Plan Review Details - Permit 15111032
Plan Review Stops For Permit 15111032
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-05-13 Cont ID  
Sent By jgomez Date 2016-05-13 Time 09:19 Rev Time 0.00
Received By jgomez Date 2016-05-13 Time 07:50 Sent To  
Notes
2016-05-13 09:19:48BUILDING REVIEW APPROVED WITH PROVISO:
 1- ENERGY CALCULATIONS SUBMITTED: REVISE ROOF FINISH
 MATERIAL INFORMATION ON PAGE 2 TO MATCH PLANS.
 2- PROVIDE COMPLETE MANUFACTURER'S SPECS FOR ALL
 FIREPLACES SHOWN ON PLANS. NOTE: DESIGNER OF RECORD TO
 REVIEW/APPROVE PRIOR TO SUBMITTAL.
 3- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R5
 SUBMITTED: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR SELECTED ASSEMBLY W-55 AS REQUIRED BY
 NOTE #8 ON PAGE 2 OF 76.
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A)ENTRY DOOR AS SPECIFIED ON PLANS. DRAWING NO
 "LAG-TEN" SUBMITTED DON'T CORRESPOND TO FLORIDA PRODUCT
 APPROVAL COVER PAGE FL15911-R1 SUBMITTED.
 B) EXTERIOR DOORS: FRENCH DOORS WITH SIDELITES, GARAGE
 SWING DOOR, LAUNDRY ROOM, CABANA BATHROOM AND CABANA
 STORAGE.
 6- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS.
  
 REMAINDER: SPECIAL INSPECTOR WILL BE REQUIRED FOR THE
 INSPECTION OF THE SECOND FLOOR SLAB. SEC. 110.3.9 CITY
 AMENDMENTS. PLEASE CONTACT KEN CONRAD (CHIEF BUILDING
 INSPECTOR. (561)805-6666 OR [email protected]) ) FOR
 DETAILS OF QUALIFIED INSPECTORS).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-04-27 Cont ID  
Sent By jgomez Date 2016-04-26 Time 11:30 Rev Time 0.00
Received By jgomez Date 2016-04-26 Time 11:30 Sent To  
Notes
2016-04-26 11:39:58NEW SINGLE FAMILY RESIDENCE (R3), THIRD BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO ONCE
 THE ENERGY CALCULATIONS ARE SIGNED. CONTRACTOR MAY
 SUBMIT REQUIRED INFORMATION AFTER THE PERMIT IS ISSUED.
 REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF
 PROVISO OPTION IS PREFERRED.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) THE BUILDING'S OWNER/AGENT NEEDS TO CERTIFY
 COMPLIANCE AT THE BOTTOM OF THE FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014). (REPEATED COMMENT).
  
 B) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING
 BUILDER NAME. SEC. R101.5.1.1.2 OF FBC - ENERGY
 CONSERVATION, 5TH EDITION (2014). (REPEATED COMMENT).
  
 C) ROOF INFORMATION ON PAGE 2 OF 6 DOESN'T MATCH PLANS.
 ROOF MATERIAL IS INCORRECT. SEC. R101.5.1.1.2 OF FBC -
 ENERGY CONSERVATION, 5TH EDITION (2014). (REPEATED
 COMMENT).
  
 ***NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING THE
 DEFAULT FACTOR FOR GLAZING.
  
 2- PROVIDE COMPLETE MANUFACTURER'S SPECS FOR ALL
 FIREPLACES SHOWN ON PLANS. SHOWING COMPLIANCE WITH
 CHAPTER 10 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 NOTE: DESIGNER OF RECORD TO REVIEW/APPROVE PRIOR TO
 SUBMITTAL.
  
 3- REVISE SPECIFICATIONS ON SECOND PARAGRAPH OF
 HANDRAILS AND GUARDRAILS SECTION ON SHEET S9 TO COMPLY
 WITH NOTE"F" OF TABLE R301.5 OF FBC-RESIDENTIAL.
 (REPEATED COMMENT).
  
 4- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R5
 SUBMITTED: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR SELECTED ASSEMBLY W-55 AS REQUIRED BY
 NOTE #8 ON PAGE 2 OF 76. NEED CALCULATIONS TO MEET THE
 DESIGNER PRESSURES REQUIRED BY SEC. R301
 FBC-RESIDENTIAL. (REPEAT COMMENT).
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A)ENTRY DOOR AS SPECIFIED ON PLANS. DRAWING NO
 "LAG-TEN" SUBMITTED DON'T CORRESPOND TO FLORIDA PRODUCT
 APPROVAL COVER PAGE FL15911-R1 SUBMITTED. PROVIDE
 DRAWINGS THAT WERE APPROVED WITH FL15911-R1
  
 B) EXTERIOR DOORS: FRENCH DOORS WITH SIDELITES AS SHOWN
 ON PLANS FOR DINING ROOM, GARAGE SWING DOOR, LAUNDRY
 ROOM, CABANA BATHROOM AND CABANA STORAGE AS SHOWN ON
 PLANS. (REPEAT COMMENT).
  
 6- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 REMAINDER: SPECIAL INSPECTOR WILL BE REQUIRED FOR THE
 INSPECTION OF THE SECOND FLOOR SLAB. SEC. 110.3.9 CITY
 AMENDMENTS. PLEASE CONTACT KEN CONRAD (CHIEF BUILDING
 INSPECTOR. (561)805-6666 OR [email protected]) ) FOR
 DETAILS OF QUALIFIED INSPECTORS).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE RE-SUBMITTED SET. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-28 Cont ID  
Sent By jgomez Date 2016-03-23 Time 14:08 Rev Time 0.00
Received By jgomez Date 2016-03-23 Time 14:08 Sent To  
Notes
2016-03-23 14:21:21NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE SOIL TEST REPORT. 2 COPIES. SEC. R401.4 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: SOILS REPORT PENDING.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) THE BUILDING'S OWNER/AGENT NEEDS TO CERTIFY
 COMPLIANCE AT THE BOTTOM OF THE FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 B) NUMBER OF BEDROOMS DOESN'T MATCH PLANS. MISSING THE
 GUEST BEDROOM ABOVE GARAGE. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 OF FBC - ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) REVISE TYPE AND NUMBER OF WATER HEATERS TO MATCH
 PLANS. THERE ARE NO ELECTRIC WATER HEATERS. SEC.
 R101.5.1.1.2 OF FBC - ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING OWNER
 NAME, BUILDER NAME AND JURISDICTION NUMBER. SEC.
 R101.5.1.1.2 OF FBC - ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 E) CLARIFY BLOCKS AND SPACES INFORMATION SHOWN ON PAGE
 2 OF 6. CLARIFY WHERE IS THE AREA TAKEN FROM FOR EACH
 BLOCK AND SPACE. CLARIFY WHERE ARE THE 2 KITCHENS
 LOCATED AT. CLARIFY WHY THERE ARE ZERO OCCUPANTS.
 CLARIFY WHICH BEDROOMS ARE INCLUDED ON EACH AREA. SEC.
 R101.5.1.1.2 OF FBC - ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) ROOF INFORMATION ON PAGE 2 OF 6 DOESN'T MATCH PLANS.
 TYPE OF ROOF IS INCORRECT. ROOF MATERIAL IS INCORRECT.
 WHERE IS THE GABLE AREA TAKEN AT?. SEC. R101.5.1.1.2 OF
 FBC - ENERGY CONSERVATION, 5TH EDITION (2014).
  
 G) PROVIDE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 OF FBC - ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 H) THE COOLING AND HEATING SYSTEMS INFORMATION ON ITEMS
 #12 AND #13 WILL BE REVIEWED ONCE THE COMPLETE
 EQUIPMENT SIZING CALCULATIONS ARE PROVIDED.
  
 ***NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING THE
 DEFAULT FACTOR FOR GLAZING.
  
 3- A) PROPERTY IS LOCATED IN FLOOD ZONE A5. PROVIDE
 COMPLETE INFORMATION SHOWING COMPLIANCE WITH THE FLOOD
 RESISTANT CONSTRUCTION OF SEC. R322 OF FBC-RESIDENTIAL,
 5TH EDITION (2014). PROVIDE SURVEY WITH FINISH FLOOR
 ELEVATIONS AND SPECIFY ON PLANS (ARCHITECTURAL AND
 STRUCTURAL) THE FINISHED FLOOR ELEVATION FOR MAIN
 HOUSE, GARAGE, CABANA AND ALL EQUIPMENT. PROVIDE
 COMPLETE SPECIFICATIONS FOR FLOOD RESISTANT
 CONSTRUCTION FOR AREAS THAT ARE BELOW THE 7'-6" (FLOOD
 ZONE A5 HAS A BASE FLOOD ELEVATION OF 7'-0". CITY
 ORDINANCE REQUIRES FINISH FLOOR TO BE 6" ABOVE THE BASE
 FLOOD ELEVATION).
  
 RESPONSE: THE FINISH FLOOR ELEVATION OF THE GARAGE IS
 SHOWN AT THE HIGHEST PART OF THE GARAGE SLAB. THE SLAB
 IS PITCHED 2". THEREFORE, THE GARAGE SLAB IS BELOW THE
 7'-6" MIN. REQUIREMENT. THE FINISH FLOOR ELEVATIONS ARE
 MEASURED AT THE LOWEST POINT OF THE SLAB. REVISE AS
 REQUIRED OR PROVIDE COMPLETE INFORMATION FOR THE FLOOD
 RESISTANT CONSTRUCTION AS REQUIRED BY SEC. R322.
  
 B) NOTE: ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. ELEVATION CERTIFICATE SUBMITTED IS FOR
 THE EXISTING HOUSE. NEW ELEVATION CERTIFICATES REQUIRED
 FOR THE PROPOSED HOUSE, GARAGE, CABANA AND ALL THE
 EQUIPMENT.
  
 RESPONSE: NEW ELEVATION CERTIFICATE DATED 1/5/2016 IS
 FOR THE EXISTING HOUSE AGAIN. THIS IS NOT WHAT I ASKED
 FOR. SEE COMMENT ABOVE. PLEASE COORDINATE ALL
 ELEVATIONS CERTIFICATES WITH SAMANTHA HILL AT
 [email protected] OR (561)805-6724.
  
 4- NEED TO SPECIFY CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH BEDROOM AS REQUIRED BY SEC. R315 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). INCLUDE FIRST
 FLOOR GUEST-ROOM AND SECOND FLOOR GUEST ROOM ABOVE
 GARAGE.
  
 RESPONSE: CARBON MONOXIDE ALARM WAS SHOWN FOR THE GUEST
 ROOM IN THE MAIN HOUSE, BUT NOT FOR THE GUEST ROOM
 ABOVE GARAGE.
  
 5- PROVIDE COMPLETE WALL SECTIONS AND SPECIFICATIONS
 FOR ALL 5 FIREPLACES SHOWN ON PLANS SHOWING COMPLIANCE
 WITH CHAPTER 10 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 PROVIDE COMPLETE MANUFACTURER'S SPECS FOR EACH ONE.
 NOTE: DESIGNER OF RECORD TO APPROVE ALL MANUFACTURER'S
 SPECS PRIOR TO SUBMITTAL. CLARIFY IF FACTORY BUILT
 FIREPLACES?. CLARIFY IF FACTORY BUILT CHIMNEYS?.
 SPECIFY ALL CLEARANCES AND CHIMNEY'S TERMINATION, ETC.
  
 RESPONSE: PROVIDE COMPLETE MANUFACTURER'S SPECS FOR
 EACH FIREPLACE. DESIGNER OF RECORD TO REVIEW/APPROVE
 PRIOR TO SUBMITTAL.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE WITH THE
 LIVE LOAD REQUIREMENTS OF TABLE R301.5 AND THE ALL
 REQUIREMENTS OF SEC. R311.7.8 AND SEC. R312 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE: INFORMATION SHOWN ON SHEET A200 IS INCORRECT.
 THE SIZE OF THE SPHERE THAT CAN NOT PASS THRU IS 4" NOT
 4-3/8". SEE SEC. R312.1.3. ALSO, NEED TO REVISE THE
 SPECIFICATIONS ON SHEET S9. INFORMATION ON THE SECOND
 PARAGRAPH OF HANDRAILS AND GUARDRAILS SPECIFICATIONS
 SEEM TO BE IN-CONFLICT WITH NOTE "F" OF TABLE R301.5.
 REVISE AS REQUIRED.
  
 7- SEC. R803.2.3.1 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014) REQUIRES 8D RING SHANK NAILS. NAILS SPECIFIED ON
 DETAIL 12/S7 ARE NO SPECIFIED AS RING SHANK NAILS.
 CLARIFY IF USING RING SHANK NAILS OR NOT. IF NOT USING
 RING SHANK NAILS, THEN PROVIDE CALCULATIONS SHOWING
 THAT THE 10D NAILS ARE EQUIVALENT OR BETTER THAN THE
 REQUIRED 8D RING SHANK NAILS. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 RESPONSE: RESPONSE LETTER STATES " SEE 12/S7". THERE
 ARE NO CHANGES ON DETAIL 12/S7. COMMENT NOT ADDRESSED.
  
 8- STRUCTURAL PLANS TO SPECIFY THE ATTIC LIVE LOAD AS
 REQUIRED BY FOOTNOTES "B" AND "G" OF TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE: RESPONSE LETTER STATES " SEE SHEET S2 & S3
 LOADING CHARTS" THERE ARE NO CHANGES ON SHEETS S2 AND
 S3. COMMENT NOT ADDRESSED.
  
 9- CLARIFY WHICH ROOF TILE ADHESIVE IS GOING TO BE
 USED. ROOF TILE FLORIDA PRODUCT APPROVAL FL7804-R8 WAS
 HIGHLIGHTED WITH RTA-1 FOAM, BUT ROOF TILE ADHESIVE
 FLORIDA PRODUCT APPROVAL FL 6332-R5 SUBMITTED IS FOR
 AH-160 FOAM. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) FLOOD VENTS IF REQUIRED. DEPENDING ON THE LOWEST
 GARAGE FINISH FLOOR ELEVATION SHOWN ON PLANS.
  
 B) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED. AND,
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE CALCULATED DESIGN
 PRESSURES.
  
 RESPONSE: THE SELECTED ASSEMBLY (W-55) FROM FLORIDA
 PRODUCT APPROVAL FL5680-R15 IS GOOD FOR -60PSF. NEED TO
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR NAIL
 ENHANCEMENT AT PERIMETER AND CORNER AREAS AS REQUIRED
 BY NOTE #8 ON PAGE 2 OF 76 OF PRODUCT APPROVAL
 SUBMITTED.
 NOTE: FORM 100 SUBMITTED IS FOR PBC BUILDING
 DEPARTMENT. THIS IS NOT USED BY THE CITY OF WPB.
  
 C) MODIFIED MEMBRANE THAT IS DESIGNED TO RECEIVE THE
 FINISH MATERIAL SPECIFIED ON PLANS FOR THE TERRACES AND
 BALCONIES. NOTE: CHECK DESIGN PRESSURES FOR SELECTED
 ASSEMBLY. SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE
 REQUIRED.
  
 RESPONSE: ACCORDING TO CONDITIONS OF USE SEC. 5.2 OF
 ICC ESR-2467 REPORT SUBMITTED, THIS PRODUCT IS FOR
 INTERIOR USE ONLY. NEED PRODUCT APPROVAL FOR EXTERIOR
 USE AND NEED TO CONSIDER THE WIND LOADS.
  
 D) ENTRY DOOR AS SPECIFIED ON PLANS.
  
 RESPONSE: DRAWINGS SUBMITTED DON'T HAVE A FLORIDA
 PRODUCT APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. IF
 THERE IS NO FLORIDA OR MIAMI DADE NOA, THEN
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL .
 NEED TO PROVIDE COMPLETE ENGINEERING PACKAGE WITH
 ORIGINAL SEAL AND SIGNATURE FOR APPROVAL BY THE
 BUILDING OFFICIAL. PLEASE CONTACT ROBERT BROWN
 (BUILDING OFFICIAL) AT (561)805-6652 TO COORDINATE
 SUBMITTAL PROCESS.
  
 E) GARAGE DOORS AS SPECIFIED ON PLANS.
  
 RESPONSE: DESIGN PRESSURES SHOWN ON FLORIDA PRODUCT
 APPROVAL FL 11494 SUBMITTED DON'T MEET THE CALCULATED
 DESIGN PRESSURES SHOWN ON DRAWINGS. NEED PRODUCT
 APPROVAL THAT MEETS THOSE DESIGN PRESSURES.
  
 F) ALL EXTERIOR DOORS AS SPECIFIED ON PLANS. AND,
 CLEARLY IDENTIFY LOCATION. FOR EXAMPLE, CABANA DOOR,
 GARAGE DOOR, LAUNDRY DOOR, STORAGE DOOR, ETC.
  
 RESPONSE: DRAWINGS SUBMITTED DON'T HAVE A FLORIDA
 PRODUCT APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. IF
 THERE IS NO FLORIDA OR MIAMI DADE NOA, THEN
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL .
 NEED TO PROVIDE COMPLETE ENGINEERING PACKAGE WITH
 ORIGINAL SEAL AND SIGNATURE FOR APPROVAL BY THE
 BUILDING OFFICIAL. PLEASE CONTACT ROBERT BROWN
 (BUILDING OFFICIAL) AT (561)805-6652 TO COORDINATE
 SUBMITTAL PROCESS.
  
 G) ALL WINDOWS AS SPECIFIED ON PLANS.
  
 RESPONSE: DRAWINGS SUBMITTED DON'T HAVE A FLORIDA
 PRODUCT APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. IF
 THERE IS NO FLORIDA OR MIAMI DADE NOA, THEN
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL .
 NEED TO PROVIDE COMPLETE ENGINEERING PACKAGE WITH
 ORIGINAL SEAL AND SIGNATURE FOR APPROVAL BY THE
 BUILDING OFFICIAL. PLEASE CONTACT ROBERT BROWN
 (BUILDING OFFICIAL) AT (561)805-6652 TO COORDINATE
 SUBMITTAL PROCESS.
  
 11- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 REMAINDER: SPECIAL INSPECTOR WILL BE REQUIRED FOR THE
 INSPECTION OF THE SECOND FLOOR SLAB. SEC. 110.3.9 CITY
 AMENDMENTS. PLEASE CONTACT KEN CONRAD (CHIEF BUILDING
 INSPECTOR. (561)805-6666 OR [email protected]) ) FOR
 DETAILS OF QUALIFIED INSPECTORS).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE RE-SUBMITTED SET. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-29 Cont ID  
Sent By jgomez Date 2015-12-29 Time 11:27 Rev Time 0.00
Received By jgomez Date 2015-12-29 Time 07:54 Sent To  
Notes
2015-12-29 11:31:27NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- NEED A SEPARATE DEMOLITION PERMIT TO DEMOLISH
 EXISTING HOUSE. SEC. 105.1 CITY AMENDMENTS.
  
 2- PROVIDE SOIL TEST REPORT. 2 COPIES. SEC. R401.4 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- PROVIDE ENERGY CALCULATIONS. SEC. R101.5 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH PLANS SUBMITTED TO AVOID
 CONFLICTS OR DELAYS.
  
 5- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 6-REVISE OCCUPANCY AND BUILDING TYPE INFORMATION ON THE
 COVER SHEET. THIS HOUSE IS NOT CONSTRUCTION TYPE III.
 SINGLE FAMILY RESIDENCES ARE TYPICALLY CONSTRUCTION VA
 OR VB. CONSTRUCTION TYPE III REQUIRES 2 HOUR WALLS. SEE
 TABLE 601 OF FBC-BUILDING, 5TH EDITION (2014). REVISE
 AS REQUIRED.
  
 7- A) PROPERTY IS LOCATED IN FLOOD ZONE A5. PROVIDE
 COMPLETE INFORMATION SHOWING COMPLIANCE WITH THE FLOOD
 RESISTANT CONSTRUCTION OF SEC. R322 OF FBC-RESIDENTIAL,
 5TH EDITION (2014). PROVIDE SURVEY WITH FINISH FLOOR
 ELEVATIONS AND SPECIFY ON PLANS (ARCHITECTURAL AND
 STRUCTURAL) THE FINISHED FLOOR ELEVATION FOR MAIN
 HOUSE, GARAGE, CABANA AND ALL EQUIPMENT. PROVIDE
 COMPLETE SPECIFICATIONS FOR FLOOD RESISTANT
 CONSTRUCTION FOR AREAS THAT ARE BELOW THE 7'-6" (FLOOD
 ZONE A5 HAS A BASE FLOOD ELEVATION OF 7'-0". CITY
 ORDINANCE REQUIRES FINISH FLOOR TO BE 6" ABOVE THE BASE
 FLOOD ELEVATION).
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE ENCLOSED AREA BELOW THE DESIGN
 FLOOD ELEVATION SHOWING COMPLIANCE WITH ALL THE
 REQUIREMENTS OF SEC. R322.2.2 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
 NOTE: SEE REQUIRED LOCATION OF VENTS. ALSO, TAKE INTO
 CONSIDERATION VENTS FOR THE CARPORT AREA. THIS AREA IS
 ENCLOSED ON THREE SIDES.
  
 C) NOTE: ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. ELEVATION CERTIFICATE SUBMITTED IS FOR
 THE EXISTING HOUSE. NEW ELEVATION CERTIFICATES REQUIRED
 FOR THE PROPOSED HOUSE, GARAGE, CABANA AND ALL THE
 EQUIPMENT.
  
 8- ENTRY DOOR DOESN'T COMPLY WITH SEC. R311.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). DOOR LEAF NEEDS TO
 PROVIDE 32" CLEAR OPENING.
  
 9- BATHROOM DOOR IN THE GUEST ROOM ON FIRST FLOOR
 DOESN'T COMPLY WITH SEC. R320 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). DOOR NEEDS TO PROVIDE 29" CLEAR
 OPENING.
  
 10- ATTIC ACCESS LOCATED IN THE GUEST ROOM ABOVE THE
 GARAGE DOESN'T COMPLY WITH SEC. R807 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). SIZE IS TOO SMALL
 AND THE LOCATION INSIDE THE CLOSET IS NOT ALLOWED. IT'S
 GOING TO BE BLOCKED BY SHELVES AND ANYTHING PLACED IN
 THE CLOSET.
  
 11- ENTRY DOOR FOR GUEST ROOM ABOVE THE GARAGE DOESN'T
 COMPLY WITH SEC. R311.2 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). DOOR LEAF NEEDS TO PROVIDE 32" CLEAR OPENING.
  
 12- PROVIDE ATTIC ACCESS IN CABANA. SEC. R807 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 13- NEED TO SPECIFY CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH BEDROOM AS REQUIRED BY SEC. R315 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). INCLUDE FIRST
 FLOOR GUEST-ROOM AND SECOND FLOOR GUEST ROOM ABOVE
 GARAGE.
  
 14- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING
 AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS.
  
 15- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS. DESIGNER OF RECORD TO
 REVIEW AND APPROVE IT PRIOR TO SUBMITTAL TO THIS
 OFFICE. SEC. R316 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 16- WALL SECTION AT GARAGE S-5/A302: PROVIDE
 SPECIFICATIONS FOR THE INSULATION BETWEEN GARAGE AND
 SECOND FLOOR GUEST-ROOM. COORDINATE WITH ENERGY
 CALCULATIONS. SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 17- PROVIDE COMPLETE WALL SECTIONS AND SPECIFICATIONS
 FOR ALL 5 FIREPLACES SHOWN ON PLANS SHOWING COMPLIANCE
 WITH CHAPTER 10 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 PROVIDE COMPLETE MANUFACTURER'S SPECS FOR EACH ONE.
 NOTE: DESIGNER OF RECORD TO APPROVE ALL MANUFACTURER'S
 SPECS PRIOR TO SUBMITTAL. CLARIFY IF FACTORY BUILT
 FIREPLACES?. CLARIFY IF FACTORY BUILT CHIMNEYS?.
 SPECIFY ALL CLEARANCES AND CHIMNEY'S TERMINATION, ETC.
 NOTE: COORDINATE WITH MECHANICAL COMMENTS. CHIMNEYS AND
 VENTS AS REQUIRED BY CHAPTER 18 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 18- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE WITH THE
 LIVE LOAD REQUIREMENTS OF TABLE R301.5 AND THE ALL
 REQUIREMENTS OF SEC. R311.7.8 AND SEC. R312 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 19- NOTE: SPECIAL INSPECTOR WILL BE REQUIRED FOR THE
 INSPECTION OF THE SECOND FLOOR SLAB. SEC. 110.3.9 CITY
 AMENDMENTS. PLEASE CONTACT KEN CONRAD (CHIEF BUILDING
 INSPECTOR. (561)805-6666 OR [email protected]) ) FOR
 DETAILS OF QUALIFIED INSPECTORS).
  
 20- SEC. R803.2.3.1 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014) REQUIRES 8D RING SHANK NAILS. NAILS SPECIFIED ON
 DETAIL 12/S7 ARE NO SPECIFIED AS RING SHANK NAILS.
 CLARIFY IF USING RING SHANK NAILS OR NOT. IF NOT USING
 RING SHANK NAILS, THEN PROVIDE CALCULATIONS SHOWING
 THAT THE 10D NAILS ARE EQUIVALENT OR BETTER THAN THE
 REQUIRED 8D RING SHANK NAILS. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 21- STRUCTURAL PLANS TO SPECIFY THE ATTIC LIVE LOAD AS
 REQUIRED BY FOOTNOTES "B" AND "G" OF TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 22- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE PERGOLA, MASTER TERRACE AND GUEST
 TERRACE TRELLIS. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 23- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 C) FLOOD VENTS AS SPECIFIED ON PLANS.
  
 D) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED. AND,
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE CALCULATED DESIGN
 PRESSURES.
  
 E) MODIFIED MEMBRANE THAT IS DESIGNED TO RECEIVE THE
 FINISH MATERIAL SPECIFIED ON PLANS FOR THE TERRACES AND
 BALCONIES. NOTE: CHECK DESIGN PRESSURES FOR SELECTED
 ASSEMBLY. SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE
 REQUIRED.
  
 F) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 G) ENTRY DOOR AS SPECIFIED ON PLANS.
  
 H) GARAGE DOORS AS SPECIFIED ON PLANS.
  
 I) ALL EXTERIOR DOORS AS SPECIFIED ON PLANS. AND,
 CLEARLY IDENTIFY LOCATION. FOR EXAMPLE, CABANA DOOR,
 GARAGE DOOR, LAUNDRY DOOR, STORAGE DOOR, ETC.
  
 J) ALL WINDOWS AS SPECIFIED ON PLANS.
  
 24- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE RE-SUBMITTED SET. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-09 Cont ID  
Sent By mvaldes Date 2016-05-09 Time 13:52 Rev Time 0.00
Received By mvaldes Date 2016-05-09 Time 13:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-17 Cont ID  
Sent By mvaldes Date 2016-03-17 Time 18:30 Rev Time 0.00
Received By mvaldes Date 2016-03-17 Time 18:30 Sent To  
Notes
2016-03-17 18:38:43JOB PERMIT NUMBER: 15111032
 JOB ADDRESS: 2914 WASHINGTON RD
 WEST PALM BEACH FLORIDA
 DATE: MARCH 17 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT. MISSING ON
 SHEET E100 BY CU#1
 - PROVIDE SERVICE EQUIPMENT LOCATION ON ELECTRICAL
 FLOOR PLANS. WBA 107
 - GARAGE DOOR MOTOR OUTLET A 15 , A 17 MUST BE GFCI
 PROTECTED NEC 210.8A
 - GENERATOR ON A SEPARATE PERMIT TO INCLUDE CUT SHEETS
 OF ATS EQUIPMENT ( SERVICE-RATED ) AND GENERATOR
 MANUFACTURE SPECS.
 - RISER DIAGRAM ON SHEET E102 STILL SHOWS SERVICE
 GROUNDED CONDUCTOR BEING IN PARALLEL BY RUNNING A # 4
 AWG BONDING CONDUCTOR THIS IS A VIOLATION OF NEC 250
 GROUNDING & BONDING PLUS NEC 310.10 H WIRING METHODS.
 - GROUNDING DETAIL TO INCLUDE INTERSYSTEM BONDING STRIP
 NEC 250.94
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-04 Cont ID  
Sent By mvaldes Date 2016-01-04 Time 17:07 Rev Time 0.00
Received By mvaldes Date 2016-01-04 Time 17:07 Sent To  
Notes
2016-01-04 17:54:141ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 GENERATOR ON SEPERATE PERMIT. POOL ON A SEPERATE
 PERMIT.
 FBC E C405.7.3.1 FEEDERS AND CUSTOMER OWNED SERVICE
 CONDUCTORS.
 FEEDER AND CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE
 SIZED FOR A MAXIMUM VOLTAGE DROP OF 2 PERCENT AT DESIGN
 LOAD.
 C405.7.3.2 BRANCH CIRCUITS.
 BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 VOLTAGE DROP OF 3 PERCENT AT DESIGN LOAD.
 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS
 SHALL
 BE PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS.
 SUCH A
 DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE
 BUILDING
 OR OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL
 CALCULATED
 LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS
 USED, THE CALCULATED LOAD AFTER APPLYING DEMAND
 FACTORS,
 AND THE SIZE AND TYPE OF CONDUCTORS TO BE USED.
 SHEET E 102 SHOWS A 2 INCH CONDUIT FOR 3 350 KCMIL
 THATS INADEQUATE CHECK TABLE 9 AND ANNEX C
 ALSO SHOWS A # 4 BONDING CONDUCTOR WHICH WOULD INDICATE
 PARRELLELING GROUNDED CONDUCTOR VIOLATION OF
 NEC 250 AND 300 WIRING METHODS. PLEASE SPECIFY
 CONDUCTOR AND CONDUIT TYPE ON RISER DIAGRAM. ( PANEL B
 , C , PE. )
 PLEASE SHOW SERVICE EQUIPMENT ON SITE / FLOOR PLANS
 PROVIDE STEAMER AND ELEVATOR SPECS DON'T SEE ON PANEL
 SCHEDULE ?
 SUB PANEL PE IS MARKED AS CIRCUIT 19 , 21 DOESN'T
 CORRESPOND WITH PANEL SCHEDULE 33, 35 ?
  
  
 406.12 TAMPER-RESISTANT RECEPTACLES FOR DWELLING UNITS.
 IN ALL AREAS SPECIFIED IN 210.52, ALL NONLOCKING-TYPE
 125-VOLT, 15- AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
 210.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 (A) DWELLING UNITS. ALL 120-VOLT, SINGLE PHASE, 15- AND
 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED
 IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION
 ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS
 SHALL
 BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER,
 COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF
 THE
 BRANCH CIRCUIT.
 SMOKE ALARMS / CARBON MONOXIODE REQUIRED PER
 RESIDENTIAL CODE SECTIONS 314 / 315
 FBC ER C405 75 % OF LIGHTING SHALL BE HIGH EFFICIENCY .
 ALL RECCESSED FIXTURE SHALL BE
 IC RATED AND SEALED TYPE.
 GARARGE DOOR OPENERS AREN'T GFCI PROTECTED NEC 210.8
 NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT.
 DISCONNECTS FOR COMPRESSOR UNITS SEEM TO BE BEHIND
 EQUIPMENT NEC 110.26 WORKING SPACE CLEARANCE.
  
  

Review Stop G GAS REVIEW
Rev No 4 Status N Date 2016-05-18 Cont ID  
Sent By gjohnson Date 2016-05-18 Time 11:08 Rev Time 0.00
Received By gjohnson Date 2016-05-18 Time 11:08 Sent To  
Notes
2016-05-18 11:28:024TH REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. FIRST SECTION OF GALVANIZED PIPE IS UNDERSIZED IT
 SHOULD BE 11/2IN. PER FBC FUEL GAS TABLE 402.4(5)
  
 2. THE SECTION OF CSST FROM SECOND BRANCH TO GALVANIZED
 AT EXTERIOR IS UNDERSIZED IT SHOULD BE 11/2IN PER FBC
 FUEL GAS TABLE 402.4(18)
  
 3. TABLE REFERENCED 402.4(20) IS FOR 1/2 POUND SYSTEM
 ITSHOULD BE TABLE 402.4(22) FOR 2LB. SYSTEM ALSO ADD
 TABLE 402.4(5) AND 402.4(18)
  
 4. SIZE PIPE DOWN STREAM OF STEPDOWN REGULATOR. PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 5.SUBMIT COMBUSTION AIR CALCULATIONS FOR THE RANGE ,
 FIRE PLACES AND GENERATOR IF ENCLOSED. PER FBC-2014
 FUEL GAS CODE SEC. 304.
  
 A GAS PLAN HAS NOT BEEN APPROVED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN APPROVED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2016-04-29 Cont ID  
Sent By gjohnson Date 2016-04-29 Time 14:22 Rev Time 0.00
Received By gjohnson Date 2016-04-29 Time 14:22 Sent To  
Notes
2016-04-29 14:25:163RD REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS: IT APPEARS GAS COMMENTS FROM SECOND
 REVIEW WERE NOT ADDRESSED
  
 2ND REQUEST
 1. SHT. P103 SYSTEM IS INDICATED AS 2PSI PLEASE SHOW
 STEP DOWN REGULATORS FOR ALL APPLIANCES SHALL COMPLY
 WITH FBC FUEL GAS SEC. 410.1-410.2
 2. SHT. P103 PE PIPING IS NOT ALLOWED TO BE INSTALLED
 IN A STRUCTURE PER FBC FUEL GAS SEC. 404.17.1
 3.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
 THE RESPONSE YOU GAVE ON FIRST REVIEW SEE P103 DOES NOT
 COMPLY
 4.SHT. P103 SHOW LENGTH OF PIPE FROM METER TO FIRST
 BRANCH PER .FUEL GAS CODE SEC. 402.4.1.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-03-23 Cont ID  
Sent By gjohnson Date 2016-03-23 Time 10:51 Rev Time 0.00
Received By gjohnson Date 2016-03-18 Time 16:47 Sent To  
Notes
2016-03-23 11:08:292ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. SHT. P103 SYSTEM IS INDICATED AS 2PSI PLEASE SHOW
 STEP DOWN REGULATORS FOR ALL APPLIANCES SHALL COMPLY
 WITH FBC FUEL GAS SEC. 410.1-410.2
 2. SHT. P103 PE PIPING IS NOT ALLOWED TO BE INSTALLED
 IN A STRUCTURE PER FBC FUEL GAS SEC. 404.17.1
 3.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
 THE RESPONSE YOU GAVE ON FIRST REVIEW SEE P103 DOES NOT
 COMPLY
 4.SHT. P103 SHOW LENGTH OF PIPE FROM METER TO FIRST
 BRANCH PER .FUEL GAS CODE SEC. 402.4.1.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-12-04 Cont ID  
Sent By tklarge Date 2015-12-04 Time 13:05 Rev Time 0.00
Received By tklarge Date 2015-12-04 Time 12:57 Sent To  
Notes
2015-12-04 12:56:481) THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT.
 2) INDICATE ON THE PLANS THE PSI OF THE GAS SYSTEM. IF
 IT IS A 2 PSI SYSTEM, SHOW THE LOCATION OF ALL THE
 REGULATORS ON THE PLAN.
 3) WHAT DOES THE TERM "ACTARIS B42" REPRESENT ON THE
 GAS RISER?
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL THE GAS
 APPLIANCES/EQUIPMENT. THE APPLIANCES/EQUIPMENT SHALL BE
 LISTED AND LABELED PER 2014 FBCR SEC. G2404.3.
 5) THE PLANS SHOW PE PIPE BEING INSTALLED UNDER THE
 STRUCTURE. PLASTIC PIPE SHALL BE INSTALLED OUTDOORS
 UNDERGROUND ONLY PER 2014 FBCR SEC. G2415.17.1.
 6) METAL PIPING IS NOT PERMITTED UNDERGROUND UNLESS
 APPROVED PROTECTIVE COATINGS OR WRAPPINGS ARE FACTORY
 APPLIED. ZINC COATINGS SHALL NOT BE DEEMED ADEQUATE
 PROTECTION FOR GAS PIPING UNDERGROUND. 2014 FBCR
 SEC.G2415.11.
 7) SUBMIT THE CORRESPONDING EHD NUMBER FOR THE CSST PER
 2014 FBCR SEC. G2413 SIZING TABLES.
 8) SHOW THE TOTAL BTU LOAD OF THE GAS SYSTEMS ON THE
 PLAN. WPB AMEND. TO FBC SEC. 107.3.5.3.
 9) SHOW THE LENGTH OF ALL SECTIONS OF GAS PIPE
 INCLUDING RISERS AND SHORT SECTIONS OF PIPE. WPB AMEND.
 TO FBC SEC. 107.3.5.3.
 10) THE BTU LOAD OF EACH OUTDOOR FIREPLACE SHALL BE ON
 THE GAS RISER DIAGRAM. WPB AMEND. TO FBC SEC.
 107.3.5.3.
 11) SHT. P103 REFERS TO TABLE 402.2 (20). THERE IS NO
 SUCH TABLE IN THE CODE. CLARIFY.
 12) THERE IS NO 170 FT. ROW IN THE GAS TABLES. THE ROW
 TO BE USED IS THE 175 FT. ROW.REVISE THE PLAN NOTE .
 13) THE GENERATOR SHALL BE UL2200 COMPLIANT.
  
 A THOROUGH GAS REVIEW COULD NOT BE ACCOMPLISHED DUE TO
 THE LACK OF THE ABOVE INFORMATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2016-04-25 Cont ID  
Sent By destabro Date 2016-04-25 Time 16:05 Rev Time 0.00
Received By destabro Date 2016-04-25 Time 16:05 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-04-11 Cont ID  
Sent By fmittner Date 2016-04-11 Time 14:27 Rev Time 0.00
Received By fmittner Date 2016-04-11 Time 14:27 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-12-23 Cont ID  
Sent By fmittner Date 2015-12-23 Time 13:58 Rev Time 0.00
Received By fmittner Date 2015-12-23 Time 13:58 Sent To  
Notes
2015-12-23 13:59:35LAST BAY IS NOT A TRUE CARPORT, ONLY HAS DOOR REMOVED.
 SHALL BE OPEN ON SOUTH AND EAST SIDE AS WEL PER HPB
 APPROVALL. QUESTIONS, CONTACT FRIEDERIKE MITTNER AT
 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-05-20 Cont ID  
Sent By cpuell Date 2016-05-20 Time 13:01 Rev Time 0.00
Received By cpuell Date 2016-05-18 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-09 Cont ID  
Sent By mvaldes Date 2016-05-09 Time 13:52 Rev Time 0.00
Received By mvaldes Date 2016-04-13 Time 12:50 Sent To  
Notes
2016-05-06 11:26:11MVALDES'S DESK
2016-04-14 12:51:08R21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-11 Cont ID  
Sent By cpuell Date 2016-04-11 Time 14:31 Rev Time 0.00
Received By cpuell Date 2016-04-11 Time 14:26 Sent To  
Notes
2016-03-09 10:02:32R22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-05 Cont ID  
Sent By cpuell Date 2016-01-05 Time 08:16 Rev Time 0.00
Received By cpuell Date 2015-11-24 Time 13:13 Sent To  
Notes
2015-11-25 13:14:17R23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-03-28 Cont ID  
Sent By jgomez Date 2016-03-28 Time 17:50 Rev Time 0.00
Received By jgomez Date 2016-03-28 Time 17:50 Sent To  
Notes
2016-03-28 17:51:11$21.91 PAID. MU-2015-027501.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-29 Cont ID  
Sent By jgomez Date 2015-12-29 Time 15:00 Rev Time 0.00
Received By jgomez Date 2015-12-29 Time 15:00 Sent To  
Notes
2015-12-29 15:00:421- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-05-11 Cont ID  
Sent By jgomez Date 2016-05-11 Time 11:10 Rev Time 0.00
Received By jgomez Date 2016-05-11 Time 11:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-04-27 Cont ID  
Sent By jgomez Date 2016-04-27 Time 16:06 Rev Time 0.00
Received By jgomez Date 2016-04-27 Time 16:06 Sent To  
Notes
2016-04-27 16:10:53 
  
  
 NOTE: MECHANICAL REVIEW TO BE PASSED ONCE THE PLANS ARE
 SIGNED BY THE ENGINEER OF RECORD.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-28 Cont ID  
Sent By jgomez Date 2016-03-28 Time 17:59 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2016-03-28 18:30:32NEW SINGLE FAMILY RESIDENCE (R3), SECOND MECHANICAL
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- RE-SUBMITTED SET OF PLANS IS MISSING DRAWINGS M201
 AND M301. NEED COMPLETE SET OF DRAWINGS. SEC. 107.2.1
 CITY AMENDMENTS.
  
 2- MECHANICAL ENGINEER OF RECORD TO PROVIDE EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 RESPONSE: RESPONSE LETTER STATES THAT "SECTION R403 IS
 NOT VALID CODE REFERENCE FOR ENERGY CODE". THIS IS
 INCORRECT. SEE SEC. R403.6.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 ALSO, THE ENGINEER IS CITING EXCEPTION #2 OF SEC.
 R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014) TO DO A SUMMARY SHEET. THIS IS INCORRECT ALSO.
 THE EXCEPTION #2 APPLIES TO ATTACHED SINGLE AND
 MULTIPLE FAMILY UNITS ONLY. THIS IS A DETACHED SINGLE
 FAMILY RESIDENCE. THEREFORE, NEED TO PROVIDE COMPLETE
 EQUIPMENT SIZING CALCULATIONS USING AN APPROVED HEATING
 AND COOLING CALCULATION METHODOLOGIES BASED ON THE
 BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE
 BUILDING AND PROVIDE THE MANUFACTURER AND MODEL NUMBER
 OF THE OUTDOOR AND INDOOR UNITS AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 3- SHEET M302: UPDATE THE CODES AND STANDARDS
 INFORMATION. THE CURRENT CODE IS THE FBC-RESIDENTIAL,
 5TH EDITION (2014) NOT 2010 FBC.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE RE-SUBMITTED SET. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-30 Cont ID  
Sent By jgomez Date 2015-12-30 Time 18:57 Rev Time 0.00
Received By jgomez Date 2015-12-30 Time 07:33 Sent To E
Notes
2015-12-30 19:04:35NEW SINGLE FAMILY RESIDENCE (R3), MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- MECHANICAL PLANS SUBMITTED DON'T PROVIDE ANY
 INFORMATION FOR THE FIREPLACES CHIMNEYS AND VENTS AS
 REQUIRED BY CHAPTER 18 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). MECHANICAL ENGINEER OF RECORD TO PROVIDE
 COMPLETE INFORMATION.
  
 2- MECHANICAL ENGINEER OF RECORD TO PROVIDE EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 3- SHEET M302: UPDATE THE CODES AND STANDARDS
 INFORMATION. THE CURRENT CODE IS THE FBC-RESIDENTIAL,
 5TH EDITION (2014) NOT 2010 FBC.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE RE-SUBMITTED SET. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2015-12-29 Cont ID  
Sent By jgomez Date 2015-12-29 Time 07:57 Rev Time 0.00
Received By jgomez Date 2015-12-29 Time 07:57 Sent To  
Notes
2015-12-29 07:59:46E-MAIL SAMANTHA HILL ([email protected]) WHEN PERMIT IS
 ISSUED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-04-29 Cont ID  
Sent By gjohnson Date 2016-04-29 Time 14:25 Rev Time 0.00
Received By gjohnson Date 2016-04-29 Time 11:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-03-18 Cont ID  
Sent By gjohnson Date 2016-03-18 Time 16:21 Rev Time 0.00
Received By gjohnson Date 2016-03-18 Time 16:21 Sent To  
Notes
2016-03-18 16:47:26 
 PLUMBING COMMENTS;
  
 1.YOUR RESPONSE TO PREVIOUS COMMENT #2 DOES NOT COMPLY
 WITH CODE . WHERE YOU HAVE A HYDRAULIC ELEVATOR PIT YOU
 SHALL COMPLY WITH FBC PL SEC. 1003.4 OIL SEPARATORS
 REQUIRED.
 AT REPAIR GARAGES, CAR-WASHING FACILITIES, AT FACTORIES
 WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND
 IN HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE
 INSTALLED INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR
 FLAMMABLE WASTES SHALL BE DISCHARGED BEFORE EMPTYING
 INTO THE BUILDING DRAINAGE SYSTEM OR OTHER POINT OF
 DISPOSAL.
  
 EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN
 HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM
 IS INSTALLED.
  
 2. SHT.104 A RECIRCULATION SYSTEM IS REQUIRED TO COMPLY
 WITH FBC PL SEC. 607.2 HOT OR TEMPERED WATER SUPPLY TO
 FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
  
 3. SHT. P102 SOIL STACK FOR BATHROOMS 208+212 SHALL
 CONNECT TO BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP
 108 TO COMPLY WITH FBCR SEC. P3108.1
  
 4. SHT P104 THE COLD WATER MAIN SUPPLY APPEARS TO BE
 UNDERSIZED SHALL COMPLY WITH FBCR SEC. P2903
  
 5. SHT,P102 THE MODEL ON THE MANUFACTURE SPEC FOR
 TANKLESS HEATER DOES NOT MATCH THE ONE ON P104 PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-04 Cont ID  
Sent By tklarge Date 2015-12-04 Time 12:12 Rev Time 0.00
Received By tklarge Date 2015-12-03 Time 11:52 Sent To  
Notes
2015-12-04 11:38:271) SHT.H2 SHOWS STRUCTURAL DETAILS AND PLANS AND THESE
 PLANS ARE SIGNED AND SEALED BY A LANDSCAPE ARCHITECT
 WHICH VIOLATES FL. STATUTE 481.103. PLEASE CLARIFY.
 2) INDICATE ON THE PLANS IF THE ELEVATOR IS A TRACTION
 TYPE OR A HYDRAULIC TYPE. IF OF A HYDRAULIC NATURE AND
 THERE IS AN ELEVATOR PIT, THEN AN OIL SEPARATOR SHALL
 BE REQUIRED.
 3) SUBMIT A WATER RISER FOR REVIEW PER WPB AMEND. TO
 FBC SEC. 107.3.5.3.
 4) SHT. P 100 - SHOW THE CONTINUATION OF THE 3"SANITARY
 LINE ON THE PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 5) CLEANOUTS ARE REQUIRED IN THE BASE OF THE STACKS TO
 THE 2ND FLOOR. 2014 FBCR SEC.P3005.2.6.
 6) SUBMIT MANUF. SPECIFICATIONS FOR THE TANKLESS WATER
 HEATERS..WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. P100 - THERE IS A 3 INCH RISER TO THE 2ND FLOOR
 IN THE DINING ROOM WALL ( RM.#119) THAT IS NOT SHOWN ON
 THE SANITARY RISER. CLARIFY.
 8) CLEANOUTS ARE REQD. IN BOTH RISERS IN THE ISLAND
 SINK. SEC. P3112 2014 FBCR.
 9) SHT. P102 - BATH 202 CANNOT DISCHARGE INTO THE VENT
 STACK FOR POWDER ROOM 102. FBCR SEC. P3108.4.
 10) SHT. P102 - BATH 208 CANNOT DISCHARGE INTO THE VENT
 STACK FOR BATH 108. FBCR SEC. P3108.4.
 11) SHT. P102 - BATH 220 - THE TUB AND WATER CLOSET ARE
 NOT VENTED. 2014 FBCR SEC. P3201.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2016-05-13 Cont ID  
Sent By jgomez Date 2016-05-13 Time 10:46 Rev Time 0.00
Received By jgomez Date 2016-05-13 Time 09:20 Sent To  
Notes
2016-05-13 10:47:39ROOFING APPROVED WITH PROVISO:
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R5
 SUBMITTED: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR SELECTED ASSEMBLY W-55 AS REQUIRED BY
 NOTE #8 ON PAGE 2 OF 76. NEED CALCULATIONS TO MEET THE
 DESIGNER PRESSURES REQUIRED BY SEC. R301
 FBC-RESIDENTIAL.
  
  
 APPROVED PRODUCT APPROVALS:
 A) SEALOFLEX WATERPROOFING SYSTEM OVER CONCRETE DECK
 NOA 15-0406.05.
  
 B) MODIFIED BITUMEN ROOF FL5680-R15.
  
 C) ROOFING TILES FL7804-R8.
  
 D) ROOF TILE ADHESIVE FL6332-R5.
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2016-04-27 Cont ID  
Sent By jgomez Date 2016-04-27 Time 17:17 Rev Time 0.00
Received By jgomez Date 2016-04-27 Time 17:16 Sent To  
Notes
2016-04-27 17:20:391- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R5
 SUBMITTED: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR SELECTED ASSEMBLY W-55 AS REQUIRED BY
 NOTE #8 ON PAGE 2 OF 76. NEED CALCULATIONS TO MEET THE
 DESIGNER PRESSURES REQUIRED BY SEC. R301
 FBC-RESIDENTIAL. (REPEAT COMMENT).
  
  
 APPROVED PRODUCT APPROVALS:
 A) SEALOFLEX WATERPROOFING SYSTEM OVER CONCRETE DECK
 NOA 15-0406.05.
  
 B) MODIFIED BITUMEN ROOF FL5680-R15.
  
 C) ROOFING TILES FL7804-R8.
  
 D) ROOF TILE ADHESIVE FL6332-R5.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-03-28 Cont ID  
Sent By jgomez Date 2016-03-28 Time 17:55 Rev Time 0.00
Received By jgomez Date 2016-03-28 Time 17:55 Sent To  
Notes
2016-03-28 17:58:51NEW SINGLE FAMILY RESIDENCE (R3), ROOFING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED. AND,
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE CALCULATED DESIGN
 PRESSURES.
  
 RESPONSE: THE SELECTED ASSEMBLY (W-55) FROM FLORIDA
 PRODUCT APPROVAL FL5680-R15 IS GOOD FOR -60PSF. NEED TO
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR NAIL
 ENHANCEMENT AT PERIMETER AND CORNER AREAS AS REQUIRED
 BY NOTE #8 ON PAGE 2 OF 76 OF PRODUCT APPROVAL
 SUBMITTED.
 NOTE: FORM 100 SUBMITTED IS FOR PBC BUILDING
 DEPARTMENT. THIS IS NOT USED BY THE CITY OF WPB.
  
 B) MODIFIED MEMBRANE THAT IS DESIGNED TO RECEIVE THE
 FINISH MATERIAL SPECIFIED ON PLANS FOR THE TERRACES AND
 BALCONIES. NOTE: CHECK DESIGN PRESSURES FOR SELECTED
 ASSEMBLY. SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE
 REQUIRED.
  
 RESPONSE: ACCORDING TO CONDITIONS OF USE SEC. 5.2 OF
 ICC ESR-2467 REPORT SUBMITTED, THIS PRODUCT IS FOR
 INTERIOR USE ONLY. NEED PRODUCT APPROVAL FOR EXTERIOR
 USE AND NEED TO CONSIDER THE WIND LOADS.
  
 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-12-30 Cont ID  
Sent By jgomez Date 2015-12-30 Time 18:31 Rev Time 0.00
Received By jgomez Date 2015-12-30 Time 18:31 Sent To  
Notes
2015-12-30 18:50:00 
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 C) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED. AND,
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE CALCULATED DESIGN
 PRESSURES.
  
 D) MODIFIED MEMBRANE THAT IS DESIGNED TO RECEIVE THE
 FINISH MATERIAL SPECIFIED ON PLANS FOR THE TERRACES AND
 BALCONIES. NOTE: CHECK DESIGN PRESSURES FOR SELECTED
 ASSEMBLY. SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE
 REQUIRED.
  
 2- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  

Review Stop Z ZONING
Rev No 4 Status P Date 2016-05-20 Cont ID  
Sent By fmittner Date 2016-05-20 Time 09:22 Rev Time 0.00
Received By fmittner Date 2016-05-20 Time 09:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2016-04-25 Cont ID  
Sent By destabro Date 2016-04-25 Time 15:59 Rev Time 0.00
Received By destabro Date 2016-04-25 Time 15:59 Sent To  
Notes
2016-04-25 16:05:13PROPOSED GATE EXCEEDS 4 FEET IN HEIGHT WITHIN FRONT
 SETBACK, PER ZONING & LAND DEVELOPMENT REGULATIONS,
 SECTION 904-32(B)1. FAILED LAST TIME FOR SAME REASON;
 REVISION NOT ADDRESSED IN RESPONSE LETTER. - DLE

Review Stop Z ZONING
Rev No 2 Status F Date 2016-04-11 Cont ID  
Sent By fmittner Date 2016-04-11 Time 14:26 Rev Time 0.00
Received By fmittner Date 2016-04-11 Time 14:26 Sent To  
Notes
2016-04-11 14:26:44GATE EXCEEDS 4'-0" IN HEIGHT

Review Stop Z ZONING
Rev No 1 Status P Date 2015-12-23 Cont ID  
Sent By fmittner Date 2015-12-23 Time 13:59 Rev Time 0.00
Received By fmittner Date 2015-12-23 Time 13:59 Sent To  
Notes
***NONE***