Plan Review Details - Permit 15120139
Plan Review Stops For Permit 15120139
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-01-08 Cont ID  
Sent By cthroop Date 2016-01-08 Time 13:56 Rev Time 0.00
Received By cthroop Date 2016-01-08 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-05 Cont ID  
Sent By cthroop Date 2016-01-05 Time 09:43 Rev Time 0.00
Received By cthroop Date 2016-01-05 Time 09:42 Sent To E
Notes
2016-01-05 09:50:08CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE DETAILED PLAN SHOWING LOCATION OF WORK SIGNED
 BY DESIGNER.
  
 PURSUANT TO FBC 107.1, AND FS 481.229 (1) (C), AS THIS
 DESIGN EXCEEDS $25,000.00 IN VALUE, THE DESIGN MUST BE
 PREPARED BY A PROFESSIONAL LICENSED PURSUANT TO FS 481.
 SEE BELOW:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-20 Cont ID  
Sent By mvaldes Date 2016-01-20 Time 16:33 Rev Time 0.00
Received By mvaldes Date 2016-01-20 Time 16:32 Sent To  
Notes
2016-01-20 16:38:13FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 PROVISO : SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE
 SECTIONS 314 AND 315

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-06 Cont ID  
Sent By mvaldes Date 2016-01-06 Time 18:00 Rev Time 0.00
Received By mvaldes Date 2016-01-06 Time 18:00 Sent To  
Notes
2016-01-06 18:03:061ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-07 Cont ID  
Sent By lmarchan Date 2016-01-07 Time 08:01 Rev Time 0.00
Received By lmarchan Date 2015-12-03 Time 13:16 Sent To  
Notes
2015-12-03 13:17:10R05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-01-08 Cont ID  
Sent By skennedy Date 2016-01-08 Time 13:50 Rev Time 0.00
Received By skennedy Date 2016-01-08 Time 13:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-21 Cont ID  
Sent By hmoser Date 2015-12-21 Time 13:37 Rev Time 0.00
Received By hmoser Date 2015-12-21 Time 13:24 Sent To  
Notes
2015-12-21 13:37:31PLAN DENIED.
  
 NO MECHANICAL PLAN OR ENERGY CALCULATIONS SUBMITTED
 SECTION 107 2014 FBC
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-12-07 Cont ID  
Sent By gjohnson Date 2015-12-07 Time 13:10 Rev Time 0.00
Received By gjohnson Date 2015-12-07 Time 13:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2015-12-11 Cont ID  
Sent By   Date 2015-12-11 Time   Rev Time  
Received By   Date 2015-12-11 Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved