| 2015-12-09 11:29:02 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120060 |
| | ADD: 701 NORTHPOINT # 400 |
| | CONT: KAST CONSTRUCTION |
| | TEL: 561-689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 09/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A0: |
| | |
| | 1A) SHEET A0 UNDER THE HEADING THE HEADING OF OCUUPANT |
| | LOAD FOR KAST OFFICES HAS A OCCUPANT LOAD OF 42 WITH |
| | 2427 SQ. FT. PLEASE PROVIDE A BREAK DOWN OF THE SQ. FT. |
| | IN THE TRAINING ROOM AND OCCUPANT LOAD OF THE TRAINING |
| | ROOM (CLASSROOM) WITH THE OCCUPANT LOAD TAKEN AT 20 SQ. |
| | FT PER 2014 FBC-B TABLE 1004.1.2 AND THE REMAINDER OF |
| | THE OFFICE OCCUPANT LOAD TAKEN AT 100 SQ. FT. GROSS. I |
| | BELIEVE THE OCCUPANT LOAD WILL INCREASE. |
| | |
| | 1B) SHEET A0 UNDER NOTE 13 AND THE 3 UNDERLAYMENT |
| | SYSTEMS BELOW THERE WILL NEED TO BE A CONSIDERATION |
| | THAT THE UNDERLAYMENST MEET THE REQUIREMENTS FOUND IN |
| | 2014 FBC-B FBC-B-2014 720.2 CONCEALED INSTALLATION. |
| | TYPE III- TYPE V CONSTRUCTION. |
| | INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| | BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| | |
| | BOAF INFORMAL INTERPRETATION |
| | DATE: WED APR 29 2015 |
| | REPORT: 7481 |
| | CODE: BUILDING CODE YEAR: 2010 |
| | SECTION: 719.2 |
| | QUESTION: |
| | IS IT THE INTENT OF 2010 FBC-B 719.2 TO INCLUDE FLOOR |
| | INSULATION IN BUILDING TYPES III, IV & V. |
| | COMMENT: |
| | THE 2007 FBC-B COMMENTARY 719.1 WITHIN THE LAST |
| | PARAGRAPH STATES THE ADDITION OF INSULATION HAS THE |
| | POTENIAL TO EITHER ADD TO |
| | OR REDUCE THE FIRE-RESISTANCE RATING OF AN ASSEMBLY. |
| | THE REDUCTION OF RATINGS IS MORE OF A PROBLEM WHEN THE |
| | INSULATION IS ADDES |
| | INTO A HORIZONTAL ASSEMBLY. NOTED FLOOR CEILING |
| | ASSEMBLIES LIST THE TYPE OF INSULATION WITHIN THE |
| | ASSEMBLY. THE QUESTION IS DOES |
| | THE CODE SECTION 719.2 REQUIRE FLAME SPREAD AND SMOKE |
| | DEVELOPMENT FOR BUILDING TYPES III, IV OR V? |
| | ANSWER: |
| | YES. PLEASE SEE THE ATTACHED COMMENTARY FOR |
| | INFORMATION. |
| | COMMENTARY: |
| | FLOORING INSULATION, WHETHER IT BE THERMAL OR SOUND |
| | INSULATION, PLACED IN A FLOOR (CONCEALED) WOULD BE |
| | REQUIRED TO MEET THE FLAME |
| | SPREAD REQUIREMENTS OF SECTION 719.2. THERE ARE SOME |
| | EXCEPTIONS AND SPECIAL CONDITIONS CALLED OUT, HOWEVER, |
| | IF IT IS A FIRE RATED |
| | ASSEMBLY, THE FIRE TESTING OF THE ASSEMBLY WOULD HAVE |
| | TO INCLUDE THE MATERIALS USED. IN ADDITION, THE |
| | MATERIALS WOULD HAVE TO |
| | MEET THE STC REQUIREMENTS AT SECTION 1207. THERE ARE |
| | MANY TYPE 3 & 5 BUILDINGS OUT THERE BEING BUILT. SOME |
| | MAY HAVE WOOD |
| | FLOOR SYSTEMS OTHERS CONCRETE, BUT THE REQUIREMENTS |
| | FOUND IN 719.2 ARE MORE RESTRICTIVE THAN FOR TYPE I |
| | TYPE II CONSTRUCTION. |
| | |
| | 1C) SHEET A0 UNDER THE NOTE 13 THERE ARE 3 UNDERLAYMENT |
| | SYSTEMS AND OR ALTERNATIVES. 2014 FLORIDA BUILDING CODE |
| | W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS |
| | AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. |
| | |
| | 2) SHEET A3.1 THERE IS A EXISITNG DOOR IN A COORIDOR |
| | NEXT TO ROOM IT CLOSET K-104, THIS DOOR DOES NOT HAVE |
| | 18 INCHES ON THE LATCH SIDE OF THE DOOR. 2014 |
| | FBC-ACCESSIBILITY CODE 404.2.4 MANEUVERING CLEARANCES. |
| | THE CONTRACT VALUE OF $30,000 DOLLORS, 20 % OF THE |
| | CONTRACT VALUE CAN BE SPENT ON ACCESSIBLE UPGRADES TO |
| | MAKE THE BUILDING MORE ACCESSIBLE SEE 2014 |
| | FBC-ACCESSIBILITY CODE 202.4 & 202.4.1. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |