AND DATE THE CHANGE. SHEET A1 THE LAST
 REVISION WAS REVISION # 1 DATED 9-14-15.
 FL ADMIN CODE 61G16.003 ARCHITECTS.
  
 2) CABANA. SHEET A-2.0 SHOWS EXTERIOR SLIDING DOORS,
 LOUVERS AND ROOFING PRODUCTS PLEASE PROVIDE COMPLIANCE
 WITH :
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) PANEL WALLS: WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 3) CABANA.107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. 107.1 GENERAL.
  
 4) CABANA.NOTE THERE IS 2 SETS OF S1 PLANS WITH DETAIL
 1/S-1 BEING DIFFERENT ON BOTH SHEETS. AGAIN THE DETAIL
 THAT SHOWS STEEL HELICAL PILES HAS HAND WRITTEN NOTES,
 NOT SIGNED NOR DATED BY THE ENGINEER OF RECORD.
 61G15-23.001.
  
 5) PLEASE PROVIDE A DETAIL OF AN ACCISSIBLE ENTRANCE
 FOR THE CABANAS FOR THE SLIDING GLASS DOOR TRACK, HOW
 HIGH WILL THE TRACK BE? SHEET A-2 DOES NOT PROVIDE A
 DETAIL SHOWING CODE COMPLIANCE? 2014 FBC-B
 ACCESSIBILITY CODE 404.2.5. THRESHOLDS VERSES
 ACCESSIBLE ENTRANCE.
  
 6) PLEASE SUBMIT GEOTECHNICAL REPORT IN REGAURDS TO THE
 INSTALATION OF THE HELICAL PILE, WHY THE ONE CABANA,
 AND NOT THE OTHERS, QUESTIONABLE SOILS. FBC-B 1803.5.2.
  
 7) RESTROOMS. RESTROOMS WERE PERMITED UNDER PERMIT
 13090634 SITE AMENITIES:
 5.1 POOL RESTROOMS
 5.2 TOWER FEATURE
 5.3 GATE HOUSE
 5.4 DUMPSTER ENCLOSURE
 5.5 MAIL KIOSK.
 THIS PERMIT WAS CLOSED ON 6/16/2014.
 POOL RESTROOMS WILL REQUIRE A SEPEERATE PERMIT FOR
 TRACKING OF INSPECTIONS AND FOR RECORD KEEPING
 PURPOSES. SEPERATE FEES AND REVIEWS WILL BE ASSOCIATED
 WITH THIS PERMIT. NOTE ON THE NEXT SUBMISSION PLEASE
 SUBMIT A PERMIT APPLICATION, AND HAVE A NEW TRACKING
 NUMBER ASSIGNED TO THE POOL RESTROOMS.
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES, 107.2.1.4 QUALITY OF BUILDING PLANS/ RECORD
 RETENTION.
  
 8) POOL RESTROOMS PLEASE PROVIDE PRODUCT APPROVALS FOR
 RESTROOMS. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 31)(A) EXTERIOR DOORS. SWING AND ROLL UP
 (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 9) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 10) NEITHER A1 OR A-3 SHOW COMPLIANCE WITH 2014 FBC-B
 1209.2 ATTIC ACCESS.
  
 11) SHEET A-3 RESTROOM GRAB BARS DOES NOT SHOW THE
 HEIGHT OF THE BAR. PLEASE SHOE COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE 609.4. 33-35 INCHES TO THE TOP
 OF THE GRASPABLE SURFACE.
  
 12) DISCREPANACY IN PLANS SHEET S1 VERSES S2. SHEET S1
 NOTE # 13 INDICATES AN ALLOWABLE MINIMUM SAFE BEARING
 VALUE OF 2,000 SPF WHERE AS S2 FOUNDATION NOTES A
 MINIMUM SAFE BEARING VALUE OF 2,500 PSF FROM GEO REPORT
 FROM D&N. 107.2.1.3.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-27 Cont ID  
Sent By albarran Date 2016-01-27 Time 11:56 Rev Time 0.00
Received By rlecky Date 2016-01-27 Time 11:03 Sent To  
Notes
2016-01-27 11:57:0915120203
 1517 CAMERON SAMUEL LN.
 POOL CABANA
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16, 110.22
 PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES
 IN CABANA. NEC 210.8
 PROVIDE A INTERSYSTEM BONDING BAR AT EACH CABANA
 ELECTRICAL SERVICE. NEC 250 .94
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-09 Cont ID  
Sent By pleduc Date 2015-12-09 Time   Rev Time 0.00
Received By pleduc Date 2015-12-09 Time 16:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-27 Cont ID  
Sent By rlecky Date 2016-01-27 Time 12:20 Rev Time 0.00
Received By rlecky Date 2015-12-04 Time 10:08 Sent To  
Notes
2016-02-18 14:27:06C04 - TRAVELLING WITH 16020687 & 16020689
2015-12-07 10:08:25C13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-16 Cont ID  
Sent By hmoser Date 2015-12-16 Time 08:10 Rev Time 0.00
Received By ccole Date 2015-12-16 Time 08:10 Sent To  
Notes
2015-12-16 08:30:121ST REVIEW 2014 MECHANICAL
 PERMIT #15120203
 12/16/15
  
 1) SHEET M-1: THE DRAWING INDICATES TWO VEHICLES PARKED
 IN THE STORAGE BUILDING: A) IDENTIFY WHAT TYPE OF
 VEHICLES ARE BEING PARKED THERE, AND WHAT TYPE OF FUEL
 IS USED TO POWER THEM. B) PLEASE REVIEW SECTIONS 404.1-
 404.3 AND REVISE THE PLANS AS REQUIRED.
 2) PROVIDE MECHANICAL PLANS FOR THE CABANA BUILDINGS
 #1,. 2, & 3. INDICATE HOW MINIMUM VENTILATION WILL BE
 PROVIDED FOR THE BUILDINGS PER SECTION 401.2- NATURAL
 OR MECHANICAL MEANS, AND PROVIDE CALCULATIONS.
 3) REFER TO SECTION 309.1 AND PROVIDE DETAILS AND
 SPECIFICATIONS FOR THE REQUIRED SPACE HEATING SYSTEMS
 IN THE CABANAS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-12 Cont ID  
Sent By tlarge Date 2015-12-12 Time 06:33 Rev Time 0.00
Received By gjohnson Date 2015-12-12 Time 06:33 Sent To  
Notes
2015-12-12 06:49:081ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1.SHEET C8.1 SHOW SIZING CALCULATIONS FOOR DECK DRAINS.
 PER WPB AMEND. SEC 107.2.1
 2.P1 THE SANITARY PLAN DOES NOT MATCH THE RISER DIAGRAM
 PLEASE CORRECT .PER WPB AMEND. TO FBC SEC 107.2.1
 3.SHEET A-3.0 ACCESSORY SCHEDULE G BAR 1+2 NOT CORRECT
 PER FBC ACC SCE 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
 4 SHEET A- 3.0 SHOW THE CENTERLINE OF THE WATER CLOSET
 SHALL BE 16 INCHES (405 MM) MINIMUM TO 18 INCHES (455
 MM) MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC. SEC 604.2

Review Stop Z ZONING
Rev No 1 Status P Date 2016-01-08 Cont ID  
Sent By ajones Date 2016-01-08 Time 15:29 Rev Time 0.00
Received By ajones Date 2016-01-08 Time 15:29 Sent To  
Notes
***NONE***