Plan Review Details - Permit 15120183
Plan Review Stops For Permit 15120183
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-01-25 Cont ID  
Sent By aclange Date 2016-01-25 Time 17:28 Rev Time 0.00
Received By aclange Date 2016-01-25 Time 17:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-29 Cont ID  
Sent By aclange Date 2015-12-29 Time 17:10 Rev Time 0.00
Received By aclange Date 2015-12-29 Time 17:10 Sent To  
Notes
2015-12-29 17:16:09****CORRECTIONS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 PLEASE PROVIDE THE FOLLOWING ADDITIONAL INFORMATION FOR
 REVIEW.
  
 1. SIGNED AND SEALED ENGINEERED DOCUMENTS.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 2. FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN
 LOADS/DESIGN PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 3. SHOW SIZE AND LENGTH OF STUDS USED. PLEASE INCLUDE
 ATTACHMENT METHOD TO CONCRETE.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-25 Cont ID  
Sent By aclange Date 2016-01-25 Time 17:28 Rev Time 0.00
Received By aclange Date 2016-01-22 Time 09:33 Sent To  
Notes
2016-01-25 09:33:15RESUB ROUTED TO ACLANGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-29 Cont ID  
Sent By aclange Date 2015-12-29 Time 17:16 Rev Time 0.00
Received By aclange Date 2015-12-03 Time 16:10 Sent To  
Notes
2015-12-15 18:26:56MISC 2 BOX.
2015-12-03 16:10:18ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2015-12-15 Cont ID  
Sent By aaponte Date 2015-12-15 Time 18:25 Rev Time 0.00
Received By aaponte Date 2015-12-15 Time 18:25 Sent To  
Notes
2015-12-15 18:26:44PROVISO: THE TOTAL VERTICAL DIMENSION OF THE 3 SIGN
 LINES COMBINES SHALL NOT EXCEED 36".