Plan Review Details - Permit 15120121
Plan Review Stops For Permit 15120121
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-28 Cont ID  
Sent By albarran Date 2015-12-28 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2015-12-28 Time 07:03 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-07 Cont ID  
Sent By jwitmer Date 2015-12-07 Time 11:28 Rev Time 0.00
Received By jwitmer Date 2015-12-07 Time 10:44 Sent To  
Notes
2015-12-07 11:28:28BUILDING PLAN REVIEW
 W. P. B. REVISION: 15120121
 W. P. B. PERMIT: 15030301
 ADD: 3805 S OLIVE AVE.
 CONT: DELTA MG
 TEL: ( 561)239-4947
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 07/ 2015
 ACTION: DENIED
  
 1) SHEET E1:
 1A) SHEET E1 SHOWS A 2 HOUR FIRE RATED WALL U. L. #
 U412 DETAIL. PLEASE NOTE THERE ARE NO WALL
 IDENTIFICATION TAGS ON EITHER THE ARCHITECTURAL NOR
 ELECTRICAL SHEETS IDENTIFYING WHICH WALLS ARE TO BE
 RATED 2 HOURS. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) SHEET E1 SHOWS A BLOW OUT PATCH DETAIL AND HEADING
 STATING FIRE RATING DETAILS. PLEASE SEE SECTION 714.2
 OF THE 2010 FBC-B. INSTALATION. FIRE-RESISTANT JOINT
 SYSTEMS SHALL BE SECURILY INSTALLED IN OR ON THE JOINT
 FOR ITS ENTIRE LENGTH SO AS NOT TO DISLODGE, LOOSEN OR
 OTHERWISE IMPAIR ITS ABILITY TO ACCOMODATE EXPECTED
 BUILDING MOVEMENTS AND TO RESIST THE PASSAGE OF FIRE
 AND HOT GASES. 714.3 FIRE TEST CRITERIA. ASTM E 1966 OR
 UL 2079.
  
 1C) DISCREPANCY IN PLANS, SHEET E1 DETAIL LABELED
 TENANT SEPERATION WALL FTG, BUT WHAT IS SHOWN IS A
 EXTERIOR WALL DETAIL, PLEASE PROVIDE A CORRECTED DETAIL
 FOR A TENANT SEPERATION WALL OR RELABEL THE EXTERIOR
 WALL DETAIL. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2016-03-23 Cont ID  
Sent By mmanhong Date 2016-03-23 Time 17:13 Rev Time 0.00
Received By albarran Date 2016-03-23 Time 17:12 Sent To  
Notes
2016-03-23 17:15:59ELECTRICAL CONTRACTOR JACKIE GUTHART OF GUTHART
 ELECTRIC STOPPED BY THE OFFICE TO DISCUSS THE PERMIT.
 APPARENTLY THIS PERMIT WAS FOR SOMETHING OTHER THAN AN
 ELECTRICAL REVISION AND NO ELECTRICAL WORK WAS WITHIN
 ITS SCOPE.
 MA

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-28 Cont ID  
Sent By albarran Date 2015-12-28 Time 13:28 Rev Time 0.00
Received By albarran Date 2015-12-28 Time 13:02 Sent To I
Notes
2015-12-28 13:32:37THE DELAY IN HEARING BACK FROM THE GC CAUSED ME TO
 COMMENCE MY 2ND ELECTRICAL REVIEW OF THIS APPLICATION.
 AS A RESULT I NOTICED THAT THE NEW E1 IS NO DIFFERENT
 THAN THE PREVIOUS. THEREFORE NOT ONLY IS THERE NO
 NARRATIVE, THERE IS NO CHANGE TO THE ELECTRICAL PAGE.
 REVISE THE ELECTRICAL SHEET ACCORDING TO THE REQUIRED
 CORRECTIONS MENTION AT THE FIRST REVIEW.
2015-12-28 13:12:34CONTACTED THE GC ON THE LACK OF THE RESPONSE LETTER. HE
 WILL CONTACT THE ARCHITECT AND GET BACK TO ME. IN THE
 MEANTIME THIS IS STILL OPEN AND ON MY DESK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-03 Cont ID  
Sent By albarran Date 2015-12-03 Time 14:15 Rev Time 0.00
Received By albarran Date 2015-12-03 Time 13:19 Sent To B
Notes
2015-12-03 14:15:55THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. YOU SHALL MARK THE LOCATION OF ALL ELECTRICAL PANELS
 ON THE FLOOR PLAN.
 2. NEC 210.63 A 125 V. SINGLE PHASE 15 OR 20 AMP
 RECEPTACLE SHALL BE INSTALLED WITHIN 25? OF THE CU?S AT
 AN ACCESSIBLE LOCATION TO SERVICE THE HVAC. (EACH UNIT
 SHALL HAVE THEIR RESPECTIVE SERVICE OUTLET POWERED FROM
 THE SOURCE IT SERVES.)
 3. MARK THE LOCATION OF THE WASHER ON THE FLOOR PLANS.
 4. NEC 210.52(E)(2) EACH GRADE LEVEL UNIT SHALL HAVE AN
 EXTERIOR GFCI OUTLET.
 5. NEC 210.52(C)(1) IF CORNER AREA BEHIND KITCHEN SINK
 IS GREATER THAN 18?, AN OUTLET WILL BE REQUIRED.
 6. NEC 250.94 AN INTER-SYSTEM BONDING TERMINAL SHALL BE
 INSTALLED AT THE SERVICE POINT FOR COMMON GROUNDING OF
 AUXILIARY SERVICES.
 7. MARK DESIGNATED CIRCUIT INFORMATION OF FLOOR PLAN
 OUTLETS.
 8. NEC 314.27 EVERY LUMINAIRE OUTLET INSTALLED IN THE
 CEILING SHALL BE LISTED TO SUPPORT 50#?S AND PADDLE FAN
 OUTLETS SHALL BE LISTED FOR THE APPLICATION.
 9. NEC 406.12 ALL NON-LOCKING TYPE 15 & 20 AMP 125 V.
 RECEPTACLES IN DWELLING UNITS SHALL BE LISTED AS TAMPER
 RESISTANT.
 10. NEC 406.9(B) ALL 15 & 20 AMP NON LOCKING TYPE
 RECEPTACLES INSTALLED OUTDOORS/WET LOCATIONS SHALL BE
 LISTED ?WR? WEATHER RESISTANT.
 11. FBC-E SECTION R402.4.4 RECESSED LUMINARIES
 INSTALLED WITHIN THE BLDG. THERMAL ENVELOPE SHALL BE IC
 RATED AND SEALED TO LIMIT THE LEAKAGE OF AIR BETWEEN
 THE CONDITIONED AND UNCONDITIONED SPACE.
 12. FBC-R SECTION R303.7 YOU SHALL PROVIDE ILLUMINATION
 FOR THE STAIRWAYS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-28 Cont ID  
Sent By albarran Date 2015-12-28 Time 13:35 Rev Time 0.00
Received By albarran Date 2015-12-23 Time 15:38 Sent To  
Notes
2015-12-28 13:35:5212/28/15 FAILED 2ND ELECTRICAL REVIEW AS NOTED. IN LIEU
 OF A MISSING EMAIL, GC NOTIFIED VIA PHONE CALL. SENT TO
 SMALL DENIED BIN "D". MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-07 Cont ID  
Sent By jwitmer Date 2015-12-07 Time 11:28 Rev Time 0.00
Received By jwitmer Date 2015-12-02 Time 11:22 Sent To  
Notes
2015-12-03 11:22:52ROUTED TO MALBARRAN