Plan Review Details - Permit 15120053
Plan Review Stops For Permit 15120053
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-11 Cont ID  
Sent By jwitmer Date 2016-03-11 Time 13:51 Rev Time 0.00
Received By jwitmer Date 2016-03-11 Time 12:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-09 Cont ID  
Sent By jwitmer Date 2015-12-09 Time 09:37 Rev Time 0.00
Received By jwitmer Date 2015-12-09 Time 09:04 Sent To  
Notes
2015-12-09 09:10:54BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120053
 ADD: 120 S. OLIVE AVE. SUITE?
 CONT: TBD
 TEL: 561-659-2383
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. DEC. 09/2015
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3. THE
 PERMIT APPLICATION LIST THE ADDRESS OF 120 S. OLIVE
 AVE. NO SUITE NUMBER IS GIVEN. THE PLANS SHEET A-0.00
 INDICATE THIS IS A NEW SUITES # 210, 211 & 212. SHEET
 A-0.00 INDICATES (EXISTING SUITES 205 & 210 BEING
 SUB-DIVIDED TO CREATE NEW SUITES 210, 211 & 212. THIS
 IS A COMMERCIAL CONDOMINIUM, WITH THE NEW SUITES BEING
 ADDED THE DECLARATION OF CONDOMINIUM WILL NEED TO BE
 UPDATED.
  
 2) SHEET A-0.00 SOMEONE HAS X-ED OUT THE WORK SHOWN ON
 THE PLAN FOR THE 2ND FLOOR. THIS IS NOT BEEN INITIALED
 BY THE DESIGNER OF RECORD AND DATED.
 IN THE CODE ANALYSIS THE WRITTEN DESCRIPTION OF WORK
 STILL SHOWS WORK TO BE PREFORMED ON THE 6TH FLOOR.
 107.2.1.3 DISCREPANCY IN PLANS, PLEASE PROVIDE
 ADDITIONAL INFORMATION. ONLY THE DESIGNER OF RECORD CAN
 MODIFY THE PLANS BY APPLYING THERE INITIALS AND DATING
 THE RED LINED DRAWING. FL ADMIN CODE 61G16.003
 ARCHITECTS.
  
 3A) SHEET A-0.00 SUITE # 212 THE ENTRY DOOR IT APPEARS
 THERE IS ONLY 12 INCHES ON THE LATCH SIDE OF THE
 INSWING DOOR. THE 2014 FBC-ACCESSIBILITY CODE SECTION
 404.2.4 MANEUVERING CLEARANCES REQUIRES A MINIMUM OF 18
 INCHES. ALSO SEE FIGURE 404.2.4.1(A).
  
 3B) SHEET A-0.00 SUITE # 211 WHAT APPEARS TO BE A BREAK
 ROOM WITH REFRIGARATOR AND SINK HAS ONLY 12 INCHES ON
 THE LATCH SIDE OF THE INSWING DOOR. THE 2014
 FBC-ACCESSIBILITY CODE SECTION 404.2.4 MANEUVERING
 CLEARANCES REQUIRES A MINIMUM OF 18 INCHES. ALSO SEE
 FIGURE 404.2.4.1(A).
  
 3C) SHEET A-0.00 SUITE # 210 WHAT APPEARS TO BE THE
 RECEPTIONIST AREA THERE IS A STUB SECTION OF WALL
 DIRECTLY AT THE DOOR. . THE 2014 FBC-ACCESSIBILITY CODE
 SECTION 404.2.4 MANEUVERING CLEARANCES REQUIRES A
 MINIMUM OF 18 INCHES. ALSO SEE FIGURE 404.2.4.1(A).
  
 4) NONE OF THE ARCHITECTURALS SHEETS PROVIDES
 IDENTIFICATION OF DOORS NOR IS THERE A DOOR SCHEDULE TO
 BE ABLE TO VERIFY CODE COMPLIANCE WITH:
 2014 FBC-B 1008.1.1 MINIMUM EGRESS DOOR SIZE.
 2014 FBC-ACCESSIBILITY 404.2.3 CLEAR WIDTH.
  
 5) SHEET A-0.00 SUITE # 211 DOES NOT INDICATE THE
 USAGEIT IS NOT CLEARLY STATE IF DEPICTED IS A FLOOR
 SINK, WORK ROOM SINK OR A BREAK ROOM SINK IS IN THE
 NORTH EAST CORNER OF THE ROOM. IT IS NOT CLEAR IF
 COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE 606.
 1-5 IS REQUIRED?
  
 6) THERE ARE NO FIRE SPRINKLER PLANS SUBMITTED SHOWING
 THE LOCATION OF THE EXISITNG SPRINKLER HEADS, IF HEADS
 NEED TO BE MOVED? THERE WERE DEMOLTION PLANS SUBMITTED
 SHOWING WHAT WALLS ARE OLD AND WHICH WALLS ARE MOVED
 AND OR NEW WALLS. 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.(5)
 SCHEMATIC FIRE SPRINKLERS.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-01-20 Cont ID  
Sent By albarran Date 2016-01-20 Time 18:08 Rev Time 0.00
Received By albarran Date 2016-01-20 Time 18:00 Sent To IMPACT
Notes
2016-01-20 18:09:37NOTICE TO ELECTRICAL CONTRACTOR
 ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE-RATED
 STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE
 RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE
 SEALING MATERIAL.
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2016-01-12 Cont ID  
Sent By   Date 2016-01-12 Time   Rev Time 0.00
Received By   Date 2016-01-12 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-03 Cont ID  
Sent By pleduc Date 2015-12-03 Time   Rev Time 0.00
Received By pleduc Date 2015-12-03 Time 15:22 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2015-12-16 Cont ID  
Sent By aaponte Date 2015-12-16 Time 14:26 Rev Time 0.00
Received By aaponte Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-11 Cont ID  
Sent By jwitmer Date 2016-03-11 Time 13:51 Rev Time 0.00
Received By jwitmer Date 2016-03-08 Time 13:20 Sent To  
Notes
2016-03-08 13:20:53RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-21 Cont ID  
Sent By jwitmer Date 2016-01-21 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2015-12-01 Time 15:59 Sent To  
Notes
2015-12-01 16:03:29B15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-01-21 Cont ID  
Sent By jwitmer Date 2016-01-21 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2016-01-21 Time 15:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-08 Cont ID  
Sent By ccole Date 2016-03-08 Time 16:30 Rev Time 0.00
Received By ccole Date 2016-03-08 Time 16:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-09 Cont ID  
Sent By ccole Date 2015-12-09 Time 10:59 Rev Time 0.00
Received By ccole Date 2015-12-09 Time 10:59 Sent To  
Notes
2015-12-09 11:06:561ST REVIEW 2014 MECHANICAL
 PERMIT #15120053
 12/9/15
  
 1) SHEETS M1.1 & M5.1 : IDENTIFY ALL THE ROOMS ON THE
 PLAN WITH LABELS MATCHING THE SPACE TYPES SHOWN IN THE
 O/A CALCULATIONS SCHEDULE.
 2) M5.1: AHU-2-2 IS NOT LISTED IN O/A SCHEDULE- AHU-2-3
 IS LISTED TWICE.
 3) INDICATE THE TYPE AND SIZE OF LOUVERED DOOR FOR THE
 NEW AHU-2-2 CLOSET.
 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE RELOCATED
 AHU-2-2: SHOW THE TYPE AND SIZE OF PIPING, THE PIPING
 RUN, AND THE DISCHARGE LOCATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-12-08 Cont ID  
Sent By gjohnson Date 2015-12-08 Time 13:44 Rev Time 0.00
Received By gjohnson Date 2015-12-08 Time 13:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2015-12-16 Cont ID  
Sent By aaponte Date 2015-12-16 Time 14:26 Rev Time  
Received By aaponte Date   Time   Sent To  
Notes
***NONE***