Plan Review Details - Permit 15120083
| Plan Review Stops For Permit 15120083 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-03-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-03-15 |
Time |
05:32 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-03-14 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2016-03-14 14:42:48 | TLARGE'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-12-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-12-23 |
Time |
03:14 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-12-22 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2015-12-22 15:31:02 | PLUMB <5K |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-03-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-03-15 |
Time |
05:32 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-03-15 |
Time |
05:06 |
Sent To |
|
|
| Notes |
| 2016-03-15 05:32:04 | 1)THE COMMENTS FROM THE PREVIOUS REVIEW HAVE NOT BEEN | | | ADDRESSED. COMPLY WITH ALL PREVIOUS COMMENTS. | | | 2) THE IRRIGATION LEGEND SHOWS A WILKINS #720-A | | | BACKFLOW PREVENTER AND IT IS CALLED OUT AS AN RPZ. THIS | | | DEVICE IS A PRESSURE VACUUM BREAKER, NOT AN RPZ. ALSO, | | | YOU HAVE SUBMITTED COPIES OF THE END OF A BOX OR | | | WHATEVER IT IS FOR A WATTS LF919QT BACKFLOW PREVENTER. | | | THIS IS NOT A MANUFACTURER'S SPECIFICATION AS | | | PREVIOUSLY REQUESTED. SUBMIT TWO COPIES OF COMPLETE | | | MANUFACTURER'S SPECIFICATIONS FOR REVIEW. | | | 3) THE BACKFLOW DEVICE MUST BE INSTALLED BY A PROPERLY | | | LICENSED PLUMBING CONTRACTOR. SUBMIT AN APPLICATION BY | | | A PLUMBING CONTRACTOR FOR THE INSTALLATION OF THIS | | | DEVICE. F.S. 489.103. | | | 4) INDICATE THE SIZE OF THE BACKFLOW PREVENTION DEVICE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-12-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-12-23 |
Time |
03:14 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-12-23 |
Time |
02:44 |
Sent To |
|
|
| Notes |
| 2015-12-23 03:06:51 | 1) SUBMIT 2 COPIES OF ALL DOCUMENTS/SPECIFICATIONS FOR | | | THE IRRIGATION SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. | | | ONLY ONE COPY HAS BEEN SUBMITTED. | | | 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS | | | FOR THE BACKFLOW PREVENTION DEVICE. THE BACKFLOW | | | PREVENTION DEVICE MUST BE: | | | A) LEAD FREE | | | B) MUST BE ON THE UNIVERSITY OF SOUTHERN CALIFORNIA | | | (USC) LIST OF APPROVED DEVICES. | | | C) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO | | | CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE | | | CITY?S REQUIREMENTS. | | | 3) SHOW THE PIPE SIZES ON THE PLAN. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|
|
|