| 2015-11-25 12:33:08 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15101010 |
| | W. P. B. PERMIT: 15050530 UNDER THE 2010 FBC |
| | ADD: 500 BELVEDERE RD. |
| | CONT: SOURCE REFRIGERATION |
| | TEL: (904)612-3627 |
| | E-MAIL: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. NOV. 25/2015 |
| | ACTION: DENIED |
| | |
| | 1) STRUCTURAL CALCULATIONS BY CHARLES MOSS FOR HILL |
| | PHOENIX, JOB PUBLIX 500 BELVEDERE RD. STORE # 1491 ROOF |
| | TOP MECHANICAL CENTER 9'-6" X 58'-0" X 8'-11". ONLY THE |
| | FIRST PAGE OF THE DOCUMENT IS SIGNED AND SEALED, NO |
| | INDEX SHEET LISTING HOW MANY PAGES ARE COVERED BY THE |
| | COVERSHEET. FLORIDA ADMINISTRATIVE STATUTE |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| | COVERED UNDER THE COVER SHEET OR INDEX SHEET. |
| | |
| | 2) THERE IS NO DOCUMENT OF THE MECHANICAL CENTER TO THE |
| | ROOF TOP CURB. IN THE SUBMITTAL PACKAGE FOR THE 831 |
| | VILLAGE BLVD THERE WAS? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED |
| | |
| | 3) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (C) PANEL WALLS, WALL LOUVERS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES NO REPORTS |
| | SUBMITTED. |
| | |
| | 4) NO INFORMATION AS TO THE PREMIER SEVERE WINDSTORM |
| | RATED FLOOR & FRAME WAS SUBMITTED NOR THE NEED TO |
| | INSTALL A NEW DOOR THAT MEETS THE WIND PRESSURES AS WAS |
| | REQUIRED WITH THE UNIT INSTALLED AT 831 VILLAGE. PLEASE |
| | PROVIDE LITERATURE AS TO WHICH DOOR AND HARDWARE WITH |
| | ASSOCIATED PRESSURES . |
| | PLEASE PROVIDE THE TEST REPORT IN COMPLIANCE WITH 2010 |
| | FBC-B 1715.3. I DO NOT SEE WHERE PREMIER DOORS HAS ANY |
| | PRODUCT LISTED WITH MIAMI-DADE OR FLORIDA WEBSITE. WE |
| | WILL REVIEW ANY REPORTS FROM A NATIONALLY RECOGNIZED |
| | AGENCY. WE DO SEE ICC REPORTS OR THE OLDER LEGACY |
| | REPORTS. |
| | NOTE PREMIER PRODUCTS HAS REAPPLIED FOR A FLORIDA |
| | APPROVAL # 17460 IT IS STILL APPLIED FOR PRINT OUT THE |
| | COVERSHEET CIRCLE THE DOOR TO BE INSTALLED AND PROVIDE |
| | THE INSTALLATION INSTRUCTIONS. |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | SHOP DRAWING STAMP OF APPROVED. |
| | |
| | 6) THE BIG ISSUE IS THIS UNIT WAS BUILT OUT OF STATE, |
| | NOT UNDER ANY STATE APPROVAL SYSTEM WHERE THERE IS A |
| | 3RD PARTY SYSTEM PROVIDING CERTIFICATION THAT THIS UNIT |
| | COMPLIES WITH THE 2010 FBC FAMILY OF CODES. IF YOU HAVE |
| | A 3RD PARTY WHO IS INDEPENDENT THAT IS GOING TO CERTIFY |
| | THE STRUCTURE INCLUDE THIS IN THE NEXT SUBMISSION. |
| | PLEASE NOTE HWC HAS SENT DOWN A FLORIDA LICENSED |
| | INSPECTOR TO INSPECT BOTH MECHANICAL UNITS THE 831 |
| | VILLAGE BLVD AND 500 BELVEDERE RD JOB. PLEASE SUBMIT |
| | THE INSPECTION REPORT FOR CODE COMPLIANCE AS WELL AS |
| | THE PERSONS FLORIDA INSPECTORS LICENSE (BN) NUMBER. |
| | |
| | THERE WERE FIELD CORRECTIONS MADE WHICH WILL REQUIRE |
| | THE 3RD PARTY CERTIFICATION, AND NOT UNDER THE MODULAR |
| | BUILDING PROGRAM. HWC IS WELL AWARE OF THE ISSUES AT |
| | HAND AND WILL NEED TO BE CONTACTED FOR THE ADDITIONAL |
| | PAPERWORK. |
| | |
| | 7) A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |