| 2016-01-07 14:25:16 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1. NEC 215.5, PROVIDE A SITE SPECIFIC RISER DIAGRAM |
| | SHOWING FEEDER DETAILS INCLUDING CONDUCTOR SIZING AND |
| | INSULATION TYPE. |
| | 2. NEC 408.4(B), INDICATE THE LOCATION OF THE SOURCE OF |
| | POWER. IDENTIFY IF FROM THE RESIDENCE OR FROM A COMMON |
| | PANELBOARD AT THE DOCK. |
| | 3. NEC 408.4(A), SHOW CIRCUIT DIRECTORY AND CLEARLY |
| | IDENTIFY THE RESPECTIVE CIRCUIT. |
| | 4. INDICATE DISTANCE FROM PANEL TO MOTORS FOR VOLTAGE |
| | DROP CONSIDERATIONS. PER FBC-E NO MORE THAN 3% VOLTAGE |
| | DROP PERMITTED. |
| | 5. A 15-20 AMP 120 VAC, GFI PROTECTED WP OUTLET |
| | REQUIRED WITHIN CLOSE PROXIMITY OF THE LIFT. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |