Plan Review Details - Permit 15120122
Plan Review Stops For Permit 15120122
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-05 Cont ID  
Sent By vperez Date 2016-02-05 Time 10:27 Rev Time 0.00
Received By vperez Date 2016-02-05 Time 10:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-30 Cont ID  
Sent By albarran Date 2015-12-30 Time 17:48 Rev Time 0.00
Received By albarran Date 2015-12-30 Time 16:33 Sent To  
Notes
2015-12-30 17:56:18THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. THE SCOPE OF WORK AS DESCRIBED ON THE PLANS DOES NOT
 MATCH THE WORK REFLECTED ON THE PLANS.
 2. THE DEVICE COUNT FOR THE NEW WORK ON THE RISER
 DIAGRAM DIFFERS FROM THAT ON THE FLOOR PLAN AND SCOPE
 OF WORK.
 3. THE ACCOMPANYING SALES AGREEMENT DOES NOT DESCRIBE
 THE SCOPE OF WORK EITHER.
 4. IT IS YOUR RESPONSIBILITY TO ASSEMBLE THE PLANS FOR
 SUBMITTAL.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-01-25 Cont ID  
Sent By pleduc Date 2016-01-25 Time   Rev Time 0.00
Received By pleduc Date 2016-01-25 Time 15:46 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-10 Cont ID  
Sent By GJT Date 2015-12-10 Time   Rev Time  
Received By   Date 2015-12-10 Time   Sent To E
Notes
2015-12-10 08:33:3912/10/15 - 1. PASSED WITH PROVISO: ENSURE THAT ADEQUATE
 NOTIFICATION IS PROVIDED IN ALL AREAS INCLUDING
 HALLWAYS. 2. DUCT DETECTORS MUST INITIATE GENERAL
 ALARM.
 GJT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-05 Cont ID  
Sent By vperez Date 2016-02-05 Time 10:30 Rev Time 0.00
Received By vperez Date 2016-02-05 Time 10:30 Sent To  
Notes
2016-02-05 10:31:07SENT TO CAROLYN/LAURA OFFICE
2016-01-19 11:47:11RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-30 Cont ID  
Sent By albarran Date 2015-12-30 Time 17:57 Rev Time 0.00
Received By albarran Date 2015-12-02 Time 11:24 Sent To  
Notes
2015-12-30 17:58:5812/30/15 FAILED ELECTRICAL REVIEW AS NOTED. NOTIFIED
 CONTRACTOR VIA EMAIL. SENT TO SMALL DENIED BIN "T". MA
2015-12-03 11:24:58ROUTED TO FIRE INBOX