Plan Review Details - Permit 15110831
Plan Review Stops For Permit 15110831
Review Stop E ELECTRICAL
Rev No 6 Status P Date 2017-03-24 Cont ID  
Sent By vperez Date 2017-03-24 Time 09:05 Rev Time 0.00
Received By vperez Date 2017-03-24 Time 09:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2017-03-08 Cont ID  
Sent By vperez Date 2017-03-08 Time 08:39 Rev Time 0.00
Received By vperez Date 2017-03-08 Time 08:39 Sent To  
Notes
2017-03-08 08:40:46SAME COMMENT NOT ADDRESSED; NOTE THAT SHEET E001 IS THE
 ONE THAT NEEDS TO BE CORRECTED
  
  
 PLEASE NOTE THAT THE REVISED SHEET E002LS WHICH IS IN
 COMPLIANCE DOES NOT MATCH OR COORELATE WITH SHEET E001
 RISER DIAGRAM. SHEET E001 STILL SHOWS PANEL GDP FEEDING
 FIRE PUMP. PLEASE CORRECT
  
 V. PEREZ

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2017-02-07 Cont ID  
Sent By vperez Date 2017-02-07 Time 10:49 Rev Time 0.00
Received By vperez Date 2017-02-07 Time 10:49 Sent To  
Notes
2017-02-07 10:52:06PLEASE NOTE THAT THE REVISED SHEET E002LS WHICH IS IN
 COMPLIANCE DOES NOT MATCH OR COORELATE WITH SHEET E001
 RISER DIAGRAM. SHEET E001 STILL SHOWS PANEL GDP FEEDING
 FIRE PUMP. PLEASE CORRECT
  
 V. PEREZ

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-12-05 Cont ID  
Sent By vperez Date 2016-12-05 Time 07:42 Rev Time 0.00
Received By vperez Date 2016-12-05 Time 07:42 Sent To  
Notes
2016-12-05 07:43:082ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 REPEAT COMMENTS:
  
 1. PLEASE SUBMIT REVISED DRAWINGS FOR THE GENERATOR TO
 COMPLY WITH THE REQUIREMENTS OF THE NEC 2008. SHOULD
 YOU HAVE ANY QUESTION PLEASE CONTACT PHIL PETTY, CHIEF
 ELECTRICAL INSPECTOR REGARDING THIS MATTER.
 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-10-21 Cont ID  
Sent By vperez Date 2016-10-21 Time 09:06 Rev Time 0.00
Received By vperez Date 2016-10-21 Time 09:06 Sent To  
Notes
2016-10-21 09:20:38INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SUBMIT REVISED DRAWINGS FOR THE GENERATOR TO
 COMPLY WITH THE REQUIREMENTS OF THE NEC 2008. SHOULD
 YOU HAVE ANY QUESTION PLEASE CONTACT PHIL PETTY, CHIEF
 ELECTRICAL INSPECTOR REGARDING THIS MATTER.
 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-11-25 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-02-13 Cont ID  
Sent By pleduc Date 2017-02-13 Time   Rev Time 0.00
Received By pleduc Date 2017-02-13 Time 14:36 Sent To  
Notes
2017-02-13 16:04:46PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PROVIDE THA APPLICABLE FIRE EXTINGUSHER PER NFPA 10,
 TAGGED AND CERTIFIED, FOR EQUIPEMNT INSIDE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-11-04 Cont ID  
Sent By pleduc Date 2016-11-04 Time 15:48 Rev Time 0.00
Received By wjolin Date 2016-10-28 Time 14:08 Sent To  
Notes
2016-10-28 14:13:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE WERE NO DRAWINGS IN THE FILE FOR REVIEW.
  
 PLEASE SUBMIT DETAILED DRAWINGS IN COMPLIANCE WITH THE
 REQUIRMENTS WITH NFPA 110 AND ALL OTHER APPLICBALE
 CODES.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-11-25 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-03-24 Cont ID  
Sent By vperez Date 2017-03-24 Time 09:05 Rev Time 0.00
Received By vperez Date 2017-03-24 Time 09:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-03-08 Cont ID  
Sent By vperez Date 2017-03-08 Time 08:41 Rev Time 0.00
Received By vperez Date 2017-03-08 Time 08:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-16 Cont ID  
Sent By cpuell Date 2017-02-16 Time 17:26 Rev Time 0.00
Received By cpuell Date 2017-01-26 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-05 Cont ID  
Sent By vperez Date 2016-12-05 Time 07:43 Rev Time 0.00
Received By vperez Date 2016-12-05 Time 07:43 Sent To  
Notes
2016-12-05 07:43:35EMAILED CP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-28 Cont ID  
Sent By pleduc Date 2016-10-28 Time   Rev Time 0.00
Received By pleduc Date 2016-10-14 Time 10:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-03-24 Cont ID  
Sent By vperez Date 2017-03-24 Time 09:05 Rev Time 0.00
Received By vperez Date 2017-03-24 Time 09:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2017-02-03 Cont ID  
Sent By eschneid Date 2017-02-03 Time 14:00 Rev Time 0.25
Received By eschneid Date 2017-02-03 Time 08:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2016-10-25 Cont ID  
Sent By eschneid Date 2016-10-25 Time 16:26 Rev Time 0.50
Received By eschneid Date 2016-10-25 Time 16:26 Sent To  
Notes
2016-10-25 16:34:25FAILED
  
 1) PROVIDE A SITE PLAN TO SHOW WHERE THE GENERATOR AND
 THE ATS WILL BE LOCATED.
  
 2) PROVIDE THE FULL HEIGHT OF THE GENERATOR PLUS CURB
 AND DETAILS ON HOW IT WILL BE SCREENED FOR ITS FULL
 HEIGHT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-11-25 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***