Plan Review Details - Permit 15110949
Plan Review Stops For Permit 15110949
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-12-05 Cont ID  
Sent By shill Date 2015-12-05 Time 13:30 Rev Time 0.00
Received By shill Date 2015-12-05 Time 13:30 Sent To  
Notes
2015-12-05 13:31:42FBC 5TH EDITION ACCESSIBILITY 604.4, SEAT HEIGHT OF A
 WATER CLOSET ABOVE THE FINISHED FLOOR SHALL BE 17"
 MINIMUM AND 19" MAXIMUM MEASURED TO THE TOP OF THE
 SEAT.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-12-17 Cont ID  
Sent By mvaldes Date 2015-12-17 Time 17:53 Rev Time 0.00
Received By mvaldes Date 2015-12-17 Time 17:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-11-30 Cont ID  
Sent By J.Walker Date 2015-11-30 Time   Rev Time 0.35
Received By   Date 2015-11-25 Time   Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-28 Cont ID  
Sent By ccole Date 2015-12-28 Time 11:23 Rev Time 0.00
Received By ccole Date 2015-12-23 Time 08:38 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-18 Cont ID  
Sent By shill Date 2015-12-18 Time 11:00 Rev Time 0.00
Received By shill Date 2015-11-23 Time 09:49 Sent To  
Notes
2015-11-24 09:49:56C08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-28 Cont ID  
Sent By ccole Date 2015-12-28 Time 11:23 Rev Time 0.00
Received By ccole Date 2015-12-28 Time 11:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-07 Cont ID  
Sent By ccole Date 2015-12-07 Time 10:54 Rev Time 0.00
Received By ccole Date 2015-12-07 Time 10:43 Sent To  
Notes
2015-12-07 11:10:041ST REVIEW 2014 MECHANICAL
 PERMIT #15110949
 12/7/15
  
 1) EXHAUST HAS BEEN PROVIDED FOR THE ENCLOSED TOILET
 ROOM, HOWEVER NO EXHAUST IS SHOWN FOR THE REMAINDER OF
 THE MEN'S ROOM CONTAINING THE URINALS- REFER TO TABLE
 403.3 AND PROVIDE A MINIMUM 50 CFM FAN.
 2) A DUCT SMOKE DETECTOR IS REQUIRED TO BE INSTALLED IN
 THE RETURN AIR SYSTEM OF THE RTU- SEE SECTION 606.2.1.=
 3) PROVIDE A MEANS OF RETUN AIR FROM THE HALLWAY BACK
 TO THE RTU- SEE SECTION 601.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-12-06 Cont ID  
Sent By tklarge Date 2015-12-06 Time 06:42 Rev Time 0.00
Received By tklarge Date 2015-12-06 Time 06:03 Sent To  
Notes
***NONE***