| Notes |
| 2015-11-20 09:08:16 | ****PROVISO**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 5TH EDITION 2014 | | | | | | TILE, RCU250, LATICRETE 125 SOUND & CRACK ADHESIVE ON A | | | 7.5" SLAB PROPOSED | | | | | | TESTED RCU250 ON 8" SLAB STC=56 | | | TESTED RCU250 ON 8" SLAB IIC = 54 | | | | | | TESTED LATICRETE ON 6" SLAB (NO UNDERLAYMENT) IIC= 44 | | | DELTA OF 17 | | | | | | ASTM E-84 (FLAME SPREAD) TEST REPORT HAS BEEN EMAILED | | | TO RECORDS | | | | | | PROVISO - ASSEMBLY INSTALLED TO BE CONSISTENT WITH | | | DOCUMENTS PROVIDED: | | | RCU 250, LATICRETE SPECTRALOCK PRO PREMIUM GROUT, | | | LATICRETE 125 SOUND AND CRACK ADHESIVE | | | | | | INSPECTION #143 REQUIRED AFTER UNDERLAYMENT IS | | | INSTALLED | | | | | | | | | |
|
|