Plan Review Details - Permit 15110885
Plan Review Stops For Permit 15110885
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-31 Cont ID  
Sent By jwitmer Date 2015-12-31 Time 16:13 Rev Time 0.00
Received By jwitmer Date 2015-12-31 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-11-24 Cont ID  
Sent By jwitmer Date 2015-11-24 Time 06:45 Rev Time 0.00
Received By jwitmer Date 2015-11-24 Time 06:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-27 Cont ID  
Sent By mvaldes Date 2016-01-27 Time 11:01 Rev Time 0.00
Received By mvaldes Date 2016-01-27 Time 11:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-10 Cont ID  
Sent By mvaldes Date 2015-12-10 Time 08:19 Rev Time 0.00
Received By mvaldes Date 2015-12-10 Time 08:19 Sent To  
Notes
2015-12-10 08:27:361ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED WITHIN 450 MM (18 IN.) OF THE TOP OF
 A
 SHOW WINDOW FOR EACH 3.7 LINEAR M (12 LINEAR FT) OR
 MAJOR
 FRACTION THEREOF OF SHOW WINDOW AREA MEASURED
 HORIZONTALLY
 AT ITS MAXIMUM WIDTH.
  
 600.5 BRANCH CIRCUITS.
 (A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL BUILDING
 AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET IN AN
 ACCESSIBLE
 LOCATION AT EACH ENTRANCE TO EACH TENANT SPACE FOR SIGN
 OR
 OUTLINE LIGHTING SYSTEM USE. THE OUTLET(S) SHALL BE
 SUPPLIED
 BY A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES
 NO OTHER LOAD. SERVICE HALLWAYS OR CORRIDORS SHALL NOT
 BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
  
 110.16 ARC-FLASH HAZARDWARNING. ELECTRICAL EQUIPMENT,
 SUCH AS SWITCHBOARDS, PANELBOARDS, INDUSTRIAL CONTROL
 PANELS,
 METER SOCKET ENCLOSURES, AND MOTOR CONTROL CENTERS,
 THAT
 ARE IN OTHER THAN DWELLING UNITS, AND ARE LIKELY TO
 REQUIRE
 EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE
 WHILE
 ENERGIZED SHALL BE FIELD MARKED TO WARN QUALIFIED
 PERSONS OF
 POTENTIAL ELECTRIC ARC FLASH HAZARDS. THE MARKING SHALL
 BE
 LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED
 PERSONS BEFORE
 EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF
 THE EQUIPMENT.
  
 408.4 FIELD IDENTIFICATION REQUIRED.
 (A) CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY
 CIRCUIT
 AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS
 TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE
 IDENTIFICATION
 SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT
 TO
 BE DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT
 CONTAIN
 UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE
 DESCRIBED
 ACCORDINGLY. THE IDENTIFICATION SHALL BE INCLUDED IN
 A CIRCUIT DIRECTORY THAT IS LOCATED ON THE FACE OR
 INSIDE OF THE
 PANEL DOOR IN THE CASE OF A PANELBOARD, AND LOCATED AT
 EACH
 SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD. NO CIRCUIT
 SHALL
 BE DESCRIBED IN A MANNER THAT DEPENDS ON TRANSIENT
 CONDITIONS
 OF OCCUPANCY.
 (B) SOURCE OF SUPPLY. ALL SWITCHBOARDS AND PANELBOARDS
 SUPPLIED BY A FEEDER IN OTHER THAN ONE- OR TWO-FAMILY
 DWELLINGS
 SHALL BE MARKED TO INDICATE THE DEVICE OR EQUIPMENT
 WHERE THE POWER SUPPLY ORIGINATES.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-30 Cont ID  
Sent By scaldero Date 2015-12-30 Time 13:47 Rev Time 0.00
Received By scaldero Date 2015-12-30 Time 13:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-11-30 Cont ID  
Sent By scaldero Date 2015-11-30 Time 16:18 Rev Time 0.00
Received By scaldero Date 2015-11-30 Time 16:09 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-27 Cont ID  
Sent By shill Date 2016-01-27 Time 11:16 Rev Time 0.00
Received By shill Date 2015-12-21 Time 16:12 Sent To  
Notes
2015-12-21 16:12:31B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-10 Cont ID  
Sent By cpuell Date 2015-12-10 Time 10:50 Rev Time 0.00
Received By cpuell Date 2015-11-20 Time 13:03 Sent To  
Notes
2015-11-20 13:06:48B08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-12-29 Cont ID  
Sent By ccole Date 2015-12-29 Time 07:37 Rev Time 0.00
Received By ccole Date 2015-12-29 Time 07:37 Sent To  
Notes
2015-12-29 07:38:49MECHANICAL PROVISO
 PERMIT #15110885
 12/29/15
  
 1) SEPARATE PERMITS REQUIRED FOR ANY ALTERATIONS MADE
 TO THE EXISTING AC SYSTEMS IN SUITES 110 AND 112.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-24 Cont ID  
Sent By ccole Date 2015-11-24 Time 15:39 Rev Time 0.00
Received By ccole Date 2015-11-24 Time 15:38 Sent To  
Notes
2015-11-24 15:58:421ST REVIEW 2014 MECHANICAL
 PERMIT #15110885
 11/14/15
  
 1) REFER TO SECTION 809.2 FBC-14 MECHANICAL: ALTERED
 EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62. PLEASE PROVIDE THE CALCULATIONS
 ON THE PLAN, AND SHOW THE REQUIRED AMOUNTS OF O/A CFM'S
 REQUIRED AND THE AMOUNT BEING PROVIDED.
 2) PROVIDE A SCOPE OF WORK OUTLINE ON THE PLAN FOR
 MECHANICAL WITH CORRESPONDING DRAWINGS AND DETAILS
 INDICATING ALL NECESSARY ALTERATIONS TO THE EXISTING AC
 SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  