Plan Review Details - Permit 15110977
Plan Review Stops For Permit 15110977
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-05 Cont ID  
Sent By jwitmer Date 2016-02-05 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2016-02-05 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-09 Cont ID  
Sent By jwitmer Date 2015-12-09 Time 07:45 Rev Time  
Received By jwitmer Date 2015-12-09 Time 06:45 Sent To  
Notes
2015-12-09 07:45:49BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110977
 ADD: 3111 45TH ST.
 CONT: DAKENNA DEVELOPMENT
 TEL: 904-245-1847
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. DEC. 09/2015
 ACTION: DENIED
  
 1A) THE COVERSHEET T-1 LIST THE 2010 FBC AS THE CODE
 THE PLANS WERE DESIGNED TOO. PLEASE BE AWARE THAT ON
 JUNE 30TH 2015 THE 5TH EDITION OF THE FLORIDA BUILDING
 CODE (2014 FBC) WAS ADOPTED STATEWIDE. PLEASE UPDATE
 PLANS TO THE CURRENT CODE.
  
 1B) IS THIS A CHANGE OF OCCUPANCY? 2014 FBC-EXISTING
 BUILDING:
 506.1 SCOPE. CHANGE OF OCCUPANCY PROVISIONS APPLY WHERE
 THE ACTIVITY IS CLASSIFIED AS A CHANGE OF OCCUPANCY AS
 DEFINED IN CHAPTER 2.
  
 506.2 APPLICATION. CHANGES OF OCCUPANCY SHALL COMPLY
 WITH THE PROVISIONS OF CHAPTER 10.
  
 2) SHEET A-1 WILL NEED TO SHOW COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE:
  
 2A) 226.1 GENERAL. WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION,
 WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN
 EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
  
 2B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2C) SHEET A-3.1 SHOWS THE ACCESSIBLE WHEELCHAIR TABLE
 NOT USE. PLEASE SHOW COMPLIANCE WITH 902.3 HEIGHT. THE
 TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE 28
 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 3) PLEASE PROVIDE WHERE CODE COMPLIANCE WITH SECTION
 227.2 OF THE 2014 FBC-ACCESSIBILITY CODE CAN BE MET.
 227.2 CHECK-OUT AISLES. WHERE CHECK-OUT AISLES ARE
 PROVIDED, CHECK-OUT AISLES COMPLYING WITH 904.3 SHALL
 BE PROVIDED IN ACCORDANCE WITH TABLE 227.2.
  
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 4) SHEET M-1 NOTE # 14 INDICATES THE CONDENSING UNITS
 FOR THE WALK IN COOLERS TO BE UNDER SEPERATE PERMIT AND
 TO BE MOUNTED ON THE ROOF. PLEASE NOTE COMPLIANCE WITH
 2014 FBC-B TABLE 1509.6.5 CLEARANCE BELOW RAISED ROOF
 MOUNTED MECHANICAL UNITS.
  
 5) BUILDING HEIGHT UNKNOWN, MAY NEED TO PROVIDE
 COMPLIANCE WITH 2014 FBC-B 1509.6.4 EQUIPMENT AND
 APPLIANCES ON ROOFS OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
  
 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-11 Cont ID  
Sent By albarran Date 2016-02-11 Time 18:36 Rev Time 0.00
Received By albarran Date 2016-02-11 Time 18:15 Sent To I
Notes
2016-02-11 18:40:05ALL PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED. LIGHT POWER DENSITY ALLOWANCE
 CHARTS PROVIDED IN SUBMITTAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-28 Cont ID  
Sent By albarran Date 2015-12-28 Time 17:20 Rev Time 0.00
Received By albarran Date 2015-12-28 Time 16:03 Sent To I
Notes
2015-12-28 17:21:18THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE CURRENT APPLICABLE CODES ARE: FLORIDA FIRE
 PREVENTION CODE: 2012, NFPA 1: 2012, NFPA 70, (NEC):
 2011, NFPA 72: 2010, NFPA 101: 2012, FBC- 5TH EDITION:
 2014. CORRECT SHEET T1 ACCORDINGLY.
 2. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL
 EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO
 REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED
 TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS.
 3. THERE IS A CONFLICT BETWEEN THE NOMINAL VOLTAGES
 MENTIONED IN EQUIPMENT POWER GUIDE AND THE DEVICE
 REQUIREMENTS OF THE GENERAL REQUIREMENTS NOTE G.
 4. ONLY YOUR KEYED NOTE 7 ADDRESSES A TIME CLOCK. FBC-E
 HAS MANDATORY SWITCHING REQUIREMENTS FOR COMMERCIAL
 LIGHTING. REVISE YOU DRAWINGS TO COMPLY.
 5. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS.
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-01-29 Cont ID  
Sent By pleduc Date 2016-01-29 Time   Rev Time 0.00
Received By pleduc Date 2016-01-29 Time 13:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-02 Cont ID  
Sent By GJT Date 2015-12-02 Time   Rev Time  
Received By   Date 2015-12-02 Time   Sent To  
Notes
2015-12-02 09:59:48PLEASE PROVIDE SUITE NUMBER
  
 SENT TO BO3

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2016-02-24 Time 15:39 Sent To  
Notes
2016-02-24 15:39:40RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-19 Cont ID  
Sent By ccole Date 2016-02-19 Time 09:25 Rev Time 0.00
Received By ccole Date 2016-02-17 Time 13:20 Sent To  
Notes
2016-02-17 13:20:56RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-11 Cont ID  
Sent By albarran Date 2016-02-11 Time 18:42 Rev Time 0.00
Received By albarran Date 2016-01-26 Time 15:51 Sent To  
Notes
2016-02-12 08:54:112/12/16 THOUGH THIS PERMIT PASSED THE ELECTRICAL REVIEW
 THERE ARE MECHANICAL ISSUED WHICH NEED ATTENTION.
 STEPHANIE CLINTON NOTIFIED VIA EMAIL. FILE SENT TO
 LARGE DENIED DRAWER "D". MA
2016-02-11 18:44:472/11/16 PASSED ELECTRICAL REVIEW BUT STILL NEEDS
 ADDITIONAL MECHANICAL CORRECTIONS. RUNNER NOTIFIED VIA
 EMAIL. SENT FILE TO LARGE DENIED BIN "D". MA
2016-01-26 15:51:48B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2015-12-28 Cont ID  
Sent By albarran Date 2015-12-28 Time 17:33 Rev Time 0.00
Received By albarran Date 2015-11-24 Time 15:43 Sent To  
Notes
2015-12-28 17:34:3012/28/15 FAILED MULTIPLE TRADE REVIEWS. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "D". MA
2015-11-24 15:43:41B03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-02-05 Cont ID  
Sent By jwitmer Date 2016-02-05 Time   Rev Time 0.00
Received By jwitmer Date 2016-02-05 Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-09 Cont ID  
Sent By jwitmer Date 2015-12-09 Time 07:51 Rev Time 0.00
Received By jwitmer Date 2015-12-09 Time 07:51 Sent To  
Notes
2015-12-09 07:51:11BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-03-01 Cont ID  
Sent By ccole Date 2016-03-01 Time 16:39 Rev Time 0.00
Received By ccole Date 2016-03-01 Time 16:39 Sent To  
Notes
2016-03-01 16:41:56MECHANICAL PROVISO
 PERMIT #15110977
 3/1/16
  
 1) SIGNED AND SEALED AC LOAD CALCULATIONS SHALL BE
 SUBMITTED FOR REVIEW PRIOR TO 1ST MECHANICAL
 INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-02-19 Cont ID  
Sent By ccole Date 2016-02-19 Time 08:44 Rev Time 0.00
Received By ccole Date 2016-02-19 Time 08:44 Sent To  
Notes
2016-02-19 08:59:483RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110977
 2/19/16
  
 1) THE SUMMARY AC COOLING AND HEATING CALCULATIONS
 SUBMITTED BY ARIZADO DESIGN ARE NOT APPROVED- REFER TO
 SECTION C403.2.1 EXCEPTION FBC-14 ENERGY CONSERVATION:
 THE SUMMARY SHEET MUST BE SIGNED AND SEALED BY A
 FLORIDA LICENSED ENGINEER.
 2) ARIZADO DESIGN IS REQUIRED TO PLACE A SIGNATURE AND
 SEAL ON ALL PLAN SHEETS WHERE HIS TITLE BLOCK APPEARS,
 AND MUST ALSO BE A FLORIDA LICENSED DESIGN PROFESSIONAL
 IN ORDER TO DO SO- REFER TO SECTIONS 61G1-16.003,
 61G1-16.004, & 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE. OTHERWISE THE TITLE BLOCK MUST BE REMOVED FROM
 THE PLAN SHEETS.
 3) THE PREVIOUSLY REQUESTED TIE-DOWN ENGINEERING FOR
 THE ROOF TOP CONDENSERS HAS NOT BEEN PROVIDED- PLEASE
 COMPLY.
 4) THE SUBMITTED ENERGY CALCULATIONS ARE INDICTING
 RTU'S IN THE COMPLIANCE DATA, HOWEVER THE PLANS ARE
 INDICATING SPLIT SYSTEMS- PLEASE CORRECT, AND PLEASE
 LIST THE EFFICENCY RATINGS AND COOLING AND HEATING
 CAPACITIES OF THE SYSTEMS ON THE AC SCHEDULE ON SHEET
 M-2.
 5) M-2: THE AC EQUIPMENT SCHEDULE IS INDICATING AN
 EXCESSIVE AMOUNT OF OUTSIDE AIR CFM'S (948) FOR THE
 SELECTED 5-TON SYSTEM THAT HAS A CAPACITY OF 2000 CFM'S
 OF SUPPLY AIR. PLEASE NOTE THAT THE THE TOTAL OUTSIDE
 AIR FOR THESE TYPE OF SYSTEMS PER STANDARD ENGINEERING
 PRACTICES IS GENERALLY NO MORE THAN 20% OF THE THE
 TOTAL SUPPLY AIR- OTHERWISE TYPICALLY A DEDICATED
 OUTSIDE AIR UNIT IS SELECTED, OR AN ERV IS ADDED TO THE
 SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-02-05 Cont ID  
Sent By ccole Date 2016-02-05 Time 14:26 Rev Time 0.00
Received By ccole Date 2016-02-05 Time 14:26 Sent To  
Notes
2016-02-05 14:37:072ND MECHANICAL REVIEW
 PERMIT #15110977
 2/5/16
  
 1) THE REVISED PLAN INDICATES NEW AC SYSTEMS: A)
 PROVIDE AC COOLING AND HEATING CALCULATIONS AND WIND
 LOAD TIE-DIOWN ENGINEERING FOR MOUNTING THE EXTERIOR
 CONDENSERS EITHER ON EXISTING OR NEW ROOF STANDS.
 2) THE REVISED O/A SCHEDULES IS INDICATING 948 CFM'S OF
 O/A FOR THE DINING ROOM AND 471 CFM'S O/A FOR THE
 KITCHEN, BUT THE AC SCHEDULE IS INDICATING AHU-1 & 2
 WILL ONLY PROVIDE 585 CFM'S O/A AIR. THERE APPEARS TO
 BE AN ERROR IN SIZING OR CALCULATIONS HERE.
 3) IN ACCORDANCE WITH SECTION C403.2.5.1 FBC-14 ENERGY
 CONSERVATION THE C02 DETECTORS SHALL BE LOCATED IN THE
 DINING ROOM FOR DEMAND CONTROLLED VENTILATION PURPOSES.
 .
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-03 Cont ID  
Sent By ccole Date 2015-12-03 Time 14:01 Rev Time 0.00
Received By ccole Date 2015-12-03 Time 14:01 Sent To  
Notes
2015-12-03 14:35:011ST REVIEW 2014 MECHANICAL
 PERMIT #15110977
 12/3/15
  
 1) THE WEST PALM BEACH CONSTRUCTION SERVICES DEPARTMENT
 REQUIRES A SEPARATE PERMIT FOR INSTALLATION OF THE
 WALK-IN BOXES AND REFRIGERATION SYSTEMS. PLEASE PLACE A
 NOTE ON THE PLANS ACCORDINGLY TO CLARIFY.
 2) IN ACCORDANCE WITH SECTION 202 FBC-14 EXISTING
 BUILDING CODE, THE PROPOSED PROJECT IS DEFINED AS A
 CHANGE OF OCCUPANCY AND SHALL BE IN COMPLIANCE WITH THE
 FBC-14 ENERGY CONSERVATION CODE. PLEASE SEE SECTIONS
 C101.4.4 AND C101.5.1, AND SUBMIT EITHER ENERGY
 EFIICENCY COMPLIANCE FORM C402-2014 (PRESCRIPTIVE
 COMPLIANCE) OR ENERGY GAUGE FORM 506-2014 (PERFORMANCE
 COMPLIANCE).
 3) SHEET M-1: REVISE KEYED NOTE #5 AND THE PLUMBING
 DRAWINGS TO SHOW CONDENSATE PIPING FROM THE AHU'S
 DISCHARGING TO AN APPROVED DISPOSAL PLACE- PLEASE NOTE
 THAT THE CONDENSATE IS PROHIBITED TO DISCHARGE INTO THE
 CITY SANITARY SEWER PER SECTION 90-126 WPB CODE OF
 ORDINANCES.
 4) M-1: A MOTORIZED OR GRAVITY DAMPER IS REQUIRED FOR
 THE FRESH AIR DUCTS IN COMPLIANCE WITH SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION. PLEASE REVISE
 NOTE #17 ACCORDINGLY.
 5) M-1 CLARIFY HOW AIR IS RETURNED TO AHU-1. THE UNIT
 IS LOCATED ABOVE THE LADIES ROOM CEILING. THE ELEVATION
 DRAWING ON SHEET A-6 INDICATE THE RESTROOM CEILINGS GO
 TO THE BOTTOM OF THE DECK: PLEASE CLARIFY.
 6) M-1: PROVIDE A DETAIL INDICATING HOW THE AIR HANDLER
 WILL BE HUNG FROM THE DECK ABOVE.
 7) M-1: INDICATE HOW THE DUCT SMOKE DETECTORS WILL BE
 SUPERVISED PER SECTION 606.4.1, AND IF THE ACTUATION OF
 A SINGLE DETECTOR WILL SHUT BOTH SYSTEMS DOWN.
 8) M-2: SEE MECHANICAL SECIFICATIONS NOTE G AND
 INDICATE ON THE PLAN THE LOCATIONS OF THE C02 AND
 TEMPERATURE SENSORS. PLEASE ALSO CORRECT THE NOTE
 INDICATING "RTU" TO ACCURATELY INDICATE SPLIT SYSTEM
 AC.
 9) M-2: THE REMARK AT THE BOTTOM OF THE O.S.A
 CALCULATIONS SCHEDULE IS INACCURATE: A) THIS PROJECT
 SHALL BE IN COMPLIANCE WITH THE FBC-14 MECHANICAL-
 REMOVE THE REFERENCE TO THE IMC CODE. B) FOOTNOTE A IS
 NOT APPLICABLE TO DINING ROOM VENTILATION AS SHOWN
 INTABLE 403.3. REVISE THE CALCULATIONS ACCORDINGLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-01-30 Cont ID  
Sent By tklarge Date 2016-01-30 Time 09:19 Rev Time 0.00
Received By tklarge Date 2016-01-30 Time 09:10 Sent To  
Notes
2016-01-30 09:21:11PROVISO
 GREASE INTERCEPTOR SIZING CALCULATIONS SHALL BE
 SUBMITTED FOR REVIEW PRIOR TO INTERCEPTOR INSTALLATION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-08 Cont ID  
Sent By tklarge Date 2015-12-08 Time 07:36 Rev Time 0.00
Received By tklarge Date 2015-12-07 Time 06:30 Sent To  
Notes
2015-12-07 14:09:361) SHT. A-5 - DETAILS #1 & #2 - THE HEIGHT OF THE
 ACCESSIBLE WATER CLOSET SHALL BE 17"-19" AFF MEASURED
 TO THE TOP OF THE SEAT PER 2014 FBC-ACCESS. SEC.604.4.
 2) SHT. A-5 - THE TOILET PAPER DISPENSER SHALL BE
 LOCATED 7"-9" IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. 2014 FBC-ACCESS.
 SEC.604.7.
 3) SHT. A-5- DETAILS #1 & #2 - THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE PER THE
 2014 FBC-ACCESS. SEC. 609.4.
 4) SHT. M-1-NOTE #5 NOTES THE CONDENSATE TO DISCHARGE
 TO THE SANITARY. CITY ORDINANCE SEC. 90-126 ( B) (5).
 5) SUBMIT MANUF. SPECIFICATIONS/INSTALL MANUAL AND A
 DETAIL ON THE ZURN GREASE TRAP.WPB AMEND. TO FBC
 SEC.107.2.1.
 6) THE WATER FILTER SYSTEM SHALL BE PROTECTED AGAINST
 CONTAMINATION IN ACCORDANCE WITH 2014 FBC- PLUMBING
 SEC.608.3.
 7) THE WATER SUPPLY CONNECTION TO BEVERAGE DISPENSERS,
 COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS
 SHALL BE PROTECTED AGAINST BACKFLOW BY A BACKFLOW
 PREVENTER CONFORMING TO ASSE 1022 PER 2014 FBC-PLUMBING
 SEC.608.16.1, 608.16.10.
 8) SUBMIT A DETAIL OF THE CO2 FILL BOX. WPB AMEND. TO
 FBC SEC. 107.2.1.
 9) A SAMPLING PORT SHALL BE INSTALLED ON THE EFFFLUENT
 LINE OF THE GREASE TRAP ON THE EXTERIOR OF THE BUILDING
 IN ACCORDANCE WITH CITY OF WPB ENGINEERING STANDARD
 DRAWING GS-7.1. I HAVE PLACED A LINK AT THE END OF THE
 REVIEW COMMENTS.
 10) SHT. P-3 - DOMESTIC WATER RISER SHOWS A 1/2" WATER
 LINE INCREASING TO 3/4" AT THE WATER HEATER. THE
 MINIMUM SIZE WATER SUPPLY TO THE WATER HEATER SHALL BE
 3/4".
 11) SHOW THE PIPE SIZE OF THE NEW CONNECTION OF THE
 WATER MAIN TO THE EXISTING ON THE WATER RISER.WPB
 AMEND. TO FBC SEC. 107.2.1.
 12) SHT.P-3-DETAIL "A" - THE WATER RISER SHOWS A 1/2"
 COLD WATER LINE SUPPLYING 1" LINES TO THE WATER CLOSETS
 IN THE RESTROOMS & SUPPLYING 3/4/" LINES TO OTHER
 FIXTURES. CLARIFY.
 13) THE SANITARY RISER SHOWS 2 FLAT DRY VENTS FOR THE
 GREASE INTERCEPTOR. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE PER THE 2014 FBC-PLUMBING
 SEC.905.3.
 14) THE SANITARY RISER DIAGRAM SHOWS ALL THE FIXTURES
 AS BEING CONNECTED TO THE HORIZONTAL DRAINS BELOW THE
 SLAB. SHOW THE FIXTURES ON THE SANITARY RISER AS THEY
 WILL BE INSTALLED ( WALL MOUNTED WATER CLOSETS,
 LAVATORIES CONNECTED TO STACKS, ETC.) WPB AMEND. TO FBC
 SEC. 107.3.5.1.3.
 15) CLEANOUTS ARE REQUIRED IN THE BASE OF EACH WASTE OR
 SOIL STACK PER FBC-PLBG. SEC.708.3.4.
 16) SIZE ALL VENTS & SECTIONS OF THE VENT SYSTEM ON THE
 SANITARY RISER. SEE VENT FOR RESTROOMS AND HANDSINK.WPB
 AMEND. TO FBC SEC. 107.2.1.
 17) SIZE ALL SECTIONS OF THE UNDERSLAB PIPING AND THE
 HORIZONTAL DRAIN FOR THE RESTROOMS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 18) SHOW THE 3/4" VENT FOR THE FLOW CONTROL FOR THE
 GREASE TRAP AS NOTED ON SHT. P-1, NOTE #17.
  
 GREASE TRAP DETAIL LINK: HTTP://WPB.ORG/ENGINEERING/WP-
 CONTENT/UPLOADS/SITES/7/2012/05/GS-7-AND-7_1.PDF
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved