Plan Review Details - Permit 15110968
Plan Review Stops For Permit 15110968
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-12-02 Cont ID  
Sent By cranford Date 2015-12-02 Time   Rev Time 1.00
Received By mgonzale Date 2015-12-02 Time   Sent To I
Notes
2015-12-02 16:58:42CALL 811 BEFORE DIGGING.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-02-16 Cont ID  
Sent By tklarge Date 2016-02-16 Time 02:40 Rev Time 0.00
Received By tklarge Date 2016-02-13 Time 07:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-02-05 Cont ID  
Sent By tklarge Date 2016-02-05 Time 05:30 Rev Time 0.00
Received By tklarge Date 2016-02-05 Time 04:17 Sent To  
Notes
2016-02-05 05:26:161)THE PLANS SHOW A LINE LENGTH OF 30 FT. OF PE PIPE TO
 THE BUILDING AND ALSO A LINE LENGTH OF 60 FT. TO THE
 500 KW FUTURE GENERATOR WHICH IS CLOSER. CLARIFY.
 2) THERE IS A SECTION OF PIPE MISSING FROM THE GAS
 RISER FROM THE 1 1/2" PE PIPE UP TO THE 5 PSI REGULATOR
 NEAR THE EXTERIOR OF THE BUILDING. CLARIFY.
 3) SHT. P-2 - THERE IS A NOTE ON THE GAS RISER THAT
 CALLS OUT A 5 PSI TO 14" W.C.REGULATOR BUT NOTHING IS
 SHOWN. CLARIFY.
 4) P-1 - DRAWING NOTE #30 IS NOT SHOWN ON SHT.P-1.
 CLARIFY.WHAT TYPE OF PIPING IS GOING TO THE 100KW
 GENERATOR? SHOW ON GAS RISER.
 5) SHT. P-1 - NOTE #4 - THE PLUMBING DESIGN DATA TABLE
 NOTES A MINIMUM OF 1 1/2" GAS LINE TO THE 100KW
 EMERGENCY GENERATOR BUT THE GAS RIISER AND SHT. P-1
 SHOWS 1". CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-11-25 Cont ID  
Sent By tklarge Date 2015-11-25 Time 06:44 Rev Time 0.00
Received By tklarge Date 2015-11-25 Time 04:57 Sent To  
Notes
2015-11-25 05:39:501) SHT. P-1 - IF THE LOCATION OF THE METER HAS BEEN
 CHANGED, SHOW THE NEW DISTANCE FOR THE PE PIPE FROM THE
 METER TO THE THE FIRST STEP DOWN REGULATOR.ENSURE PIPE
 SIZE IS ADEQUATE FOR THE LOAD. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SHOW THE TYPE OF PIPE, SIZE, PSI OF THE GAS AND THE
 LENGTH OF ALL PIPE SECTIONS FOR THE UNDERGROUND PE
 PIPEFROM THE GAS METER TO THE FIRST STEP DOWN
 REGULATOR. THIS INFO CAN BE FOUND ON THE ORIGINAL GAS
 PLAN.
 3) SHOW THE BTU LOAD AND SIZE THE GAS LINE FOR THE
 FUTURE STANDBY GENERATOR. THE BTU LOAD SHALL CORRELATE
 WITH THE BTU LOAD ON P-1.
 4) THE BTU LOAD FOR THE EMERGENCY GENERATOR ON SHT. P-2
 SHOWS 860 CFH AND SHT. P-1 SHOWS 1,353 CFH.
 CLARIFY.ENSURE THE PIPE IS SIZED FOR THE MAXIMUM BTU
 LOAD BASED ON THE TOTAL DEVELOPED LENGTH FROM THE POINT
 OF DELIVERY.
 5) SIZE ALL PIPE SECTIONS FROM THE GAS METER UP TO
 WHERE THE GAS PIPING PENETRATES THE EXTERIOR WALL OF
 THE STRUCTURE. ALSO, SIZE ALL PIPE SECTIONS AND
 INDICATE TYPE OF PIPE AND PSI OF THE GAS TO THE FUTURE
 STANDBY GENERATOR. SHOW THE LOCATION OF ALL REGULATORS.
 6) SHT. C09 - CLEARLY SHOW THE LOCATION OF THE GAS
 METER. THE PLAN SHOWS "PROPOSED 1 1/2 POLY GAS
 SERVICE". THIS IS VAGUE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-16 Cont ID  
Sent By tklarge Date 2016-02-16 Time 02:40 Rev Time 0.00
Received By tklarge Date 2016-02-12 Time 14:45 Sent To  
Notes
2016-02-12 14:45:23RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-05 Cont ID  
Sent By tklarge Date 2016-02-05 Time 05:30 Rev Time 0.00
Received By tklarge Date 2016-01-22 Time 09:51 Sent To  
Notes
2016-01-25 09:51:37RESUB ROUTED TO ENGINEERING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-03 Cont ID  
Sent By lmarchan Date 2015-12-03 Time 16:04 Rev Time 0.00
Received By lmarchan Date 2015-11-24 Time 14:21 Sent To  
Notes
2015-11-24 14:22:02REVISION ROUTED TO TKLARGE

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-11-25 Cont ID  
Sent By tklarge Date 2015-11-25 Time 06:44 Rev Time 0.00
Received By tklarge Date 2015-11-25 Time 06:44 Sent To  
Notes
2015-11-25 06:44:56REVISION IS FOR GAS ONLY.